Gas-fired sorption appliances for heating and/or cooling with a net heat input not exceeding 70 kW - Part 6: Calculation of seasonal performances

1.1   Scope of EN 12309
Appliances covered by this standard include one or a combination of the following:
-   gas-fired sorption chiller;
-   gas-fired sorption chiller/heater;
-   gas-fired sorption heat pump.
This European Standard applies to appliances designed to be used for space heating or cooling or refrigeration with or without heat recovery.
This European Standard applies to appliances having flue gas systems of type B and type C (according to CEN/TR 1749) and to appliances designed for outdoor installations. EN 12309 does not apply to air conditioners, it only applies to appliances having:
-   integral burners under the control of fully automatic burner control systems,
-   closed system refrigerant circuits in which the refrigerant does not come into direct contact with the water or air to be cooled or heated,
-   mechanical means to assist transportation of the combustion air and/or the flue gas.
The above appliances can have one or more primary or secondary functions (i.e. heat recovery - see definitions in EN 12309 1:2014).
In the case of packaged units (consisting of several parts), this European Standard applies only to those designed and supplied as a complete package.
The appliances having their condenser cooled by air and by the evaporation of external additional water are not covered by EN 12309.
Installations used for heating and/or cooling of industrial processes are not within the scope of EN 12309.
All the symbols given in this text should be used regardless of the language used.
1.2   Scope of this Part 6 to EN 12309
This part of EN 12309 specifies the calculation methods of seasonal performances for gas-fired sorption appliances for heating and/or cooling with a net heat input not exceeding 70 kW. It deals in particular with the calculation methods of reference seasonal performances in cooling and heating mode for monovalent and bivalent appliances.
NOTE   This European Standard serves as an input for the calculation of the system energy efficiency in heating mode of specific heat pump systems in buildings, as stipulated in EN 15316-4-2.

Gasbefeuerte Sorptions-Geräte für Heizung und/oder Kühlung mit einer Nennwärmebelastung nicht über 70 kW - Teil 6: Berechnung der saisonalen Effizienzkennzahlen

Appareils à sorption fonctionnant au gaz pour le chauffage et/ou le refroidissement de débit calorifique sur PCI inférieur ou égal à 70 kW - Partie 6 : Calcul des performances saisonnières

Absorpcijske in adsorpcijske plinske naprave za gretje in/ali hlajenje z grelno močjo do vključno 70 kW - 6. del: Izračun sezonske zmogljivosti

General Information

Status
Not Published
Publication Date
02-Oct-2024
Current Stage
4060 - Closure of enquiry - Enquiry
Start Date
16-Mar-2023
Due Date
08-Feb-2023
Completion Date
16-Mar-2023

Relations

Buy Standard

Draft
prEN 12309-6:2023
English language
47 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
oSIST prEN 12309-6:2023
01-januar-2023
Absorpcijske in adsorpcijske plinske naprave za gretje in/ali hlajenje z grelno
močjo do vključno 70 kW - 6. del: Izračun sezonske zmogljivosti
Gas-fired sorption appliances for heating and/or cooling with a net heat input not
exceeding 70 kW - Part 6: Calculation of seasonal performances
Gasbefeuerte Sorptions-Geräte für Heizung und/oder Kühlung mit einer
Nennwärmebelastung nicht über 70 kW - Teil 6: Berechnung der saisonalen
Effizienzkennzahlen
Appareils à sorption fonctionnant au gaz pour le chauffage et/ou le refroidissement de
débit calorifique sur PCI inférieur ou égal à 70 kW - Partie 6 : Calcul des performances
saisonnières
Ta slovenski standard je istoveten z: prEN 12309-6
ICS:
27.080 Toplotne črpalke Heat pumps
91.140.30 Prezračevalni in klimatski Ventilation and air-
sistemi conditioning systems
oSIST prEN 12309-6:2023 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 12309-6:2023

