Abstract

This document specifies the:
—   field of application:
—   The dimensional, the physicochemical, the design, the hydraulic, the mechanical and the acoustic characteristics of non-controllable backflow preventer with different pressure zones, family C, type A, nominal sizes DN 6 to DN 25, nominal pressure PN 10.
It is applicable to:
—   Family C, type A, class “a” for general use: devices of class “a” can be capable of working:
—   at any pressure up to 1 MPa (10 bar);
—   with any pressure variation up to 1 MPa (10 bar);
—   at a supply temperature limit of 65 °C and 90 °C for 1 h;
—   Family C, type A, class “b” for specific use: devices of class “b” shall be capable of working:
—   at any downstream pressure up to 0,3 MPa (3 bar);
—   with any downstream pressure variation up to 0,3 MPa (3 bar); at a supply temperature limit of 65 °C and 90 °C for 1 h;
Class “b” devices can capable of operating: at any downstream pressure up to 300 kPa (3 bar), with any downstream pressure variation up to 300 kPa (3 bar) at a supply temperature limit of 65 °C and 90 °C for 1 h. Class “b” devices with specific hydraulic and non-acoustic requirements and are intended to equip filling devices physically integrated into a single-function (heating) or dual-function (heating and domestic hot water) boiler.
It specifies also:
—   test methods and requirements for verifying these characteristics;
—   marking;
—   presentation and the delivery.

Status
Not Published
Publication Date
29-Mar-2027
Technical Committee
CEN/TC 164 - Water supply
Current Stage
4060 - Closure of enquiry - Enquiry
Start Date
01-Oct-2026
Due Date
10-Mar-2026
Completion Date
10-Mar-2026

Buy Documents

prEN 14367 is a draft European Standard from CEN for non controllable backflow preventer with different pressure zones - Family C, type A. It specifies the design, materials, test methods, marking and delivery requirements for DN 6 to DN 25 devices with PN 10, including class a for general use and class b for specific use in sealed heating system filling applications. It is aimed at people who need to specify, make, test, buy or approve these backflow protection devices for water supply installations.

What does prEN 14367 specify?

prEN 14367 specifies the characteristics and verification methods for family C, type A non controllable backflow preventers. The document covers dimensional, physicochemical, design, hydraulic, mechanical and acoustic requirements, together with marking, technical documentation and presentation at delivery.

The scope is limited to devices for water supply systems in nominal sizes DN 6 to DN 25 with nominal pressure PN 10. It distinguishes two application classes:

  • class a for general use
  • class b for specific use at filling points of domestic sealed heating systems, including devices physically integrated into single-function or dual-function boilers

How the document is organized

Clause or annexWhat it covers
1Scope
2Normative references
3Terms and definitions
4Nominal size (denomination)
5Designation
6Symbolization
7Physico-chemical characteristics
8Design
9Characteristics and test methods
10Marking and technical documents
11Presentation at delivery
Annex AComplementary test methods for CA class b with a plastic body
Annex BOrder of tests

What are the key requirements of prEN 14367?

prEN 14367 sets out a complete product and test framework, not just a single functional check. In practice, a compliant device must be built from suitable materials, have the right connection and discharge arrangement, and pass the mechanical, tightness, hydraulic, compatibility and acoustic tests that apply to its class.

Size, designation and symbolization

Clause 4 links the nominal size to the flow-rate-related denomination for class a devices, while class b devices all have to meet the same performance requirements as DN 6. Clause 5 then defines the designation string, which combines family, type, class, denomination where applicable, connection type, body material, surface finish, acoustic group for class a, and the reference to the standard. This matters because procurement and documentation need a precise way to identify exactly which variant is being supplied.

Clause 6 provides the graphic symbol for class a and class b devices. That helps designers, drawings and installation documents show the device clearly and consistently.

Materials and construction

Clause 7 requires materials and coatings to be suitable for contact with drinking water and not to contaminate it or change its quality, appearance, smell or taste. The manufacturer has to state the nature of the materials and coatings in a technical document, and materials with insufficient corrosion resistance need additional protection.

