ASTM E2393-10
(Practice)Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers
Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers
SIGNIFICANCE AND USE
This practice is intended to provide a standard set of guidelines that are to be followed when conducting and reporting on inspections of installed fire resistive joint systems.
This practice is intended to provide a means to verify compliance of the installed fire resistive joint systems to the inspection documents.
This practice is not intended to provide a basis for selecting installers or products, or both.
This practice is not intended to establish any performance criteria of the inspected fire resistive joint systems.
SCOPE
1.1 This practice covers the establishment of procedures to inspect fire resistive joint systems, including methods for field verification and inspection.
1.2 This practice addresses all types of fire resistive joint systems and of perimeter joint protection.
Note 1—Fire resistive joint system and joint are defined in Test Method E1966.
Note 2—Perimeter joint protection is defined in Test Method E2307.
Note 3—Fire resistive joint systems include joints between two fire resistive assemblies, and perimeter joints between a fire resistive floor assembly and a non-fire-resistive wall assembly. The application of these systems are sometimes extended based on an evaluation to other types of construction.
1.3 This practice provides methods by which qualified inspectors verify that required fire resistive joint systems on a project have been installed and that their installations are in accordance with the inspection documents.
1.4 The values stated in inch-pound units are to be regarded as standard. No other units of measurement are included in this standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
1.6 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
General Information
Relations
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:E2393–10
Standard Practice for
On-Site Inspection of Installed Fire Resistive Joint Systems
1
and Perimeter Fire Barriers
This standard is issued under the fixed designation E2393; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope E631 Terminology of Building Constructions
E699 Practice for Evaluation of Agencies Involved in Test-
1.1 This practice covers the establishment of procedures to
ing, Quality Assurance, and Evaluating of Building Com-
inspect fire resistive joint systems, including methods for field
ponents
verification and inspection.
E1966 Test Method for Fire-Resistive Joint Systems
1.2 This practice addresses all types of fire resistive joint
E2307 Test Method for Determining Fire Resistance of
systems and of perimeter joint protection.
Perimeter Fire Barriers Using Intermediate-Scale, Multi-
NOTE 1—Fire resistive joint system and joint are defined in Test
story Test Apparatus
Method E1966.
2.2 Other Standard:
NOTE 2—Perimeter joint protection is defined in Test Method E2307.
3
UL 2079 Fire Tests of Fire Resistive Joints
NOTE 3—Fire resistive joint systems include joints between two fire
2.3 Other Documents:
resistive assemblies, and perimeter joints between a fire resistive floor
4
International Building Code
assembly and a non-fire-resistive wall assembly. The application of these
5
systems are sometimes extended based on an evaluation to other types of
NFPA 5000 Building Code
construction.
3. Terminology
1.3 This practice provides methods by which qualified
3.1 Definitions—Terms defined in Terminology E631, Ter-
inspectors verify that required fire resistive joint systems on a
minology E176, and Practice E699 will prevail for terms not
project have been installed and that their installations are in
defined in this document.
accordance with the inspection documents.
3.2 Definitions of Terms Specific to This Standard:
1.4 The values stated in inch-pound units are to be regarded
3.2.1 authorizing authority (AA)—the designated person, or
as standard. No other units of measurement are included in this
organization, or their duly authorized representative, charged
standard.
with the administration and enforcement of the provisions of
1.5 This standard does not purport to address all of the
this inspection document.
safety concerns, if any, associated with its use. It is the
responsibility of the user of this standard to establish appro-
NOTE 4—Examples of the AA include the responsible Architect, Engi-
priate safety and health practices and determine the applica-
neer, Building Owner, or their representatives.
bility of regulatory limitations prior to use.
3.2.2 authority having jurisdiction (AHJ)—the designated
1.6 The text of this standard references notes and footnotes
authority, or their duly authorized representative, charged with
which provide explanatory material. These notes and footnotes
the administration and enforcement of the local fire code or
(excluding those in tables and figures) shall not be considered
building code, or both.
as requirements of the standard.
3.2.3 accredited testing laboratory—a company engaged in
conducting testing and possesses a valid evaluation report for
2. Referenced Documents
testing services and is recognized by the AHJ.
2
2.1 ASTM Standards:
3.2.4 evaluation report—an approved document issued by
E176 Terminology of Fire Standards
the Model Code Body Evaluation Service or by the AHJ.