---------------------- Page: 2 ----------------------
oSIST prEN 12309-6:2023


DRAFT
EUROPEAN STANDARD
prEN 12309-6
NORME EUROPÉENNE

EUROPÄISCHE NORM

December 2022
ICS Will supersede EN 12309-6:2014
English Version

Gas-fired sorption appliances for heating and/or cooling
with a net heat input not exceeding 70 kW - Part 6:
Calculation of seasonal performances
Appareils à sorption fonctionnant au gaz pour le Gasbefeuerte Sorptions-Geräte für Heizung und/oder
chauffage et/ou le refroidissement de débit calorifique Kühlung mit einer Nennwärmebelastung nicht über 70
sur PCI inférieur ou égal à 70 kW - Partie 6 : Calcul des kW - Teil 6: Berechnung der saisonalen
performances saisonnières Effizienzkennzahlen
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 299.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 12309-6:2022 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 12309-6:2023
prEN 12309-6:2022(E)
Contents Page

European foreword . 4
1 Scope . 5
1.1 Scope of EN 12309 . 5
1.2 Scope of this Part 6 to EN 12309 . 5
2 Normative references . 6
3 Terms and definitions . 6
4 Calculation methods for reference SGUE and SAEF in cooling mode . 6
4.1 General. 6
4.2 Part load conditions . 7
4.2.1 General. 7
4.2.2 Air-to-water appliances . 7
4.2.3 Water-to-water and brine-to-water appliances . 8
4.3 Calculation of reference SGUEc . 8
4.4 Calculation of reference SAEFc . 9
4.5 Calculation of reference annual cooling demand (Q ) . 10
refc
4.6 Calculation of reference SAEFc . 10
on
4.7 Procedures for the determination of GUEc / AEFc values . 10
5 Calculation methods for reference seasonal performance in heating mode . 11
5.1 General. 11
5.2 Part load conditions . 12
5.2.1 General. 12
5.2.2 Air-to-water appliances . 13
5.2.3 Water-to-water and brine-to-water appliances . 16
5.3 Calculation of reference SPERh . 19
5.4 Calculation of reference SGUEh . 19
5.5 Calculation of reference SAEFh . 21
5.6 Calculation of reference annual heating demand (Q ) . 22
refh
5.7 Calculation of reference SAEFh . 22
on
5.8 Procedures for the determination of GUEh / AEFh values . 23
Annex A (informative) Calculation example for reference SGUEc and SAEFc . 24
Annex B (informative) Calculation example for reference SGUEh, SAEFh and SPERh . 26
Annex C (normative) Number of hours in thermostat off mode, stand-by mode and off mode
for reference SAEFc and SAEFh calculation . 28
Annex D (normative) Calculation of the reference seasonal performance in heating mode for
bivalent appliances . 32
D.1 General. 32
D.2 Determination of supplementary heater efficiency and heating capacity . 32
D.2.1 General. 32
D.2.2 Supplementary boiler . 32
2

---------------------- Page: 4 ----------------------
oSIST prEN 12309-6:2023
prEN 12309-6:2022 (E)
D.2.3 Supplementary resistor. 33
D.3 Determination of GUEh and AEFh . 33
D.4 Seasonal performance figures for the bivalent appliance as a whole . 34
D.4.1 General . 34
D.4.2 Supplementary boiler . 34
D.4.3 Supplementary resistor. 35
D.5 Seasonal performance figures for the sole heat pumps appliance during active mode
. 36
Annex E (normative) Procedures for the determination of GUEh, AEFh and SAEFh value with
multiple identical heat pumps . 38
E.1 General . 38
E.2 Calculation procedure for GUEh and AEFh for fixed capacity heat pumps . 38
E.3 Calculation procedure for GUEh and AEFh for variable capacity heat pumps . 39
E.4 Calculation procedure for SAEFh . 40
Annex F (normative) Calculation of seasonal space heating energy efficiency for monovalent
or bivalent gas-driven sorption heat pump based heating appliances . 41
Annex ZA (informative) Relationship between this European Standard and the ecodesign
requirements of Commission Regulation (EU) No 813/2013 of 2 August 2013 [OJEU L
239/136, 6.9.2013] aimed to be covered . 44
Annex ZB (informative) Relationship between this European Standard and the energy
labelling requirements of Commission Delegated Regulation (EU) No 811/2013 of 18
February 2013 [OJEU L 239/1, 6.9.2013] aimed to be covered . 45
Bibliography . 47