For copper alloys, where dezincification-resistant material is required, the product has to meet the stated resistance limit and be tested to EN ISO 6509-1. If required by national rules, the product is marked DR. In practice, this is the part readers use to check whether the body material is acceptable for potable-water use and local market rules.

Design rules that affect safety and serviceability

Clause 8 requires the device function to depend only on water pressure, with fixed, non-adjustable spring settings. If the internal parts can be accessed for inspection or repair, they must go back in only one way, so reversal or interchange is not possible.

For class a devices, any strainer has to be upstream of the upstream non-return system and easy to remove for cleaning. For class b devices, the complete device is not meant to be removable for maintenance of the individual parts. That affects how the product is serviced and how installers should plan replacement versus repair.

Relief valve and discharge arrangement

Clause 8 also sets requirements for the relief valve. The control has to be of positive safety, meaning failure or leakage leaves the relief open. The discharge outlet needs an air break to drain, and class a devices have to meet the dimensional requirements of EN 1717 for that air break.

Class b devices have additional discharge features, including at least two air inlet openings and a relief device arrangement that does not obstruct those openings. In practical terms, this is about avoiding unsafe backflow paths while still allowing the device to discharge freely.

Test program and performance checks

Clause 9 makes the device undergo tests as installed according to the manufacturer’s technical documents. The standard also fixes the default test conditions and measuring accuracy, so the results are comparable between laboratories.

The test programme covers:

  • body strength under pressure
  • torque and bending checks on union fittings and body tightness
  • endurance
  • downstream and upstream check-valve tightness
  • closing pressure of the downstream check valve
  • vacuum behavior
  • pressure loss versus flow rate
  • relief-valve opening and closing behavior
  • relief flow rate
  • compatibility with potassium permanganate and sodium hypochlorite disinfection treatments
  • acoustic testing for class a devices

This matters because compliance depends on the whole performance package, not only on whether the device resists pressure.

Marking, documents and delivery

Clause 10 requires permanent, visible marking on the casing or on a fixed plate, including identification, flow direction, family/type/class, DN where applicable, PN, maximum operating temperature, acoustic group where applicable, traceability, and the standard reference. Clause 11 requires protection against damage and contamination from manufacture up to installation. For users, this is what supports traceability, correct installation and clean delivery.

What terms does prEN 14367 define?

  • Non controllable backflow preventer with different pressure zones - Family C - Type A (CA) - A device with upstream, vented intermediate and downstream zones that disconnects by venting when the pressure difference falls below the stated threshold, without control means.
  • Class a - The general-use version of the device, intended to work at any pressure up to the stated limit and with the full range of pressure variations in the scope.
  • Class b - The specific-use version for filling points in domestic sealed heating systems, with tighter hydraulic conditions and no acoustic requirement.
  • Specific use - The use of the backflow protection device at the filling point of domestic sealed heating systems, which applies only to class b.
  • Nominal size (DN) - The denomination used to identify the device size and its performance class.
  • Nominal pressure (PN) - The pressure rating used for the device design and test basis.
  • Acoustic group - The noise classification used for class a devices after acoustic testing.
  • Air break to drain - The discharge arrangement that maintains an air gap between the waste drain and the collected discharged water.

Who uses prEN 14367?

Manufacturers of backflow protection devices use prEN 14367 to design the product, choose materials, set up the relief valve and prepare the marking and technical documents. Test laboratories use it to run the mechanical, hydraulic, tightness, endurance and acoustic checks.

It is also used by:

  • plumbing and water-supply engineers who specify backflow protection in installations
  • boiler and heating equipment manufacturers, especially for class b integrated applications
  • quality and conformity-assessment teams checking product evidence and test reports
  • buyers and technical approvers who need to match a device to a specific installation or market requirement

What changed in prEN 14367 from the previous edition?

prEN 14367:2026 will supersede EN 14367:2005. The foreword states these significant technical changes:

  • the scope was updated
  • an accuracy chapter was added
  • the testing and requirements system was revised
  • Annex B was deleted and replaced by a new order-of-tests annex
  • all figures were updated
  • the text was editorially revised

Which standards are used with prEN 14367?

