Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines (Metric)

SIGNIFICANCE AND USE
5.1 This is not a routine test. The values recorded are applicable only to the sewer being tested and at the time of testing.
SCOPE
1.1 This practice covers procedures for testing installed precast concrete pipe sewer lines using either water infiltration or exfiltration acceptance limits to demonstrate the integrity of the installed materials and construction procedure.  
1.2 This practice is the SI companion of Practice C969.  
Note 1: The owner shall specify the following: who will conduct, observe, and furnish labor, furnish material and measuring devices, and pay for the tests; who is responsible for determining local groundwater conditions; and which test is to be conducted, that is, an infiltration test or an exfiltration test.
Note 2: The user of this practice is advised that test criteria presented in this practice are similar to those in general use. Pipe, 600-mm diameter or larger, may be accepted by visual inspection when testing for infiltration.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Published
Publication Date
31-Dec-2018
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM C969M-19 - Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines (Metric)
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM C969M-19 - Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines (Metric)
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: C969M − 19
Standard Practice for
Infiltration and Exfiltration Acceptance Testing of Installed
1
Precast Concrete Pipe Sewer Lines (Metric)
This standard is issued under the fixed designation C969M; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 4. Summary of Practice
1.1 This practice covers procedures for testing installed 4.1 Determine the groundwater conditions surrounding the
precast concrete pipe sewer lines using either water infiltration section of sewer to be tested and select the type of test to be
or exfiltration acceptance limits to demonstrate the integrity of conducted.
the installed materials and construction procedure.
4.2 For the infiltration test, the amount of water leaking into
1.2 This practice is the SI companion of Practice C969. the sewer line is measured, and the rate of infiltration is
determined. If the rate is less than or equal to the allowable
NOTE 1—The owner shall specify the following: who will conduct,
limit, the section of sewer tested is acceptable.
observe, and furnish labor, furnish material and measuring devices, and
pay for the tests; who is responsible for determining local groundwater
4.3 For the exfiltration test, the sewer line is filled with
conditions; and which test is to be conducted, that is, an infiltration test or
water to the specified test head and the rate of water loss is
an exfiltration test.
determined. If the rate is less than or equal to the allowable
NOTE 2—The user of this practice is advised that test criteria presented
limit, the section of sewer tested is acceptable.
in this practice are similar to those in general use. Pipe, 600-mm diameter
or larger, may be accepted by visual inspection when testing for
infiltration.
5. Significance and Use
1.3 This standard does not purport to address all of the
5.1 This is not a routine test. The values recorded are
safety concerns, if any, associated with its use. It is the
applicable only to the sewer being tested and at the time of
responsibility of the user of this standard to establish appro-
testing.
priate safety, health, and environmental practices and deter-
mine the applicability of regulatory limitations prior to use.
6. Preparation of the Sewer Line
1.4 This international standard was developed in accor-
6.1 The sewer line shall be free of debris prior to testing.
dance with internationally recognized principles on standard-
6.2 The manholes, the ends of the branches, laterals, wyes,
ization established in the Decision on Principles for the
and stubs to be included in the test shall be plugged. All plugs
Development of International Standards, Guides and Recom-
shall be secured to prevent leakage blowout due to testing
mendations issued by the World Trade Organization Technical
pressure.
Barriers to Trade (TBT) Committee.
2. Referenced Documents
7. Procedure
2
2.1 ASTM Standards:
7.1 Infiltration Testing:
C822 Terminology Relating to Concrete Pipe and Related
7.1.1 Conduct testing from manhole to manhole or between
Products
more than two manholes. The length of main tested shall not
exceed 213 m.
3. Terminology
7.1.2 Stop all dewatering operations and allow the ground-
3.1 Definitions—For definitions of terms relating to concrete
water to return to its normal level. Infiltration testing shall not
pipe, see Terminology C822.
be used unless the groundwater level is at least 0.6 m above the
crown of the pipe for the entire length of the test section.
1
This practice is under the jurisdiction of ASTM Committee C13 on Concrete
7.1.3 Plug all pipe outlets discharging into the upstream
Pipe and is the direct responsibility of Subcommittee C13.09 on Methods of Test.
manhole.
Current edition approved Jan. 1, 2019. Published January 2019. Originally
7.1.4 Measure the groundwater elevation and determine the
approved in 1982. Last previous edition approved in 2017 as C969M – 17. DOI:
10.1520/C0969M-19.
average head over the test section.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
7.1.5 Measure infiltration leakage at the outlet of the test
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
section. Because leakage allowances are small, measurements
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. are best made by either timing the filling of a small container
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshoho
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: C969M − 17 C969M − 19
Standard Practice for
Infiltration and Exfiltration Acceptance Testing of Installed
1
Precast Concrete Pipe Sewer Lines (Metric)
This standard is issued under the fixed designation C969M; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This practice covers procedures for testing installed precast concrete pipe sewer lines using either water infiltration or
exfiltration acceptance limits to demonstrate the integrity of the installed materials and construction procedure.
1.2 This practice is the SI companion of Practice C969.
NOTE 1—The owner shall specify the following: who will conduct, observe, and furnish labor, furnish material and measuring devices, and pay for
the tests; who is responsible for determining local groundwater conditions; and which test is to be conducted, that is, an infiltration test or an exfiltration
test.
NOTE 2—The user of this practice is advised that test criteria presented in this practice are similar to those in general use. Pipe, 600-mm diameter or
larger, may be accepted by visual inspection when testing for infiltration.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2
2.1 ASTM Standards:
C822 Terminology Relating to Concrete Pipe and Related Products
3. Terminology
3.1 Definitions—For definitions of terms relating to concrete pipe, see Terminology C822.
4. Summary of Practice
4.1 Determine the groundwater conditions surrounding the section of sewer to be tested and select the type of test to be
conducted.
4.2 For the infiltration test, the amount of water leaking into the sewer line is measured, and the rate of infiltration is determined.
If the rate is less than or equal to the allowable limit, the section of sewer tested is acceptable.
4.3 For the exfiltration test, the sewer line is filled with water to the specified test head and the rate of water loss is determined.
If the rate is less than or equal to the allowable limit, the section of sewer tested is acceptable.
5. Significance and Use
5.1 This is not a routine test. The values recorded are applicable only to the sewer being tested and at the time of testing.
6. Preparation of the Sewer Line
6.1 The sewer line shall be free of debris prior to testing.
1
This practice is under the jurisdiction of ASTM Committee C13 on Concrete Pipe and is the direct responsibility of Subcommittee C13.09 on Methods of Test.
Current edition approved April 15, 2017Jan. 1, 2019. Published May 2017January 2019. Originally approved in 1982. Last previous edition approved in 20092017 as
C969M – 02C969M(2009). – 17. DOI: 10.1520/C0969M-17.10.1520/C0969M-19.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C969M − 19
6.2 The manholes, the ends of the branches, laterals, wyes, and stubs to be included in the test shall be plugged. All plugs shall
be secured to prevent leakage blowout due to testing pressure.
7. Procedure
7.1 Infiltration Testing:
7.1.1 Conduct testing from manhole to manhole or between more than two manholes. The length of main tested shall not exceed
213 m.
7.1.2 Stop all dewatering operations and allow the groundwater to return to its normal level. Infiltration testing shall not be used
unless the groundwater level is at least 0.6 m above the crown of the pipe for the entire length of the test section.
7.1.3 Plug all pipe outlets discharging into the upstream manhole.
7.1.4
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.