3

---------------------- Page: 5 ----------------------
oSIST prEN 12309-6:2023
prEN 12309-6:2022(E)
European foreword
This document (prEN 12309-6:2022) has been prepared by Technical Committee CEN/TC 299 “Gas-fired
sorption appliances, indirect fired sorption appliances, gas-fired endothermic engine heat pumps and
domestic gas-fired washing and drying appliances”, the secretariat of which is held by UNI.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 12309-6:2014.
This document includes the following significant technical changes with respect to EN 12309-6:2014:
— Terminology has been aligned to Commission Regulation (EU) No 813/2013 of 2 August 2013 and
Commission Delegated Regulation (EU) No 811/2013 of 18 February 2013;
— Heating temperature profile 45 °C has been eliminated;
— Optional testing points have been added.
This standard comprises parts under the general title, Gas-fired sorption appliances for heating and/or
cooling with a net heat input not exceeding 70 kW. A list of all parts in a series can be found on the CEN
website.
This document will be reviewed whenever new mandates could apply.
This document has been prepared under a Standardization Request given to CEN by the European
Commission and the European Free Trade Association, and supports essential requirements of
EU Directive(s) / Regulation(s).
For relationship with EU Directive(s) / Regulation(s), see informative Annex ZA and ZB which are
integral parts of this document.
4

---------------------- Page: 6 ----------------------
oSIST prEN 12309-6:2023
prEN 12309-6:2022 (E)
1 Scope
1.1 Scope of EN 12309
Appliances covered by this document include one or a combination of the following:
— gas-fired sorption chiller;
— gas-fired sorption chiller/heater;
— gas-fired sorption heat pump.
This document applies to appliances designed to be used for space heating or cooling or refrigeration
with or without heat recovery.
This document applies to appliances having flue gas systems of Type B and Type C (according to
EN 1749:2020) and to appliances designed for outdoor installations, including Type A. EN 12309 does
not apply to air conditioners, it only applies to appliances having:
— integral burners under the control of fully automatic burner control systems,
— closed system refrigerant circuits in which the refrigerant does not come into direct contact with the
water or air to be cooled or heated,
— mechanical means to assist transportation of the combustion air and/or the flue gas.
The above appliances can have one or more primary or secondary functions (i.e. heat recovery - see
definitions in prEN 12309-1:2022).
In the case of packaged units (consisting of several parts), this European Standard applies only to those
designed and supplied as a complete package.
The appliances having their condenser cooled by air and by the evaporation of external additional water
are not covered by EN 12309.
Installations used for heating and/or cooling of industrial processes are not within the scope of EN 12309.
All the symbols given in this text should be used regardless of the language used.
1.2 Scope of this Part 6 to EN 12309
This part of EN 12309 specifies the calculation methods of seasonal performances for gas-fired sorption
appliances for heating and/or cooling with a net heat input not exceeding 70 kW. It deals in particular
with the calculation methods of reference seasonal performances in cooling and heating mode for
monovalent and bivalent appliances.
5

---------------------- Page: 7 ----------------------
oSIST prEN 12309-6:2023
prEN 12309-6:2022(E)
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
1
prEN 12309-1:2022 , Gas-fired sorption appliances for heating and/or cooling with a net heat input not
exceeding 70 kW — Part 1: Terms and definitions
2
prEN 12309-3:2022 , Gas-fired sorption appliances for heating and/or cooling with a net heat input not
exceeding 70 kW - Part 3: Requirements, test conditions and test methods
EN 15502-1:2021, Gas-fired heating boilers - Part 1: General requirements and tests
3 Terms and definitions
For the purposes of this document, the terms and definitions given in prEN 12309-1:2022 apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp/
— IEC Electropedia: available at https://www.electropedia.org/
4 Calculation methods for reference SGUE and SAEF in cooling mode
4.1 General
The calculation of the reference Seasonal Gas Utilization Efficiency ratio in cooling mode (SGUEc) and
reference Seasonal Auxiliary Energy factor in cooling mode (SAEFc) follows from the application of the
bin method, where the part load Gas Utilization Efficiency ratio in cooling mode (GUEc) and Auxiliary
Energy Factor in cooling mode (AEFc) at each bin temperature is determined via linear interpolation of
the respective part load values at the reference part load conditions A, B, C and D.
The part load conditions A, B, C, D provide the part load ratios and the temperature test conditions at four
reference outdoor air dry bulb temperatures: 35 °C, 30 °C, 25 °C and 20 °C.
The part load ratio corresponding to a given outdoor temperature Tj is defined according to Formula (1):
PLRc Tj=Tj−16 / 35−16 (1)
( ) ( ) ( )
At part load condition A, the declared capacity of the appliance is assumed equal to the building load (i.e.
capacity ratio = 100 %).
At part load conditions B, C and D, the declared capacity of the appliance is higher than the building load.
The capacity ratio (CR), i.e. the ratio of the cooling load (Pc) over the declared capacity (DC) of the
appliance at the same temperature conditions, is lower than one. In such conditions, the GUEc and AEFc
are affected by both temperature test conditions and capacity ratio. The methods for the determination
of GUEc and AEFc are defined in prEN 12309-3:2022.