StandardWhat it contributes
EN 1717General backflow-protection terminology and the framework for protection of potable water
EN 1254 (all parts)Copper and copper alloy plumbing fittings used for connections
EN 1267Water-based flow-resistance test method and related hydraulic test rig basis
EN ISO 228-1Pipe thread dimensions, tolerances and designation
EN ISO 3822-1:1999Laboratory measurement of noise emission
EN ISO 3822-3:2018Mounting and operating conditions for in-line valves and appliances in acoustic tests
EN ISO 6509-1Test method for dezincification resistance of brass
EN 13959Certified check valve EB referenced in the closing-pressure verification
EN ISO 5167-1Pressure-differential flow measurement principles used in the hydraulic test rig
ISO 7-1Pipe thread dimensions, tolerances and designation for pressure-tight joints
ISO 965-1Metric screw thread tolerances, used for M10 × 1 connections

What does the prEN 14367 document contain?

The document contains design principles, symbols, connection rules and a large set of test figures and procedures. The figures show the device principle and the rigs used for torque, bending, endurance, tightness, vacuum, pressure-loss, relief-valve and acoustic testing.

Its tables provide the practical data used in testing and classification, including nominal-size-related flow values, torque and bending requirements, endurance flow rates, hydraulic pressure-loss limits, relief-flow limits and acoustic group limits. Annex A adds extra test methods for CA class b devices with a plastic body, while Annex B sets out the order of tests so laboratories can plan samples and test sequence correctly.

Relations

Effective Date
19-Jan-2023

Buy Documents

Get Certified

Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)

German Institute for Building Technology.

DAKKS Germany Verified

DIN CERTCO

DIN Group product certification.

DAKKS Germany Verified

Aboma Certification B.V.

Specialized in construction, metal, and transport sectors.

RVA Netherlands Verified

Sponsored listings

Frequently Asked Questions

prEN 14367 is a draft published by the European Committee for Standardization (CEN). Its full title is "Non controllable backflow preventer with different pressure zones - Family C, type A". This standard covers: This document specifies the: — field of application: — The dimensional, the physicochemical, the design, the hydraulic, the mechanical and the acoustic characteristics of non-controllable backflow preventer with different pressure zones, family C, type A, nominal sizes DN 6 to DN 25, nominal pressure PN 10. It is applicable to: — Family C, type A, class “a” for general use: devices of class “a” can be capable of working: — at any pressure up to 1 MPa (10 bar); — with any pressure variation up to 1 MPa (10 bar); — at a supply temperature limit of 65 °C and 90 °C for 1 h; — Family C, type A, class “b” for specific use: devices of class “b” shall be capable of working: — at any downstream pressure up to 0,3 MPa (3 bar); — with any downstream pressure variation up to 0,3 MPa (3 bar); at a supply temperature limit of 65 °C and 90 °C for 1 h; Class “b” devices can capable of operating: at any downstream pressure up to 300 kPa (3 bar), with any downstream pressure variation up to 300 kPa (3 bar) at a supply temperature limit of 65 °C and 90 °C for 1 h. Class “b” devices with specific hydraulic and non-acoustic requirements and are intended to equip filling devices physically integrated into a single-function (heating) or dual-function (heating and domestic hot water) boiler. It specifies also: — test methods and requirements for verifying these characteristics; — marking; — presentation and the delivery.

