ASTM C1290-06
(Specification)Standard Specification for Flexible Fibrous Glass Blanket Insulation Used to Externally Insulate HVAC Ducts
Standard Specification for Flexible Fibrous Glass Blanket Insulation Used to Externally Insulate HVAC Ducts
SCOPE
1.1 This specification covers the composition, size, dimensions, and physical properties of flexible fiber glass blanket, ductwrap, used to externally insulate HVAC ducts used for the distribution of condition air with a temperature up to 250°F (121°C).
1.2 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only and may be approximate.
1.3 When the installation and use of thermal insulation materials, accessories, and systems may pose safety and health problems, the manufacturer shall provide the user appropriate current information regarding any known problems associated with the recommended use of the company's products, and shall also recommend protective measures to be employed in their safe utilization. The user shall establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.
1.4 The following safety hazards caveat pertains only to the test methods, Section 13, in this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C 1290 – 06
Standard Specification for
Flexible Fibrous Glass Blanket Insulation Used to Externally
1
Insulate HVAC Ducts
This standard is issued under the fixed designation C 1290; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope C 177 Test Method for Steady-State Heat Flux Measure-
ments and Thermal Transmission Properties by Means of
1.1 This specification covers the composition, size, dimen-
the Guarded-Hot-Plate Apparatus
sions, and physical properties of flexible fiber glass blanket,
C 390 Practice for Sampling and Acceptance of Thermal
ductwrap, used to externally insulate HVAC ducts used for the
Insulation Lots
distribution of condition air with a temperature up to 250°F
C411 Test Method for Hot-Surface Performance of High-
(121°C).
Temperature Thermal Insulation
1.2 The values stated in inch-pound units are to be regarded
C 518 Test Method for Steady-State Thermal Transmission
as the standard. The values given in parentheses are for
Properties by Means of the Heat Flow Meter Apparatus
information only and may be approximate.
C 665 Specification for Mineral-Fiber Blanket Thermal In-
1.3 When the installation and use of thermal insulation
sulation for Light Frame Construction and Manufactured
materials, accessories, and systems may pose safety and health
Housing
problems, the manufacturer shall provide the user appropriate
C 1104/C 1104M Test Method for Determining the Water
current information regarding any known problems associated
Vapor Sorption of Unfaced Mineral Fiber Insulation
with the recommended use of the company’s products, and
C 1136 Specification for Flexible, Low Permeance Vapor
shall also recommend protective measures to be employed in
Retarders for Thermal Insulation
their safe utilization.The user shall establish appropriate safety
C 1045 Practice for Calculating Thermal Transmission
and health practices and determine the applicability of regula-
Properties Under Steady-State Conditions
tory requirements prior to use.
E84 Test Method for Surface Burning Characteristics of
1.4 The following safety hazards caveat pertains only to the
Building Materials
test methods, Section 13, in this specification. This standard
E 96/E 96M Test Methods for Water Vapor Transmission of
does not purport to address all of the safety concerns, if any,
Materials
associated with its use. It is the responsibility of the user of this
E 2231 Practice for Specimen Preparation and Mounting of
standard to establish appropriate safety and health practices
Pipe and Duct Insulation Materials to Assess Surface
and determine the applicability of regulatory limitations prior
Burning Characteristics
to use.
2.2 Other Documents:
2. Referenced Documents CAN/UCL-S102–M88 Standard Method ofTest for Surface
2
Burning Characteristics of Building Materials andAssem-
2.1 ASTM Standards:
3
blies
C 167 Test Methods for Thickness and Density of Blanket
or Batt Thermal Insulations
3. Terminology
C 168 Terminology Relating to Thermal Insulation
3.1 Definitions—For definitions of terms defined in this
specification, see Terminology C 168.
1
This specification is under the jurisdiction of ASTM Committee C16 on
4. Classification
Thermal Insulation and is under the direct responsibility of Subcommittee C16.23
on Blanket and Loose Fill Insulation .
4.1 Fibrous glass flexible blanket HVAC duct external
Current edition approved March 1, 2006. Published March 2006.
insulation consists of the following three types:
Originally approved in 1995. Last previous edition approved in 2004 as C
4.1.1 Type I—Blankets without membrane facing.
1290–04.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
3
Standards volume information, refer to the standard’s Document Summary page on Available from Underwriters Laboratories of Canada, 7 Crouse Road, Scarbor-
the ASTM website. ough, Ontario, Canada M1R 3A9.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
C1290–06
4.1.2 Type II—Blankets faced with a vapor-retarder mem- 7.6 Odor Emission— A detectable odor of objectionable
brane having a water vapor permeance no higher than 1.30 nature recorded by more than two of the five panel members
Perm. shall constitute rejection of the product when tested in accor-
4.1.3 Type III—Flexible blankets faced with a vapor- dance with 13.7.
retarder membrane with a water vapor permeance no higher 7.7 Corrosiveness— When tested in accord
...