EN 14897:2006
(Main)Water conditioning equipment inside buildings - Devices using mercury low-pressure ultraviolet radiators - Requirements for performance, safety and testing
Water conditioning equipment inside buildings - Devices using mercury low-pressure ultraviolet radiators - Requirements for performance, safety and testing
This document specifies definitions, principles of construction, requirements and methods for testing the performance of UV devices for drinking water installations inside buildings which are permanently connected to the mains supply at the point of entry into a building or within the water distribution system inside the building.
UV devices in the sense of this standard are UV bactericidal treatment devices or UV disinfection devices.
Anlagen zur Behandlung von Trinkwasser innerhalb von Gebäuden - Geräte mit Quecksilberdampf-Niederdruckstrahlern - Anforderungen an Ausführung, Sicherheit und Prüfung
Diese Norm legt Begriffe, Grundsätze der Konstruktion, Anforderungen und Angaben zum Betrieb sowie Verfahren für die Prüfung der Leistungsanforderungen von UV-Geräten für Trinkwasserinstallationen innerhalb von Gebäuden nach der Normen-Reihe EN 806, die fest am Eintrittspunkt des Wassers in die Hausinstallation mit DN 15 bis DIN 100 angeschlossen oder in die weitere Installation integriert sind, das für den menschlichen Gebrauch bestimmt ist, fest.
Équipements de traitement de l'eau à l'intérieur des bâtiments - Lampes à rayonnement UV à mercure et basse pression - Exigences relatives aux performances, à la sécurité et aux essais
Le présent document prescrit des définitions, des principes de construction, des exigences ainsi que des méthodes d’essai permettant de contrôler l’efficacité des dispositifs à UV destinés à être utilisés dans les installations d’eau potable à l’intérieur des bâtiments, ces dispositifs étant raccordés en permanence au réseau d’adduction d’eau soit au point d’entrée dans le bâtiment, soit dans le système de distribution d’eau à l’intérieur du bâtiment.
Les dispositifs à UV au sens de la présente norme comprennent les dispositifs de traitement bactéricide par UV ou les dispositifs de désinfection par UV.
Oprema, ki se uporablja za pripravo pitne vode v stavbah - Naprave z živosrebrnimi nizkotlačnimi ultravijoličnimi sevalniki - Zahteve za delovanje, varnost in preskušanje
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Anlagen zur Behandlung von Trinkwasser innerhalb von Gebäuden - Geräte mit Quecksilberdampf-Niederdruckstrahlern - Anforderungen an Ausführung, Sicherheit und PrüfungÉquipements de traitement de l'eau a l'intérieur des bâtiments - Lampes a rayonnement UV a mercure et basse pression - Exigences relatives aux performances, a la sécurité et aux essaisWater conditioning equipment inside buildings - Devices using mercury low-pressure ultraviolet radiators - Requirements for performance, safety and testing91.140.60Sistemi za oskrbo z vodoWater supply systems13.060.20Pitna vodaDrinking waterICS:Ta slovenski standard je istoveten z:EN 14897:2006SIST EN 14897:2006en01-oktober-2006SIST EN 14897:2006SLOVENSKI
STANDARD
EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 14897June 2006ICS 91.140.60 English VersionWater conditioning equipment inside buildings - Devices usingmercury low-pressure ultraviolet radiators - Requirements forperformance, safety and testingÉquipements de conditionnement de l'eau à l'intérieur desbâtiments - Dispositifs utilisant des radiateurs à mercure etbasse pression de rayonnement UV - Exigences relativesaux performances, à la sécurité et aux essaisAnlagen zur Behandlung von Trinkwasser innerhalb vonGebäuden - Geräte mit Quecksilberdampf-Niederdruckstrahlern - Anforderungen an Ausführung,Sicherheit und PrüfungThis European Standard was approved by CEN on 10 May 2006.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Central Secretariat or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania,Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2006 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 14897:2006: ESIST EN 14897:2006
Requirements for the device sensor.17 A.1 Calibration.17 A.2 Selectivity.17 A.3 Measuring range linearity.17 A.4 Measuring range and resolution.17 A.5 Temperature drift.18 A.6 Stability over time.18 Annex B (normative)
Biodosimeter calibration.19 Annex C (informative)
Monitoring window.22 Annex D (normative)
Manufacturer's information for the type test.23 Annex E (normative)
Manufacturer's information for the UV device user.25 Bibliography.26
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. SIST EN 14897:2006
UV devices in the sense of this standard are UV bactericidal treatment devices or UV disinfection devices. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1717, Protection against pollution of potable water in water installations and general requirements of devices to prevent pollution by backflow 3 Definitions For the purposes of this document, the following terms and definitions apply. 3.1 absorption decrease of the incident irradiance of a light beam including transformation into other forms suffered by radiant energy passing through a material substance (e. g. heat) 3.2 irradiance measure of the UV light flux divided by the area that intercepts the radiation, in W/m2
NOTE The irradiance measured in UV disinfection devices by the UV device sensor
is mainly influenced by the lamp output, the transmittance of the water, and scaling/fouling of the protective quartz sleeves and the position of the lamps in the radiation chamber. 3.3 disinfection action of killing or inactivating all types of pathogenic bacteria to a specified degree of at least 99,999 % and all types of pathogenic viruses to a degree of at least 99,99 % using a UV disinfection device 3.4 bactericidal treatment action of inactivating or killing bacteria present in water to an unspecified degree using a UV bactericidal treatment device 3.5 fluence dose product of irradiance in W/m2 and exposure time in s, in J/m2 NOTE Fluence is the correct term from a strictly scientific point of view.
3.6 germicidal fluence
fluence weighted with the germicidal UV sensitivity, in J/m2 SIST EN 14897:2006
3.19 UV lamp radiator which produces UV light 3.20 UV device general expression for products using UV light to irradiate water flow through, with the purpose of inactivating microrganisms being present in the water 3.21 UV disinfection device device designed to disinfect water 3.22 UV bactericidal treatment device device designed for bactericidal water treatment 3.23 turbidity reduction of optical transmittance of a liquid caused by the presence of undissolved matter 3.24 UV transmittance (% T100) spectral transmission rate at a wavelength of 254 nm at an optical path length in the medium of 100 mm, in % NOTE In general, the UV transmittance includes the influence of attenuation and absorption of the through passing medium. The UV transmittance is measur
...