ASTM C1467/C1467M-00(2006)
(Specification)Standard Specification for the Installation of Molded Glass Fiber Reinforced Gypsum Parts
Standard Specification for the Installation of Molded Glass Fiber Reinforced Gypsum Parts
ABSTRACT
This specification covers the installation of molded glass fiber reinforced gypsum (GRG) parts. Molded glass fiber reinforced gypsum parts shall conform to environment conditions, substrate preparation, installation, and finishing requirements specified.
SCOPE
1.1 This specification covers the installation of molded glass fiber reinforced gypsum (GRG) parts.
1.2 The values stated in either inch-pound units or SI (metric) are to be regarded separately as the standard. Within the text, SI units are shown in brackets. The values stated in each shall be used independent of the other. Values from the two systems shall not be combined.
1.3 All references to finishes, dimensions and tolerances shall refer to the finished surface of the part.
1.4 The text of this standard references notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C1467/C1467M – 00 (Reapproved 2006)
Standard Specification for
the Installation of Molded Glass Fiber Reinforced Gypsum
Parts
This standard is issued under the fixed designation C1467/C1467M; the number immediately following the designation indicates the
year of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last
reapproval. A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 3.2 Definitions of Terms Specific to This Standard:
3.2.1 critical lighting, n—strong side lighting from natural
1.1 Thisspecificationcoverstheinstallationofmoldedglass
or artificial light sources.
fiber reinforced gypsum (GRG) parts.
3.2.2 primer, n—paint material formulated to fill the pores
1.2 The values stated in either inch-pound units or SI
and equalize the suction difference between the GRG part and
(metric) are to be regarded separately as the standard. Within
finishing compounds used.
the text, SI units are shown in brackets. The values stated in
each shall be used independent of the other. Values from the
4. Materials
two systems shall not be combined.
4.1 Molded GRG parts shall meet the requirements of
1.3 All references to finishes, dimensions and tolerances
Specification C1381.
shall refer to the finished surface of the part.
1.4 The text of this standard references notes and footnotes
5. Environmental Conditions
that provide explanatory material. These notes and footnotes
5.1 Room temperature shall be maintained at not less than
(excluding those in tables and figures) shall not be considered
40 °F [4 °C] during the installation of GRG parts except when
as requirements of the standard.
adhesive is used for the bonding or attachment of parts to each
other or to a substrate. For the bonding of adhesive and joint
2. Referenced Documents
treatment the room temperature shall be maintained at not less
2.1 ASTM Standards:
than 50 °F [10 °C] for 48 hours prior to application and
C11 TerminologyRelatingtoGypsumandRelatedBuilding
continuously thereafter until completely dry.
Materials and Systems
5.2 When a temporary heat source is used, the temperature
C754 Specification for Installation of Steel Framing Mem-
shall not exceed 95 °F [35 °C] in any given room or area.
bers to Receive Screw-Attached Gypsum Panel Products
5.3 InstalledGRGshallbeprotectedfromdirectexposureto
C840 Specification for Application and Finishing of Gyp-
rain, snow, sunlight and other excessive weather conditions.
sum Board
C1007 Specification for Installation of Load Bearing
NOTE 1—Installation in conditions of excessive humidity is not recom-
(Transverse and Axial) Steel Studs and Related Accesso- mended.TheidealconditionstoinstallmoldedGRGpartsis70°F[21°C]
and 50 % RH.
ries
C1381 Specification for Molded Glass Fiber Reinforced
6. Substrate Preparation
Gypsum Parts
6.1 SubstratestoacceptGRGpartsshallbeinstalledstraight
3. Terminology
and true within ⁄8 in. in 8 ft [3 mm in 2500 mm] and shall be
free of obstructions and interference that prohibits correct
3.1 Definitions— Definitions of terms shall be in accor-
attachment of GRG parts.
dance with Terminology C11.
6.2 Metal framing members shall be of the proper size and
design for the intended use and shall be sufficient to properly
This specification is under the jurisdiction of ASTM Committee C11 on
support the installed GRG parts. Metal framing members shall
Gypsum and Related Building Materials and Systems and is the direct responsibili
...