This document specifies the: — field of application: — The dimensional, the physicochemical, the design, the hydraulic, the mechanical and the acoustic characteristics of non-controllable backflow preventer with different pressure zones, family C, type A, nominal sizes DN 6 to DN 25, nominal pressure PN 10. It is applicable to: — Family C, type A, class “a” for general use: devices of class “a” can be capable of working: — at any pressure up to 1 MPa (10 bar); — with any pressure variation up to 1 MPa (10 bar); — at a supply temperature limit of 65 °C and 90 °C for 1 h; — Family C, type A, class “b” for specific use: devices of class “b” shall be capable of working: — at any downstream pressure up to 0,3 MPa (3 bar); — with any downstream pressure variation up to 0,3 MPa (3 bar); at a supply temperature limit of 65 °C and 90 °C for 1 h; Class “b” devices can capable of operating: at any downstream pressure up to 300 kPa (3 bar), with any downstream pressure variation up to 300 kPa (3 bar) at a supply temperature limit of 65 °C and 90 °C for 1 h. Class “b” devices with specific hydraulic and non-acoustic requirements and are intended to equip filling devices physically integrated into a single-function (heating) or dual-function (heating and domestic hot water) boiler. It specifies also: — test methods and requirements for verifying these characteristics; — marking; — presentation and the delivery.

prEN 14367 is classified under the following ICS (International Classification for Standards) categories: 91.140.60 - Water supply systems. The ICS classification helps identify the subject area and facilitates finding related standards.

prEN 14367 has the following relationships with other standards: It is inter standard links to EN 14367:2005. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

prEN 14367 is associated with the following European legislation: EU Directives/Regulations: 305/2011. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

prEN 14367 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 1 Upstream zone
  • 2 Intermediate zone
  • 3 Downstream zone
  • 4 Strainer (optional)
  • 3.2 specific use
  • 4 Nominal size (denomination)
  • 4.1 Class a device
  • 4.2 Class b device
  • 5 Designation
  • 6 Symbolization
  • 7 Physico-chemical characteristics
  • 7.1 Materials
  • 7.2 Nature of the materials
  • 8 Design
  • 8.1 General
  • 8.2 Relief valve
  • 9 Characteristics and tests methods
  • 9.1 General
  • 9.2 Accuracy of measurements
  • 9.3 Accuracy of measuring instruments
  • 9.4 End connections
  • 9.5 Mechanical characteristics
  • 1 Isolating valve
  • 2 Pressure gauge
  • 8 Pressure gauge
  • 1 Isolating valve
  • 2 Pressure gauge
  • 3 Temperate gauge
  • 9.6 Tightness characteristics
  • 3 Adjusting valve
  • 3 Vacuum pump
  • 4 Vacuum tank
  • 5 Water trap
  • 6 Supply water
  • 7 Isolating valve
  • 8 Adjusting valve
  • 9.7 Hydraulic characteristics
  • 1 Water supply
  • 2 Flow meter
  • 7 Test device
  • 10 Differential pressure measuring device
  • 3 Adjusting valve
  • 1 Pressure gauge
  • 2 Adjusting valve
  • 3 Water supply
  • 9.8 Compatibility with the products used for disinfection of the networks
  • 9.9 Acoustic tests
  • 10 Marking and technical documents
  • 10.1 Marking
  • 10.2 Technical documents
  • 11 Presentation at delivery
  • Annex A
  • 3 Pressure gauge
  • 4 Oven
  • 1 Pressure gauge
  • 2 Isolating valve
  • 1 Adjusting valve
  • Annex B
  • Bibliography

Introduction

In respect of potential adverse effects on the quality of water intended for human consumption, caused by the product covered by this document:

a) This document provides no information as to whether the product might be used without restriction in any of the Member States of the EU or EFTA.

b) while awaiting the adoption of verifiable European criteria, existing national regulations concerning the use and/or the characteristics of this product remain in force.

oSIST prEN 14367:2026 prEN 14367:2026 (E)

1 Scope

This document specifies the:

  • field of application:
  • The dimensional, the physicochemical, the design, the hydraulic, the mechanical and the acoustic characteristics of non-controllable backflow preventer with different pressure zones, family C, type A, nominal sizes DN 6 to DN 25, nominal pressure PN 10.

