Determination of the freeze-thaw resistance of autoclaved aerated concrete

This document specifies a method of determining the freeze-thaw resistance of autoclaved aerated concrete manufactured according to prEN 12602 or EN 771-4.

Bestimmung des Frost-Tau-Widerstandes von dampfgehärtetem Porenbeton

Dieses Dokument legt ein Verfahren fest zur Bestimmung des Frost-Tau-Widerstands von dampfgehärtetem Porenbeton, der nach prEN 12602 oder EN 771-4 hergestellt wird.

Détermination de la résistance au gel/dégel du béton cellulaire autoclavé

Le présent document spécifie une méthode de détermination de la résistance au gel/dégel du béton cellulaire autoclavé fabriqué conformément au prEN 12602 ou à l’EN 771-4.

Določanje obstojnosti avtoklaviranega celičastega betona proti zamrzovanju-tajanju

General Information

Status
Withdrawn
Publication Date
05-Jun-2007
Withdrawal Date
02-Mar-2010
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
03-Mar-2010
Completion Date
03-Mar-2010

Relations

Buy Standard

Standard
EN 15304:2008
English language
15 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.PU]RYDQMXWDMDQMXBestimmung des Frost-Tau-Widerstandes von dampfgehärtetem PorenbetonDétermination de la résistance au gel/dégel du béton cellulaire autoclavéDetermination of the freeze-thaw resistance of autoclaved aerated concrete91.100.30Beton in betonski izdelkiConcrete and concrete productsICS:Ta slovenski standard je istoveten z:EN 15304:2007SIST EN 15304:2008en,fr,de01-november-2008SIST EN 15304:2008SLOVENSKI
STANDARD



SIST EN 15304:2008



EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 15304June 2007ICS 91.100.30 English VersionDetermination of the freeze-thaw resistance of autoclavedaerated concreteDétermination de la résistance au gel/dégel du bétoncellulaire autoclavéBestimmung des Frost-Tau-Widerstandes vondampfgehärtetem PorenbetonThis European Standard was approved by CEN on 10 May 2007.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2007 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 15304:2007: ESIST EN 15304:2008



EN 15304:2007 (E) 2 Contents Page Foreword.3 1 Scope.4 2 Normative references.4 3 Principle.4 4 Apparatus.4 5 Test specimens.5 6 Testing procedure.6 7 Test results.8 8 Test report.9 Annex A (informative)
Determination of the loss in mass and compressive strength.10 Annex B (informative)
Flow chart of freeze-thaw test.13 Bibliography.15
Figures Figure 1 – Cutting scheme.6
SIST EN 15304:2008



EN 15304:2007 (E) 3 Foreword This document (EN 15304:2007) has been prepared by Technical Committee CEN/TC 177 “Prefabricated reinforced components of autoclaved aerated concrete or light-weight aggregate concrete with open structure”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by December 2007, and conflicting national standards shall be withdrawn at the latest by December 2007. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic,
...