1
Currently in preparation.
2
Currently in preparation.
6

---------------------- Page: 8 ----------------------
oSIST prEN 12309-6:2023
prEN 12309-6:2022 (E)
4.2 Part load conditions
4.2.1 General
For the indoor heat exchanger both fan coil and floor cooling applications are considered.
For the fan coil application, appliances which do, and do not, allow variations of the outlet water
temperature with the outdoor temperature are considered. Variable outlet temperatures shall only be
applied when the programming unit provides an outdoor air temperature dependant modification of the
outlet temperature.
4.2.2 Air-to-water appliances
Table 1 — Part load conditions for the seasonal performance calculation in cooling mode of air-
to-water appliances
Outdoor heat
Indoor heat exchanger
exchanger
Air dry bulb Fan coil application Floor cooling
temperature application
Inlet / outlet water temperatures
 Part load ratio
°C Inlet / outlet
°C
water
temperatures
Fixed outlet Variable outlet
°C
A 1 35 12 / 7 12 / 7 23 / 18
(30–16) / (35–
a a a
B 30 / 7 / 8,5 / 18
16)
(25–16) / (35–
a a a
C 25 / 7 / 10 / 18
16)
(20–16) / (35–
a a a
D 20 / 7 / 11,5 / 18
16)
a
 With the water flow rate as determined during standard rating test with a fixed water flow rate.
7

---------------------- Page: 9 ----------------------
oSIST prEN 12309-6:2023
prEN 12309-6:2022(E)
4.2.3 Water-to-water and brine-to-water appliances
Table 2 — Part load conditions for the seasonal performance calculation in cooling mode of
water-to-water appliances and brine to water appliances
 Part load Outdoor heat exchanger Indoor heat exchanger
ratio
Cooling tower Ground couple Dry cooler Fan coil Floor cooling
application d application application application application
(water or
Inlet/outlet w Inlet/outlet wa Inlet/outlet wate Inlet/outlet
brine)
ater ter r temperatures water
temperatures Inlet/outlet wa temperatures temperatures
°C
ter
°C °C °C
Fixed Variable
temperatures
outlet outlet
°C
A 1 30 / 35 10 / 15 50 / 55 12 / 7 12 / 7 23 / 18
a a a a a a
B (30– 26 / 10 / 45 /  / 7 / 8,5 / 18
16) / (35
–16)
a a a a a a
C (25– 22 / 10 / 40 /  / 7 / 10 / 18
16) / (35

–16)
a a a a a a
D (20– 18 / 10 / 35 /  / 7 / 11,5 / 18
16) / (35
–16)
a
 With the water flow rate as determined during standard rating test with a fixed water flow rate.
4.3 Calculation of reference SGUEc
The calculation of the reference Seasonal Gas Utilization Efficiency ratio in cooling mode (SGUEc) that
applies to all types of appliances is given by Formula (2):
n
hj×Pc Tj
( )

j=1
SGUEc= (2)
Pc Tj
n ( )
hj×

j=1
GUEc Tj
( )
where
Tj is the bin temperature;
j is the bin number;
n is the number of bins;
Pc(Tj) is the cooling load of the building not exceeding the appliance declared capacity at the
corresponding temperature Tj;
hj is the number of bin hours occurring at the corresponding temperature Tj;
GUEc(Tj) is the GUEc of the appliance for the corresponding temperature Tj.
The values to be used for j, Tj and hj are determined in Table 3.
8