It is applicable to:

  • Family C, type A, class “a” for general use: devices of class “a” can be capable of working:
  • at any pressure up to 1 MPa (10 bar);
  • with any pressure variation up to 1 MPa (10 bar);
  • at a supply temperature limit of 65 °C and 90 °C for 1 h;
  • Family C, type A, class “b” for specific use: devices of class “b” shall be capable of working:
  • at any downstream pressure up to 0,3 MPa (3 bar);
  • with any downstream pressure variation up to 0,3 MPa (3 bar); at a supply temperature limit of 65 °C and 90 °C for 1 h; Class “b” devices can capable of operating: at any downstream pressure up to 300 kPa (3 bar), with any downstream pressure variation up to 300 kPa (3 bar) at a supply temperature limit of 65 °C and 90 °C for 1 h. Class “b” devices with specific hydraulic and non-acoustic requirements and are intended to equip filling devices physically integrated into a single-function (heating) or dual-function (heating and domestic hot water) boiler.

It specifies also:

  • test methods and requirements for verifying these characteristics;
  • marking;
  • presentation and the delivery.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1254 (all parts), Copper and copper alloys — Plumbing fittings EN 1267, Industrial Valves — Test of flow resistance using water as test fluid EN 1717, Protection against pollution of water intended for human consumption in potable water installations and general requirements for devices to prevent pollution by backflow EN ISO 228-1, Pipe threads where pressure-tight joints are not made on the threads — Part 1: Dimensions, tolerances and designation (ISO 228-1)

oSIST prEN 14367:2026 prEN 14367:2026 (E) EN ISO 3822-1:1999, Acoustics — Laboratory tests on noise emission from appliances and equipment used in water supply installations — Part 1: Method of measurement (ISO 3822-1:1999) EN ISO 3822-3:2018, Acoustics — Laboratory tests on noise emission from appliances and equipment used in water supply installations — Part 3: Mounting and operating conditions for in line valves and appliances(ISO 3822-3:2018) EN ISO 6509-1, Corrosion of metals and alloys — Determination of dezincification resistance of brass (ISO 6509-1:1981)

3 Terms and definitions

For the purposes of this document, the terms and definitions given in EN 1717 and the following apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • ISO Online browsing platform: available at https://www.iso.org/obp/
  • IEC Electropedia: available at https://www.electropedia.org/ 3.1 non controllable backflow preventer with different pressure zones — Family C — Type A the specific characteristics of this device called “CA”, are as follows:

The device is divided into three zones:

  • one upstream zone p ;
  • one intermediate zone (p not measurable) vented to the atmosphere;
  • one downstream zone p .

The device provides disconnection by venting the intermediate pressure zone to the atmosphere when the difference of pressure between the intermediate zone and the upstream zone is less than 10 % of the upstream pressure (p – p < 10 % p ) i 1 1 It ensures a discharge (backflow rate) through the intermediate zone, at least equal to the given discharge flow rate Means for the control of the protection device are not included

oSIST prEN 14367:2026 prEN 14367:2026 (E)

Key p

1 Upstream zone

p

2 Intermediate zone

p

3 Downstream zone

4 Strainer (optional)

Figure 1 — Design principle For the purposes of this document “Non controllable backflow preventer with different pressure zones — Family C — Type A” is hereafter referred to as “device”.

3.2 specific use

use of the backflow protection device at the filling point of domestic sealed heating systems, class b only

4 Nominal size (denomination)

4.1 Class a device

The nominal size shall be in accordance with the flow rate in the Table 3.

4.2 Class b device

All Class b devices shall comply with the same performances requirements as a DN 6.

5 Designation

A non-controllable backflow preventer with different pressure zones family C, type A is designated by:

  • family, its type and class;
  • denomination (see Table 3) except class b device;
  • connection type;
  • material of its body;
  • surface finish (possible coating);
  • acoustic group except class b device;
  • reference to the present standard.