3.2.5 inspection document—any information provided to
1
This practice is under the jurisdiction of ASTM Committee E06 on Perfor- the inspector by the AA that is to be used as the basis for the
mance of Buildings and is the direct responsibility of Subcommittee E06.21 on
Serviceability.
Current edition approved Feb. 15, 2010. Published May 2010. Originally
3
approved in 2004. Last previous edition approved in 2009 as E2393 – 09. DOI: Available from Underwriters Laboratories (UL), Corporate Progress, 333
10.1520/E2393-10. Pfingsten Rd., Northbrook, IL 60062, http://www.ul.com.
2 4
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Available from International Code Council (ICC), 500 New Jersey Ave., NW,
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM 6th Floor, Washington, DC 20001-2070, http://www.iccsafe.org.
5
Standards volume information, refer to the standard’s Document Summary page on Available from National Fire Protection Association (NFPA), 1 Batterymarch
the ASTM website. Park, Quincy, MA 02169-7471, http://www.nfpa.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 194
...
This document is not anASTM standard and is intended only to provide the user of anASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:E2393–09 Designation: E2393 – 10
Standard Practice for
On-Site Inspection of Installed Fire Resistive Joint Systems
1
and Perimeter Fire Barriers
This standard is issued under the fixed designation E2393; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This practice covers the establishment of procedures to inspect fire resistive joint systems, including methods for field
verification and inspection.
1.2 This practice addresses all types of fire resistive joint systems and of perimeter joint protection.
NOTE 1—Fire resistive joint system and joint are defined in Test Method E1966.
NOTE 2—Perimeter joint protection is defined in Test Method E2307.
NOTE 3—Fire resistive joint systems include joints between two fire resistive assemblies, and perimeter joints between a fire resistive floor assembly
and a non-fire-resistive wall assembly. The application of these systems are sometimes extended based on an evaluation to other types of construction.
1.3 This practice provides methods by which qualified inspectors verify that required fire resistive joint systems on a project
have been installed and that their installations are in accordance with the inspection documents.
1.4 The values stated in inch-pound units are to be regarded as standard. No other units of measurement are included in this
standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
1.6 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes
(excluding those in tables and figures) shall not be considered as requirements of the standard.
2. Referenced Documents
2
2.1 ASTM Standards:
E176 Terminology of Fire Standards
E631 Terminology of Building Constructions
E699 Practice for Evaluation of Agencies Involved in Testing, Quality Assurance, and Evaluating of Building Components
E1966 Test Method for Fire-Resistive Joint Systems
E2307 Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale, Multi-story Test
Apparatus
2.2 Other Standard:
3
UL 2079 Fire Tests of Fire Resistive Joints
2.3 Other Documents:
4
International Building Code
5
NFPA 5000 Building Code
3. Terminology
3.1 Definitions—Terms defined in Terminology E631, Terminology E176, and Practice E699 will prevail for terms not defined
in this document.
3.2 Definitions of Terms Specific to This Standard:
1
This practice is under the jurisdiction ofASTM Committee E06 on Performance of Buildings and is the direct responsibility of Subcommittee E06.21 on Serviceability.
Current edition approved May 1, 2009. Published July 2009. Originally approved in 2004. Last previous edition approved in 2004 as E2393–04. DOI: 10.1520/E2393-09.
Current edition approved Feb. 15, 2010. Published May 2010. Originally approved in 2004. Last previous edition approved in 2009 as E2393 – 09. DOI:
10.1520/E2393-10.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from Underwriters Laboratories (UL), Corporate Progress, 333 Pfingsten Rd., Northbrook, IL 60062, http://www.ul.com.
4
Available from International Code Council (ICC), 500 New Jersey Ave., NW, 6th Floor, Washington, DC 20001-2070, http://www.iccsafe.org.
5
Available from National Fire Protection Association (NFPA), 1 Batterymarch Park, Quincy, MA 02169-7471, http://www.nfpa.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
E2393 – 10
3.2.1 authorizing authority (AA)—the designated person, or organization, or their duly authorized representative, charged with
the administration and enforcement of the provisions of this inspection document.
NOTE 4—Examples of the AA include the responsible Architect, Engineer, Building Owner, or their representatives.
3.2.2 authority having jurisdiction (AHJ)—the designated aut
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.