---------------------- Page: 10 ----------------------
oSIST prEN 12309-6:2023
prEN 12309-6:2022 (E)
Table 3 — bin number j, outdoor bin temperature Tj in °C and number of hours per bin hj
corresponding to the reference cooling season
j (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
T (°C) 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
j
h (h) 205 227 225 225 216 215 218 197 178 158 137 109 88 63 39 31 24 17 13 9 4 3 1 0
j
The cooling load that is not exceeding the appliance declared capacity is determined by multiplying the
full load value (P ) with the part load ratio PLRc(Tj) of the corresponding bin:
design,c
Pc Tj P×PLRc Tj (3)
( ) ( )
designc
where PLRc(Tj) is:
— defined according to Formula (1) for Tj less than or equal to 35 °C;
— always 1 for Tj greater than 35 °C.
The GUEc values at each bin are determined via interpolation of the GUEc values at part load conditions A,
B, C and D as defined in 4.1.
For part load conditions above part load condition A, the same GUEc values as for condition A shall be
used.
For part load conditions below part load condition D, the same GUEc values as for condition D shall be
used.
4.4 Calculation of reference SAEFc
The calculation of the reference Seasonal Auxiliary Energy Factor in cooling mode (SAEFc) that applies to
all types of appliances is given by reference annual cooling demand divided by the annual electricity
consumption.
The annual electricity consumption includes the power consumption during active mode, thermostat off
mode, standby mode and off mode.
Q
refc
SAEFc= (4)
Q
ref
+H ×P +H ×+P H ×P
TO TO SB SB OFF OFF
SAEFc
on
where
Qref is the reference annual cooling demand, expressed in kWh, as defined in 4.5;
c
SAEFcon is the Seasonal Auxiliary Energy Factor in cooling mode and active mode, as
defined in 4.6;
H , H , H are the number of hours the appliance is considered to work in respectively
TO SB OFF
thermostat off mode, standby mode and off mode. The number of hours to be used
for cooling is indicated in Annex C;
P , P , P are the electricity consumption during respectively thermostat off mode, standby
TO SB OFF
mode and off mode, expressed in kW. The measurement of P , P , P shall be
TO SB OFF
made according to prEN 12309-3:2022.
9
=

---------------------- Page: 11 ----------------------
oSIST prEN 12309-6:2023
prEN 12309-6:2022(E)
4.5 Calculation of reference annual cooling demand (Qrefc)
The reference annual cooling demand is expressed in kWh and can be calculated as the design cooling
load (P ) multiplied by the number of equivalent cooling hours (H ):
design,c ec
QP×H (5)
refc designc ec
The number of equivalent cooling hours (H ) can be found in Annex C.
ec
4.6 Calculation of reference SAEFcon
The reference SAEFc is determined as follows:
on
n
hj×Pc Tj
( )

j=1
SAEFc = (6)
on
Pc Tj
n ( )
hj×

j=1
AEFc Tj
( )
where
Tj is the bin temperature;
j is the bin number;
n is the number of bin;
Pc(Tj) is the cooling load of the building for the corresponding temperature Tj;
hj is the number of bin hours occurring at the corresponding temperature Tj;
AEFc (Tj) is the AEFc values of the appliance for the corresponding temperature Tj.
The values to be used for j, Tj and hj are determined in Table 3.
The cooling load Pc(Tj) shall be determined according to Formula (3).
The AEFc values at each bin are determined via interpolation of the AEFc values at part load conditions
A, B, C and D as defined in 4.1.
For part load conditions above part load condition A, the same AEFc values as for condition A shall be
used.
For part load conditions below part load condition D, the same AEFc values as for condition D shall be
used.
4.7 Procedures for the determination of GUEc / AEFc values
In part load condition A (full load), the declared capacity of an appliance is considered equal to the cooling
load (P ). Accordingly, the test methods at full capacity shall be used, as defined in
design,c
prEN 12309-3:2022.
In part load conditions B, C, D, the test methods at reduced capacity shall be used, as defined in
prEN 12309-3:2022.
10
=