EXAMPLE Examples for a designation:

oSIST prEN 14367:2026 prEN 14367:2026 (E) class a:

  • Non controllable backflow preventer with different pressure zones, EN 14367, family C, type A, class a, DN 20, G3/4 × G3/4, bronze, I, class b:
  • Non controllable backflow preventer with different pressure zones, EN 14367, family C, type A, class b, M10 × 1, brass,

6 Symbolization

The graphic representation of the non-controllable backflow preventer with different pressure zones — family C, type A is as follows:

a) Class a b) Class b Figure 2 — Graphic symbol

7 Physico-chemical characteristics

7.1 Materials

The selection of materials is the responsibility of the manufacturer, provided they satisfy the following requirements:

a) materials and coatings shall not contaminate the potable water; b) in a technical document, the nature of the materials and coatings used shall be stated; c) materials with inadequate corrosion resistance shall have additional protection; d) the materials used shall be suitable for the temperatures specified in the tests in this document; e) the materials, and in particular copper alloys, for which recommendations or international standards exist, shall comply with the relevant European standards.

7.2 Nature of the materials

7.2.1 General

All materials coming into contact with water intended for human consumption shall present no health risk nor cause any change to the water in terms of quality, appearance, smell or taste. NOTE While awaiting the adoption of verifiable European criteria for testing materials in contact with water intended for human consumption, existing national regulations concerning the use and/or the characteristics of these products remain in force.

oSIST prEN 14367:2026 prEN 14367:2026 (E)

7.2.2 Dezincification resistant copper alloy

Copper-zinc alloys containing more than 15 % zinc are subject to dezincification when submitted to water capable of dezincification. In the countries where the use of products made of dezincification resistant materials is required, the materials used shall guarantee a dezincification depth less than 200 µm in any direction. For this purpose, materials shall be tested in accordance with EN ISO 6509-1 and the product shall be marked in compliance with the indications according to Clause 10.

7.2.3 Nature of apparent surfaces

Depending on the materials of the disconnectors, the outer and inner surfaces may or may not have a coating. This coating shall not disturb the functional characteristics of the device.

7.2.4 Uncoated surface

The finish of surfaces should be free from appearance defects such as:

  • Gales
  • Cracks
  • sand inclusions,
  • machining “fire”,
  • blows, tool bites
  • scratches, etc. ...

No disturb the functional characteristics of the device.

7.2.5 Surface with coating

It is strongly recommended not to use a so-called “decorative” coating for this type of product (Ni, Ni- Cr ...). Any use shall be justified by the holder.

Coated surfaces shall meet the requirements of article 5 of EN 248:2002.

7.2.6 Detection of residual stress
7.2.6.1 General

This test shall be performed for bodies made out of brass materials and with female threads according to EN 10226-1 and compression ends according to EN 1254-2.

7.2.6.2 Test

This test is based on ISO 6957. Its purpose is to verify the resistance to cracking under stress corrosion in ammonia medium (as described in 7.2.6.3, b)).

The test entails exposing test specimens consisting of the assembled device in an atmosphere loaded with ammonia vapour.

7.2.6.3 Test method (Procedure)

The paragraph below details ISO 6957.

Test solution:

a) Use solutions of analysis quality and of distilled water.

oSIST prEN 14367:2026 prEN 14367:2026 (E) b) Solution of ammonia at 20 % (in weight).

c) The pH of the test solution shall be adjusted to 9,5 by using hydrochloric acid. d) The test temperature shall be (23 ± 2) °C with a measurement uncertainty of ± 1 K. Test specimen:

e) The test specimen consists of three samples of a single assembled product. The test specimen shall be inserted into the test enclosure under no stress.

7.2.6.4 Instructions

a) Rinse the test specimens with a clean non-chlorinated solvent (for example, ethanol). b) Let it dry in the air.

c) Insert the test specimens into the test enclosure along with the ammonia solution. The volume of the container made of glass (e.g. desiccator) shall be minimum (10 ± 1) l. d) The volume of the solution inserted shall be (200 ± 10) ml per 3 l of total volume of the container (e.g. for a 10 l container it means (667 ± 33) ml).

e) Place the test specimens in the container in such a way that they will not touch each other and that they will not be in contact with the solution.

