Standard Test Method for Determination of Glass Fiber Content in Glass Fiber Reinforced Concrete (GFRC) (Wash-Out Test)

SIGNIFICANCE AND USE
Glass fiber contents, determined by this test method, are useful for quality control of GFRC products to ensure that manufacturing equipment has been set up to deliver the correct proportions of glass fiber reinforcement in a GFRC composite.
SCOPE
1.1 This test method covers determination of the fiber content in an uncured, glass fiber reinforced concrete (GFRC) sample panel.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
30-Apr-2009
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM C1229-94(2009) - Standard Test Method for Determination of Glass Fiber Content in Glass Fiber Reinforced Concrete (GFRC) (Wash-Out Test)
English language
2 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C1229 − 94(Reapproved 2009)
Standard Test Method for
Determination of Glass Fiber Content in Glass Fiber
Reinforced Concrete (GFRC) (Wash-Out Test)
This standard is issued under the fixed designation C1229; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 5.2 Mesh Basket or Strainer, approximately 30 in. (493
cm ) capacity of woven stainless steel wire and mesh size
1.1 This test method covers determination of the fiber
3 1
between ⁄16 (4.5 mm) and ⁄16 (1.5 mm). Overall dimensions
content in an uncured, glass fiber reinforced concrete (GFRC)
must totally accept the test sample without any overhang, and
sample panel.
depth should be approximately twice the thickness of the test
1.2 The values stated in inch-pound units are to be regarded
sample. Gage and construction must be such that mesh
as standard. The values given in parentheses are mathematical
dimension cannot easily enlarge, allowing glass reinforcement
conversions to SI units that are provided for information only
to escape.
and are not considered standard.
5.3 Drying Chamber, an oven that can be set at 230 6 10°F
1.3 This standard does not purport to address all of the
(110 6 10°C), or a muffle furnace set at 900 6 10°F (482 6
safety concerns, if any, associated with its use. It is the
10°C).
responsibility of the user of this standard to establish appro-
5.4 Razor Knife, capable of 6 in. blade extension.
priate safety and health practices and determine the applica-
bility of regulatory limitations prior to use.
5.5 Splitting Jig, see Fig. 1.
2. Referenced Documents
6. Sampling
2.1 ASTM Standards:
6.1 Sampling should be in accordance with governing
C1228 Practice for Preparing Coupons for Flexural and
specifications.
Washout Tests on Glass Fiber Reinforced Concrete
7. Test Specimens
3. Terminology
7.1 Cut the coupons with a razor knife from a freshly cast,
3.1 Definitions:
damp,uncuredsamplepanel.Whencuttingoutthetestcoupon,
3.1.1 glass fiber reinforced concrete (GFRC)—a composi-
the sample panel shall have sufficient cohesiveness such that:
tion of cementitious material, aggregates, water, admixtures,
(a) a clean cut can be made without pulling out fibers from the
and alkali-resistant glass fiber.
test coupon or the adjacent material, and (b) that material is not
lost from the test coupon prior to determining mass.
4. Significance and Use
2 2
7.2 The test specimen shall be between 12 in. (78 cm ) and
4.1 Glass fiber contents, determined by this test method, are
2 2
16 in. (103 cm ).
useful for quality control of GFRC products to ensure that
manufacturing equipment has been set up to deliver the correct
8. Procedure
proportions of glass fiber reinforcement in a GFRC composite.
8.1 Cut two test coupons with a razor knife from a freshly
5. Apparatus
produced, damp, uncured sample panel as done in Practice
C1228. Place the coupons in a mesh basket of known mass
5.1 Balance, 2 kg capacity, sensitive to the nearest 0.1 g.
(W 1) and record the total mass (W2). The basket and contents
are held under a stream of running water and the composite is
This test method is under the jurisdiction ofASTM Committee C27 on Precast
worked with fingers to break it up. Take care to ensure that no
Concrete Products and is the direct responsibility of Subcommittee C27.40 on Glass
Fiber Reinforced Concrete.
glass is lost. See Fig. 2.
Current edition approved May 1, 2009. Published May 2009. Originally
8.2 When all the cement and fine aggregate (if any) are
approved in 1993. Last previous edition approved in 2001 as C1229 – 94(2001).
DOI: 10.1520/C1229-94R09.
washed aw
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.