prEN IEC 60076-2:2026
(Main)Power transformers - Part 2: Temperature rise for liquid-immersed transformers
- Status
- Not Published
- Publication Date
- 02-Mar-2028
- Technical Committee
- CLC/TC 14 - Power transformers
- Current Stage
- 4020 - Enquiry circulated - Enquiry
- Start Date
- 25-Sep-2026
- Due Date
- 31-Jan-2024
- Completion Date
- 31-Jan-2024
prEN IEC 60076-2:2026 is a CLC draft of IEC 60076-2 for power transformers. It specifies temperature rise measurement and test procedures for liquid-immersed transformers, so users can check whether transformer liquids, windings, and related parts meet the declared thermal requirements. It is written for transformer manufacturers, test laboratories, and customers who need factory verification, thermal data, or overload assessment.
What does prEN IEC 60076-2:2026 specify?
prEN IEC 60076-2:2026 applies to liquid-immersed transformers and gives the methods for temperature rise tests and thermal performance measurement. In practice, it tells you how to set up the test, what temperatures to measure, how to derive winding and liquid temperature rises, and how to report the results.
The document is organized into:
- Clause 1 Scope
- Clause 2 Normative references
- Clause 3 Terms and definitions
- Clause 4 Thermal performance measurement, including test methods, calculations, corrections, uncertainty, and dissolved gas-in-liquid analysis
- Annexes A to I, which cover calculation guidance, test techniques, sensor use, gas analysis, exponents, end-of-test detection, and related examples
| Annex | What it covers |
|---|---|
| A | Winding hotspot temperature rise for OFAF and OFWF cooled transformers based on top liquid temperature in tank |
| B | Methods to estimate winding hotspot temperature rises from design data and temperature rise test results |
| C | Techniques used in temperature rise testing of liquid-immersed transformers |
| D | Dissolved gases analysis for the detection of overheating |
| E | Optical fibre and thermocouple sensors for winding hotspot measurements in active and structural parts |
| F | Liquid and winding exponents |
| G | Detection of the end of heat run test sequence with total loss supply |
| H | Typical Heat Sink |
| I | Superposition method for winding resistance determination |
What are the key requirements of prEN IEC 60076-2:2026?
Test purpose and general approach
prEN IEC 60076-2:2026 says temperature rise testing is used to verify the guaranteed temperature rises of the insulation liquid and windings, and it can also reveal overheating from stray flux heating or poor connections. It also allows loading capability to be assessed either by direct measurement or by thermal models based on test data.
For transformers with alternative cooling method ratings, the standard calls for a temperature rise test for each cooling method rating. By agreement, testing may be reduced to the nominal power case if the customer accepts calculated parameters for the other ratings.
Test environment and temperature measurement
prEN IEC 60076-2:2026 sets rules for the external cooling medium, meaning air or water. For air, the document requires controlled conditions, regular readings, and sensor arrangements matched to the cooling method, such as AN and AF arrangements shown in Clause 4.2.1. For water, it requires intake measurement, flow-rate tracking, and flow-weighted averaging when there is more than one intake.
These rules matter because ambient drift can distort the result. The standard therefore requires heat sinks or ambient cans, synchronized automatic recording, and stable airflow around the transformer during the test.
Main test methods
prEN IEC 60076-2:2026 makes the equivalent short-circuit connection the standard method for steady-state temperature rise determination. It also allows, by agreement, rated voltage and current testing with a suitable load, and a back-to-back arrangement for suitable cases.
The standard separates the test outcomes into top liquid, bottom liquid, and average liquid temperature rises at steady state, plus average winding temperature rise and winding hotspot temperature rise. For internal core hotspot temperature rise, the document uses a separate no-load excitation method in Clause 4.3.9.
Shut-down measurement and cooling-down evaluation
prEN IEC 60076-2:2026 requires winding temperature to be determined after shut down from winding resistance measurements. Clause C.1 and C.2 describe how the cooling equipment is handled during the measurement and how the resistance values are extrapolated back to the shut-down instant.
This matters because the temperature keeps changing after power is removed. Annex C therefore provides procedures and a numerical extrapolation method for the cooling-down curve, including a spreadsheet-based approach and validation checks.
Winding hotspot and core hotspot determination
prEN IEC 60076-2:2026 normally determines winding hotspot temperature rise by calculation, with direct measurement used when specified by the customer. Annex B gives the calculation approaches based on design data and test results, while Annex E covers direct fibre optic or thermocouple measurement.
For the internal core hotspot temperature rise, Clause 4.8 gives two methods based on the gradient between the core and either top liquid or bottom liquid at no-load test end. This is important when core or structural part temperatures need to be checked for special design reviews.
Corrections, uncertainty, and gas analysis
prEN IEC 60076-2:2026 allows corrections when the injected test losses or current do not reach the target values, provided steady-state conditions are reached and minimum levels are met. Table 1 gives the exponents used for those corrections, and Annex F explains where exponent values come from.