(+2) After an exposure of 24 h, remove the test specimens and rinse them. (−0)

7.2.6.5 Requirements

After the test, the devices shall be inspected visually for stress corrosion cracking. No cracking shall occur on any component.

8 Design

8.1 General

a) Only the pressure of the water (upstream and/or downstream): shall have an effect of the function of components of the device.

b) The settings of the springs shall be fixed and not adjustable. c) As regards devices designed in such a way that the access to the internal parts is possible (for inspection, repair or replacement), these components shall be able to be refitted at their initial place without ambiguity (impossibility of reversal, interchange of obturators, diaphragms, springs, …). A visible mark is not sufficient.

d) For the non-controllable backflow preventer with different pressure zones – Family C-Type A-Class a: If the device includes a strainer:

  • it located upstream of the upstream non-return system (see the Figure 1);
  • it shall be easily removable for cleaning.

oSIST prEN 14367:2026 prEN 14367:2026 (E) e) For the non-controllable backflow preventer with different pressure zones – Family C-Type A-Class b: The complete device shall not be removable for maintenance service of the single parts of Cab.

8.2 Relief valve

If the relief valve system operates by means of pilot tube then the cross section of the pilot tube shall be 2 2 equal to or greater than 45 mm for devices DN > 15 or 12,5 mm for devices DN ≤ 15 no dimension being less than 4 mm.

The water passage through the discharge orifice shall have a cross-section of minimal 12,5 mm . The smallest dimension used to calculate this cross-section shall not be inferior to 4 mm for nonmoving part. The control of the relief valve shall be of positive safety, i.e. in case of rupture or leakage, the relief shall be open.

This will be checked by examination of the behaviour of the device, after dismantling the control system of the relief valve (diaphragm, piston seal …).

An air break to drain shall be placed at the discharge outlet. An air gap shall exist between any waste drain and any means to collect the discharged water (floor, tundish, curb, sink …). The device shall be capable, by design, evacuating the full relief flow rate as defined in 9.6.4 without spilling to the outside of the air break to drain.

Class a device shall be equipped with:

The air break to drain shall meet the dimensional requirements of EN 1717. This air break to drain shall be:

  • either directly incorporated into the device;
  • or factory fitted;
  • or supplied with the device.

In the last two cases, the relief valve outlet of the device shall permit neither fitting of a standardized threaded pipe, nor the connection by the inside of a standardized pipe or shape, be it by glue, welding or interlocking.

Class b device shall be equipped with:

  • At least two air inlets openings with each a minimum cross-section of 12,5 mm upstream of the relief piping shall be incorporated.

The smallest dimension used to calculate this cross-section shall not be less than 4 mm. - A relief device capable of mounting a standardized or flexible tube without disturbing the operation of the discharge device system and without obstructing, even partially, the air inlet ports. Characteristics and test methods General.

Performance tests shall be carried out on the device as installed in accordance with the manufacturer’s technical documents.

oSIST prEN 14367:2026 prEN 14367:2026 (E)

9 Characteristics and tests methods

9.1 General

The performance tests shall be carried out on the device as installed in accordance with the manufacturer’s technical documents.

If not specified, all tests shall be carried out with water at room temperature. The examples illustrated in the figures are for illustrative purposes only. Laboratory equipment shall be designed to ensure that the device can be tested in accordance with the requirement (e.g sensors instead of column).

9.2 Accuracy of measurements

In the absence of any particular specifications:

  • flow rate and pressure: ±2 % of the value specified;
  • temperature: cold water ± 5 K of the value specified; hot water ± 2 K of the value specified; +10
  • time:

% of the value specified;

  • other values: ±5 % of the value specified.

9.3 Accuracy of measuring instruments

9.3.1 General

All the measuring instruments shall have a measurement accuracy of ± 2 % of the measured value, except for temperature measurement accuracy shall be ± 1 K.

9.4 End connections

9.4.1 General

The connection shall be demountable without any damage to the piping and in accordance with relevant European Standards e.g. EN 1254-20, EN ISO 228-1 and ISO 10226-1. EXAMPLE Coupling nut, union.

...