ASTM C1467/C1467M-00(2016)
(Specification)Standard Specification for the Installation of Molded Glass Fiber Reinforced Gypsum Parts
Standard Specification for the Installation of Molded Glass Fiber Reinforced Gypsum Parts
ABSTRACT
This specification covers the installation of molded glass fiber reinforced gypsum (GRG) parts. Molded glass fiber reinforced gypsum parts shall conform to environment conditions, substrate preparation, installation, and finishing requirements specified.
SCOPE
1.1 This specification covers the installation of molded glass fiber reinforced gypsum (GRG) parts.
1.2 The values stated in either inch-pound units or SI (metric) are to be regarded separately as the standard. Within the text, SI units are shown in brackets. The values stated in each shall be used independent of the other. Values from the two systems shall not be combined.
1.3 All references to finishes, dimensions and tolerances shall refer to the finished surface of the part.
1.4 The text of this standard references notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
General Information
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:C1467/C1467M −00 (Reapproved 2016)
Standard Specification for
the Installation of Molded Glass Fiber Reinforced Gypsum
1
Parts
This standard is issued under the fixed designation C1467/C1467M; the number immediately following the designation indicates the
year of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last
reapproval. A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 3.2 Definitions of Terms Specific to This Standard:
3.2.1 critical lighting, n—strong side lighting from natural
1.1 Thisspecificationcoverstheinstallationofmoldedglass
or artificial light sources.
fiber reinforced gypsum (GRG) parts.
3.2.2 primer, n—paint material formulated to fill the pores
1.2 The values stated in either inch-pound units or SI
and equalize the suction difference between the GRG part and
(metric) are to be regarded separately as the standard. Within
finishing compounds used.
the text, SI units are shown in brackets. The values stated in
each shall be used independent of the other. Values from the
4. Materials
two systems shall not be combined.
4.1 Molded GRG parts shall meet the requirements of
1.3 All references to finishes, dimensions and tolerances
Specification C1381.
shall refer to the finished surface of the part.
5. Environmental Conditions
1.4 The text of this standard references notes and footnotes
that provide explanatory material. These notes and footnotes
5.1 Room temperature shall be maintained at not less than
(excluding those in tables and figures) shall not be considered
40 °F [4 °C] during the installation of GRG parts except when
as requirements of the standard.
adhesive is used for the bonding or attachment of parts to each
other or to a substrate. For the bonding of adhesive and joint
2. Referenced Documents
treatment the room temperature shall be maintained at not less
2
2.1 ASTM Standards:
than 50 °F [10 °C] for 48 hours prior to application and
C11 Terminology Relating to Gypsum and Related Building
continuously thereafter until completely dry.
Materials and Systems
5.2 When a temporary heat source is used, the temperature
C754 Specification for Installation of Steel Framing Mem-
shall not exceed 95 °F [35 °C] in any given room or area.
bers to Receive Screw-Attached Gypsum Panel Products
5.3 InstalledGRGshallbeprotectedfromdirectexposureto
C840 SpecificationforApplicationandFinishingofGypsum
rain, snow, sunlight and other excessive weather conditions.
Board
C1007 Specification for Installation of Load Bearing (Trans-
NOTE 1—Installation in conditions of excessive humidity is not recom-
verse and Axial) Steel Studs and Related Accessories
mended.TheidealconditionstoinstallmoldedGRGpartsis70°F[21°C]
and 50 % RH.
C1381 Specification for Molded Glass Fiber Reinforced
Gypsum Parts
6. Substrate Preparation
3. Terminology
6.1 SubstratestoacceptGRGpartsshallbeinstalledstraight
1
and true within ⁄8 in. in 8 ft [3 mm in 2500 mm] and shall be
3.1 Definitions—Definitionsoftermsshallbeinaccordance
free of obstructions and interference that prohibits correct
with Terminology C11.
attachment of GRG parts.
6.2 Metal framing members shall be of the proper size and
1
This specification is under the jurisdiction of ASTM Committee C11 on
design for the intended use and shall be sufficient to properly
Gypsum and Related Building Materials and Systems and is the direct responsibility
ofSubcommitteeC11.03onSpecificationsfortheApplicationofGypsumandOther
support the installed GRG parts. Metal framing members shall
Products in Assemblies.
be installed in accordance with SpecificationC754 or C1007 as
Current edition approved Sept. 1, 2016. Published September 2016. Originally
required.
approved in 2000. Last previous edition approved in 2012 as C1467/C1467M – 00
(2012). DOI: 10.1520/C1467_C1467M-00R16.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or 7. Tolerances of Installed GRG Parts
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
7.1 Parts shall be installed plumb and not be out of line
Standards volume information, refer to the standard’s Document Summary page on
1
the ASTM website. more than 6 ⁄8 in. in 8 ft [3 mm in 2500 mm] in any direction.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
C1467/C1467M−00 (2016)
NOTE 2—GRG parts are furnished with a primer-ready surface.
