EN 16430-3:2014
(Main)Fan assisted radiators, convectors and trench convectors - Part 3: Test method and rating for cooling capacity
Fan assisted radiators, convectors and trench convectors - Part 3: Test method and rating for cooling capacity
This European Standard applies to the testing of the dry cooling capacity with no condensation of fan assisted radiators, convectors and trench convectors which are factory assembled or kits, i.e.
- fan assisted radiators and convectors, provided the cooler has a dedicated fan or fans,
- radiators and convectors without dedicated fan(s),
- trench convectors with and without fan(s), provided the cooler and the fan(s) are dedicated.
Gebläseunterstützte Heizkörper, Konvektoren und Unterflurkonvektoren - Teil 3: Prüfverfahren und Bewertung der Kühlleistung
Diese Europäische Norm gilt für die Prüfung der Kühlleistung von gebläseunterstützten Heizkörpern, Konvektoren und Unterflurkonvektoren ohne Kondensation, d. h. für:
- gebläseunterstützte Heizkörper und Konvektoren, vorausgesetzt der Wärmeerzeuger besitzt ein oder mehrere fest eingebaute Gebläse;
- Heizkörper und Konvektoren ohne ein oder mehrere fest eingebaute Gebläse;
- Unterflurkonvektoren mit und ohne Gebläse, vorausgesetzt Wärmeerzeuger und Gebläse sind eindeutig einander zugeordnet.
Radiateurs assistés par ventilateur, convecteurs et convecteurs de caniveaux - Partie 3: Méthode d'essais et d'évaluation de la puissance thermique en mode rafraîchissement
La présente norme européenne s’applique aux essais de la puissance thermique en mode rafraîchissement sans condensation des radiateurs assistés par ventilateur, convecteurs et convecteurs de caniveaux, c’est à dire
- radiateurs et convecteurs assistés par ventilateur, sous réserve que l’élément chauffant ait un ou des ventilateurs dédiés ;
- radiateurs et convecteurs sans ventilateur(s) dédié(s) ;
- convecteurs de caniveaux avec et sans ventilateur(s), sous réserve que l’élément chauffant et le(s) ventilateur(s) soi(en)t dédié(s).
Končni prenosniki toplote z ventilatorjem, konvektorji in talni konvektorji - 3. del: Preskusne metode in vrednotenje hladilne moči
Ta evropski standard se uporablja za preskušanje hladilne moči (brez kondenzacije) radiatorjev z ventilatorji, konvektorjev in talnih konvektorjev tj.
– radiatorjev z ventilatorji in konvektorjev, če ima grelnik namenski ventilator ali ventilatorje,
– radiatorjev in konvektorjev brez namenskih radiatorjev,
– talnih konvektorjev z ventilatorji ali brez njih, če so grelnik in ventilatorji namenski.
General Information
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Gebläseunterstützte Heizkörper, Konvektoren und Unterflurkonvektoren - Teil 3: Prüfverfahren und Bewertung der KühlleistungRadiateurs assistés par ventilateur, convecteurs et convecteurs de caniveaux - Partie 3: Méthode d'essais et d'évaluation de la puissance thermique en mode rafraîchissementFan assisted radiators, convectors and trench convectors - Part 3: Test method and rating for cooling capacity91.140.10Sistemi centralnega ogrevanjaCentral heating systemsICS:Ta slovenski standard je istoveten z:EN 16430-3:2014SIST EN 16430-3:2015en,fr,de01-marec-2015SIST EN 16430-3:2015SLOVENSKI
STANDARD
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 16430-3
December 2014 ICS 91.140.10 English Version
Fan assisted radiators, convectors and trench convectors - Part 3: Test method and rating for cooling capacity
Radiateurs assistés par ventilateur, convecteurs et convecteurs de caniveaux - Partie 3: Méthode d'essais et d'évaluation de la puissance thermique en mode rafraîchissement
Gebläseunterstützte Radiatoren, Konvektoren und Unterflurkonvektoren - Teil 3: Prüfverfahren und Bewertung der Kühlleistung This European Standard was approved by CEN on 9 November 2014.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2014 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 16430-3:2014 ESIST EN 16430-3:2015
Foreword .3 1 Scope .4 2 Normative references .4 3 Terms and definitions .4 4 Testing of dry cooling capacity .5 4.1 Short description .5 4.2 Test booth .5 4.3 Test methods .7 4.3.1 General .7 4.3.2 Fan assisted radiators / convectors .8 4.4 Master radiator for dry cooling capacity . 12 5 Carrying out the measurements . 13 5.1 Dimension and construction of the test samples . 13 5.2 Selection of the models to be tested for determining the dry cooling capacity of a type . 13 5.3 Installation of the sample in the test booth . 13 5.3.1 General . 13 5.3.2 Radiators and wall-mounted convectors . 14 5.3.3 Trench convectors . 14 5.4 Connection of the test sample to the measuring circuit . 14 5.5 Minimum dry cooling performance . 14 5.6 Mass flow rate . 14 5.7 Reference air temperature . 14 5.8 Steady state conditions . 14 5.9 Correction due to air pressure . 15 5.10 Results of measurements – characteristic equation . 15 6 Test Report . 15 6.1 General . 15 6.2 Data . 15
Key 1 water cooled metal panels 5 dry cooling load simulator 2 insulation 6 measuring point of air temperature 3 test panel or convector 7 measuring point of reference air temperature 4 measuring point of air temperature 8 measuring point of temperature under insulation (position according to EN 442-2) Figure 1 — Test booth with an installed dry cooling convector or radiator, dry cooling load simulators and the measuring points for the temperatures SIST EN 16430-3:2015
Key 1
cover 2 4 holes, evenly distributed 3 60 W heat source 4 open 5 bottom plate 6 support Figure 2 — Dry cooling load simulator (dummy) 4.3 Test methods 4.3.1 General The test method shall be carried out according to EN 442-2. Analogue to the excess temperatures given, the under temperatures shall be: ûT===(8=h=± 0,5) K ûT===(10=h=± 0,5) K ûT===(12=h=± 0,5) K SIST EN 16430-3:2015
...