---------------------- Page: 12 ----------------------
oSIST prEN 12309-6:2023
prEN 12309-6:2022 (E)
5 Calculation methods for reference seasonal performance in heating mode
5.1 General
For the purpose of calculating the reference seasonal performance in heating mode, three reference
climatic conditions are defined: average (A), warmer (W) and colder (C).
The relevant reference design outdoor temperature for heating (T ) and bivalent temperature
design,h
(T ) values are set as follows:
bivalent
Table 4 — Design temperature and bivalent temperature upper limit for the different reference
heating seasons
Dry bulb temperature conditions
Reference Heating
Season
T T upper limit
design,h bivalent
Average (A) −10 °C 2 °C
Warmer (W) +2 °C +7 °C
Colder (C) −22 °C −7 °C
For bivalent appliances, T can be any value between T and the T upper limit. Once T
bivalent design,h bivalent bivalent
is defined in dry bulb, the corresponding wet bulb temperature shall be calculated as dry bulb
temperature minus 1 K. For monovalent appliances, T shall be assumed equal to T .
bivalent design,h
For air to water appliances, the declared Operation Limit Temperature (TOL) of the heat pump appliance
shall also be considered. TOL higher than T is an acceptable condition only for bivalent appliances.
design,h
If TOL is lower than T , TOL is not taken into account for the calculation of the seasonal performance
design,h
and it can be assumed equal to T .
design,h
The calculation of the seasonal performance follows from the application of the bin method, where the
part load Gas Utilization Efficiency ratio in heating mode (GUEh) and Auxiliary Energy Factor in heating
mode (AEFh) at each bin temperature is determined via linear interpolation of the respective part load
values at the reference part load conditions A, B, C, D, E, F and G.
The part load conditions A, B, C, D and G provide the part load ratios and the temperature test conditions
at five reference outdoor air dry bulb temperatures: −7 °C, +2 °C, +7 °C, +12 °C and −15 °C.
The part load conditions E and F provide the part load ratios and temperature test conditions at the
appliance operation limit outdoor temperature (TOL) and at the appliance bivalent outdoor temperature
(T ), respectively.
bivalent
different from A, B, C, D, E, F and G can
Optional test conditions at outdoor air dry bulb temperatures Tj
be measured; inlet/outlet temperatures shall be determined via linear interpolation between the two
closest reference part load conditions A, B, C, D, E, F and G. Optional testing points, if used for the
calculation of seasonal performance, shall be declared.
The part load ratio corresponding to a given outdoor temperature Tj is defined according to Formula (7):
PLRh Tj=Tj−−16 / T 16 (7)
( ) ( ) ( )
designh
At part load conditions for which the outdoor temperature is lower than or equal to the defined T
bivalent
temperature, the appliance declared capacity is lower than or equal to the requested heating load. In this
condition, the appliance operates at its maximum capacity and the gap between heating load and
appliance declared capacity is covered by a supplementary heater. The GUEh and AEFh at full capacity
are to be used.
11

---------------------- Page: 13 ----------------------
oSIST prEN 12309-6:2023
prEN 12309-6:2022(E)
At the T part load condition (F), the appliance’s declared capacity is equal to the requested heating
bivalent
load. In this condition, the appliance operates at its maximum capacity and the supplementary heater (if
any) is turned off. The GUEh and AEFh at full capacity are to be used.
At any other part load conditions, the declared capacity of the appliance is larger than the building load.
Accordingly, the supplementary heater (if any) is turned off and the appliance capacity ratio (CR), i.e. the
ratio of the heating load (Ph) over the declared capacity (DC) of the appliance at the same temperature
conditions, is lower than 1. The GUEh and AEFh are affected by both temperature test conditions and
capacity ratio. The methods for the determination of GUEh and AEFh are defined in prEN 12309-3:2022.
5.2 Part load conditions
5.2.1 General
The part load conditions for each type of appliance (air-to-water, water-to-water and brine-to water),
reference h
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.