Clause 4.9 asks for uncertainty estimates in the report, and Clause 4.10 introduces dissolved gas-in-liquid analysis as a way to detect possible local overheating. Annex D gives the sampling and interpretation guidance, including before-and-after testing and optional in-test sampling.
What terms does prEN IEC 60076-2:2026 define?
- external cooling medium - The air or water outside the transformer cooling system that receives heat from the transformer.
- top liquid temperature - The liquid temperature at the top of the tank, representative of the top liquid in the cooling flow stream.
- bottom liquid temperature - The liquid temperature entering the bottom winding.
- average liquid temperature - The average of the top liquid and bottom liquid temperatures.
- average winding temperature - The winding temperature determined from winding d.c. resistance at the end of the temperature rise test.
- hotspot factor - A dimensionless factor used to estimate the local increase of the average winding gradient.
- winding hotspot temperature rise - The difference between winding hotspot temperature and external cooling medium temperature.
- internal core hotspot temperature - The hottest core internal temperature determined from the no-load temperature rise at the highest core excitation and the relevant liquid temperatures.
Who uses prEN IEC 60076-2:2026?
prEN IEC 60076-2:2026 is used by transformer manufacturers, test engineers, and factory laboratories that perform heat-run and thermal performance tests. It is also used by customers, buyers, and quality managers who need to specify acceptance criteria, review test reports, or compare design data with measured thermal behavior.
The document is also relevant to engineers working on cooling systems, hotspot prediction, thermal models, sensor installation, and dissolved gas-in-liquid analysis after testing. In practice, it supports type verification, design validation, and investigation of overheating concerns.
What changed in prEN IEC 60076-2:2026 from the previous edition?
The foreword says this revision replaces the third edition published in 2011 and is a technical revision. The listed changes are:
- the title was changed to Thermal performance measurement and test procedures for liquid-immersed transformers
- the scope was changed to cover liquid-immersed transformers, temperature requirements, and temperature rise test methods
- Clauses 4, 5, and 6 from the 2011 edition were moved to IEC 60076-1, including temperature rise limits and ambient reference values
- the temperature rise test procedures were improved for the new thermal requirements
- the core temperature test and core temperature rise determination were introduced
- Annexes B, D, and E were modified, and Annexes F, G, H, and I were added
Which standards are used with prEN IEC 60076-2:2026?
- IEC 60076-1 - Gives general rules for power transformers and provides related definitions and limits used by this part.
- IEC 60076-7 - Supplies the loading guide used for long-time emergency loading temperature limit considerations.
- IEC 60076-8 - Provides the application guide for practical transformer use.
- IEC 61181 - Gives guidance for dissolved gas analysis on factory tests and liquid sampling interpretation.
- IEC Guide 115 - Gives guidance for applying measurement uncertainty in conformity assessment.
- IEC 60076-19-1 - Gives rules for uncertainty in power transformer loss measurements and related corrections.
- IEC 60076-22-2 - Covers removable radiators used in cooling equipment.
- IEC 60076-22-3 - Covers insulating liquid to air heat exchangers.
- IEC 60076-22-6 - Covers electric fans for transformers.
- ISO 10880 - Gives general principles for infrared thermographic testing.
What does the prEN IEC 60076-2:2026 document contain?
The document contains the test setup rules, sensor placement guidance, calculation methods, correction relations, and reporting-related guidance needed for transformer temperature rise testing. It includes figures for ambient sensor positions, resistance-measurement circuits, cooling-down curves, hotspot sensor placement, and heat-sink examples.
It also contains tables for correction exponents, hotspot-related test data, and gas analysis limits. Annex C provides worked techniques for winding resistance measurement and cooling-down extrapolation, Annex D provides gas analysis criteria, Annex E gives sensor installation guidance, and Annex G gives a data-driven method for detecting the end of a heat-run test under total loss supply.
Relations
- Revises
EN 60076-2:2011 - Power transformers - Part 2: Temperature rise for liquid-immersed transformers - Effective Date
- 23-May-2023
Get Certified
Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)
Italian electrical product certification.

SLG Prüf- und Zertifizierungs GmbH
German testing and certification body.

UL Solutions
Global safety science company with testing, inspection and certification.
