Lightning Protection Components (LPC) - Part 5: Requirements for earth electrode inspection housings and earth electrode seals

This European Standard specifies the requirements and tests for - earth electrode inspection housings (earth pit), - earth electrode seals. Lightning protection components (LPC) may also be suitable for use in hazardous atmospheres. Regard should then be taken of the extra requirements necessary for the components to be installed in such conditions.

Bitzschutzbauteile - Teil 5: Anforderungen an Revisionskästen und Erderdurchführungen

Diese Europäische Norm legt die Anforderungen und Prüfungen fest für - Revisionskästen; - Erderdurchführungen. Blitzschutzbauteile können auch für die Anwendung in gefährlichen Atmosphären geeignet sein. Es sollten dann die besonderen Anforderungen, die für den Einbau dieser Bauteile unter solchen Bedingungen notwendig sind, beachtet werden.

Composants de protection contre la foudre (CPF) - Partie 5: Prescriptions pour les regards de visite et les joints d'étanchéité des électrodes de terre

Cette Norme Européenne spécifie les exigences et les essais pour - les regards de visite (regard de terre), - les joints d’étanchéité de piquet de terre. Les composants de protection contre la foudre (CPF) peuvent aussi être employés dans des atmosphères dangereuses. Dans ce cas, il convient de veiller à ce que les caractéristiques des composants soient en adéquation avec ces conditions.

Elementi za zaščito pred strelo (LPC) - 5. del: Zahteve za merilne omarice ozemljil in tesnjenje izolacije pri ozemljilih

General Information

Status
Withdrawn
Publication Date
14-Jan-2009
Withdrawal Date
30-Nov-2011
Drafting Committee
Parallel Committee
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
28-Jul-2014
Completion Date
28-Jul-2014

Relations

Buy Standard

Standard
EN 50164-5:2009
English language
9 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-junij-2009
(OHPHQWL]D]DãþLWRSUHGVWUHOR /3& GHO=DKWHYH]DPHULOQHRPDULFHR]HPOMLO
LQWHVQMHQMHL]RODFLMHSULR]HPOMLOLK
Lightning Protection Components (LPC) -- Part 5: Requirements for earth electrode
inspection housings and earth electrode seals
Bitzschutzbauteile -- Teil 5: Anforderungen an Revisionskästen und
Erderdurchführungen
Composants de protection contre la foudre (CPF) -- Partie 5: Prescriptions pour les
regards de visite et les joints d'étanchéité des électrodes de terre
Ta slovenski standard je istoveten z: EN 50164-5:2009
ICS:
91.120.40 =DãþLWDSUHGVWUHOR Lightning protection
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 50164-5
NORME EUROPÉENNE
January 2009
EUROPÄISCHE NORM
ICS 91.120.40
English version
Lightning Protection Components (LPC) -
Part 5: Requirements for earth electrode inspection housings
and earth electrode seals
Composants de protection  Bitzschutzbauteile -
contre la foudre (CPF) - Teil 5: Anforderungen
Partie 5: Prescriptions pour les regards an Revisionskästen und
de visite et les joints d'étanchéité Erderdurchführungen
des électrodes de terre
This European Standard was approved by CENELEC on 2008-12-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: avenue Marnix 17, B - 1000 Brussels

© 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50164-5:2009 E
Foreword
This European Standard was prepared by the Technical Committee CENELEC TC 81X, Lightning
protection.
The text of the draft was submitted to the Unique Acceptance Procedure and was approved by
CENELEC as EN 50164-5 on 2008-12-01.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2009-12-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2011-12-01
__________
– 3 – EN 50164-5:2009
Contents
1 Scope . 4
2 Normative references . 4
3 Definitions . 4
4 Requirements . 4
4.1 Documentation . 4
4.2 Earth electrode inspection housing . 5
4.3 Earth electrode seal . 5
5 Marking . 5
6 Tests . 5
6.1 General . 5
6.2 Earth electrode inspection housing . 6
6.3 Earth electrode seal . 7
6.4 Marking test . 8
6.5 Acceptance criteria . 8
7 Electromagnetic compatibility (EMC) . 8
8 Structure and content of the test report . 8
8.1 Report identification . 8
8.2 Sample description . 9
8.3 Standards and references . 9
8.4 Test procedure . 9
8.5 Testing equipment, description . 9
8.6 Results and parameters recorded . 9
Figures
Figure 1 Test arrangement . 6
Figure 2 Test arrangement . 7

1 Scope
This European Standard specifies the requirements and tests for
− earth electrode inspection housings (earth pit),
− earth electrode seals.
Lightning protection components (LPC) may also be suitable for use in hazardous atmospheres.
Regard should then be taken of the extra requirements necessary for the components to be installed
in such conditions.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 62305-1, Protection against lightning – Part 1: General principles (IEC 62305-1)
EN 62305-3, Protection against lightning – Part 3: Physical damage to structures and life hazard
(IEC 62305-3, mod.)
EN 62305-4, Protection against lightning – Part 4: Electrical and electronic systems within structures
(IEC 62305-4)
3 Definitions
For the purposes of this document, the following terms and definitions apply.
3.1
earth electrode inspection housing
metallic or non-metallic enclosure that houses the down conductor/earth termination connection for
inspection and testing purposes. This consists of a housing and a removable lid
3.2
earth electrode seal
water pressure seal used in conjunction with an earth rod electrode that passes through the
foundation of the building, so preventing ground water from entering the building
4 Requirements
All earth electrode inspection housings and earth electrode seals shall be so designed and
constructed that in normal use their performance is reliable and without danger to persons and the
surrounding.
The choice of a material depends on its ability to match the particular application requirements.
4.1 Documentation
The manufacturer or supplier of the earth electrode inspection housing and earth electrode seals shall
provide adequate information in his literature to ensure that the installer can select and install the
materials in a suitable and safe manner, in accordance with EN 62305-3.
Compliance is checked by inspection.

– 5 – EN 50164-5:2009
4.2 Earth electrode inspection housing
The design of the earth electrode inspection housing shall be such that it carri
...