7.2 The planar surface of any part shall not vary by more
1
than ⁄8 in. [3 mm] from the planar surface of any adjacent part.
10. Handling and Storage
7.3 GRG parts shall be installed so that the joints between
1
parts are not more than ⁄4 in. [6 mm] in width.
10.1 GRG parts shall be stored in a
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: C1467/C1467M − 00 (Reapproved 2012) C1467/C1467M − 00 (Reapproved
2016)
Standard Specification for
the Installation of Molded Glass Fiber Reinforced Gypsum
1
Parts
This standard is issued under the fixed designation C1467/C1467M; the number immediately following the designation indicates the
year of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last
reapproval. A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This specification covers the installation of molded glass fiber reinforced gypsum (GRG) parts.
1.2 The values stated in either inch-pound units or SI (metric) are to be regarded separately as the standard. Within the text, SI
units are shown in brackets. The values stated in each shall be used independent of the other. Values from the two systems shall
not be combined.
1.3 All references to finishes, dimensions and tolerances shall refer to the finished surface of the part.
1.4 The text of this standard references notes and footnotes that provide explanatory material. These notes and footnotes
(excluding those in tables and figures) shall not be considered as requirements of the standard.
2. Referenced Documents
2
2.1 ASTM Standards:
C11 Terminology Relating to Gypsum and Related Building Materials and Systems
C754 Specification for Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products
C840 Specification for Application and Finishing of Gypsum Board
C1007 Specification for Installation of Load Bearing (Transverse and Axial) Steel Studs and Related Accessories
C1381 Specification for Molded Glass Fiber Reinforced Gypsum Parts
3. Terminology
3.1 Definitions— Definitions of terms shall be in accordance with Terminology C11.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 critical lighting, n—strong side lighting from natural or artificial light sources.
3.2.2 primer, n—paint material formulated to fill the pores and equalize the suction difference between the GRG part and
finishing compounds used.
4. Materials
4.1 Molded GRG parts shall meet the requirements of Specification C1381.
5. Environmental Conditions
5.1 Room temperature shall be maintained at not less than 40 °F [4 °C] during the installation of GRG parts except when
adhesive is used for the bonding or attachment of parts to each other or to a substrate. For the bonding of adhesive and joint
treatment the room temperature shall be maintained at not less than 50 °F [10 °C] for 48 hours prior to application and continuously
thereafter until completely dry.
5.2 When a temporary heat source is used, the temperature shall not exceed 95 °F [35 °C] in any given room or area.
1
This specification is under the jurisdiction of ASTM Committee C11 on Gypsum and Related Building Materials and Systems and is the direct responsibility of
Subcommittee C11.03 on Specifications for the Application of Gypsum and Other Products in Assemblies.
Current edition approved March 1, 2012Sept. 1, 2016. Published June 2012September 2016. Originally approved in 2000. Last previous edition approved in 20062012
as C1467/C1467M – 00 (2006).(2012). DOI: 10.1520/C1467_C1467M-00R12. 10.1520/C1467_C1467M-00R16.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
C1467/C1467M − 00 (2016)
5.3 Installed GRG shall be protected from direct exposure to rain, snow, sunlight and other excessive weather conditions.
NOTE 1—Installation in conditions of excessive humidity is not recommended. The ideal conditions to install molded GRG parts is 70 °F [21 °C] and
50 % RH.
6. Substrate Preparation
1
6.1 Substrates to accept GRG parts shall be installed straight and true within ⁄8 in. in 8 ft [3 mm in 2500 mm] and shall be free
of obstructions and interference that prohibits correct attachment of GRG parts.
6.2 Metal framing members shall be of the proper size and design for the intended use and shall be sufficient to properly support
the installed GRG parts. Metal framing members shall be installed in accordance with Specification C754 or C1007 as required.
7. Tolerances of Installed GRG Parts
1
7.1 Parts shall be installed plumb and no
...