Sponsored listings
Frequently Asked Questions
prEN IEC 60076-2:2026 is a draft published by CLC. Its full title is "Power transformers - Part 2: Temperature rise for liquid-immersed transformers". This standard covers: Power transformers - Part 2: Temperature rise for liquid-immersed transformers
Power transformers - Part 2: Temperature rise for liquid-immersed transformers
prEN IEC 60076-2:2026 is classified under the following ICS (International Classification for Standards) categories: 29.180 - Transformers. Reactors. The ICS classification helps identify the subject area and facilitates finding related standards.
prEN IEC 60076-2:2026 has the following relationships with other standards: It is inter standard links to EN 60076-2:2011. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
prEN IEC 60076-2:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 49 B.3 Determination by calculation based on design data
- 50 B.4 Mathematical models for natural and direct forced liquid flow cooling 51 systems based on temperature rise test results
- 52 B.4.1 Core type transformers
- 53 B.4.2 Shell type transformers
- 54 B.5 Mathematical models for forced liquid flow cooling systems
- 55 Annex C (normative) Techniques used in temperature rise testing of liquid-immersed 56 transformers
- 57 C.1 Winding resistance measurement after shut down
- 58 C.1.1 Setting of the cooling equipment during the winding resistance 59 measurement
- 60 C.1.2 Procedure for winding resistance measurement
- 61 C.2 Extrapolation of winding temperature to the shut down
- 62 C.3 A numerical extrapolation procedure of cooling down curve
- 63 Annex D (informative) Dissolved gases analysis for the detection of overheating
- 64 D.1 General
- 65 D.2 Temperature rise test duration
- 66 D.3 Sampling of liquid
- 67 D.4 Gas analysis and result interpretation
- 68 Annex E (informative) Application of optical fibre and thermocouple sensors for 69 winding hotspot measurements in transformer active and structural parts
- 70 E.1 Direct measurement of winding hotspot temperature rise
- 71 E.2 Direct measurement of hotspot temperature rise in core and structural parts
- 72 E.3 Generic rule for determination of core surface and structural part 73 temperature rises
- 74 Annex F (informative) Liquid and Winding exponents
- 75 F.1 General
- 76 F.2 Theoretical approach
- 77 F.3 Extended temperature rise test approach
- 78 Annex G (informative) Detection of the end of heat run test sequence with total loss 79 supply
- 80 G.1 Scope
- 81 G.2 References
- 82 G.3 Terms and definitions
- 83 G.4 Summary of total loss supply heat-run method (context)
- 84 G.5 Data processing procedure (step-by-step)
- 85 G.6 End-of-test detection criteria
- 86 G.7 Reporting
- 87 G.8 Parameterization and adjustable constraints
- 88 G.9 Uncertainty and quality metrics
- 89 G.10 Implementation traceability (Excel/VBA)
- 90 G.11 Data-flow overview
- 91 G.12 Disclaimer
- 92 Annex H (informative) Typical Heat Sink
- 93 H.1 Heat Sink Design
- 94 Annex I (informative) Superposition method for winding resistance determination
- 96 Figure 4-1 – Sensor location around AN cooled transformer without radiator and 97 external cooler, figure illustrates a general piece of cooling equipment
98 Figure 4-2 – Sensor location around a transformer, AN cooling, figure illustrates a 99 general piece of cooling equipment ....................................................................................... 15 100 Figure 4-3 – Example of sensor location around a vertically forced-cooled 101 transformer(..AF), figure illustrates a general piece of cooling equipment ............................. 16 102 Figure 4-4 – Sensor location around a horizontally forced-cooled transformer(..AF) 103 equipped with radiators, figure illustrates a general piece of cooling equipment .................... 16 104 Figure 4-5 – Sensor location around a horizontally forced-cooled transformer with 105 radiators(..AF), figure illustrates a general piece of cooling equipment .................................. 17 106 Figure 4-6 – Example sensor location around a transformer(..AF) equipped with liquid 107 to air heat exchanger ............................................................................................................ 17 108 Figure 4-7 – Example sensor location (..AF) equipped with separated liquid to air heat 109 exchanger ............................................................................................................................. 18 110 Figure 4-8 – Example sensor location (..AF) equipped with liquid to air heat exchanger 111 attached to the tank wall ....................................................................................................... 18 112 Figure B.1 – Temperature rise distribution model .................................................................. 37 113 Figure C.1 – Recommended circuit for transformers with a low resistance winding 114 using two separate direct current sources, one for each winding ........................................... 41 115 Figure C.2 – Alternative recommended circuit using only one direct current source for 116 both windings ........................................................................................................................ 42 117 Figure C.3 – Average winding temperature variation - cooling down curve test ..................... 43 118 Figure C.4 – Extrapolation of the cooling down curve , using the fitting curve 𝜽𝑾𝒕 = 119 𝑨𝟎 − 𝒌𝒕 + 𝑩𝒆 − 𝒕𝑻𝑾 ............................................................................................................... 46 120 Figure C.5 – Average winding temperature variation - cooling down curve test ..................... 48 121 Figure E.1 – Temperature winding rises above top liquid temperature (in tank ...................... 54 122 Figure E.2 – Coil edges, where the sensors should be located in the edge with the 123 higher calculated temperature rise ........................................................................................ 55 124 Figure E.3 – Temperature rises above top liquid temperature at the end of an 8 h 125 thermal no-load test at 110 % supply voltage ........................................................................ 56 126 Figure F.1 – Transformer exponent estimation plots .............................................................. 60 127 Figure G.1 – Data-flow chart ................................................................................................. 63 128 Figure H.1 – Typical heat sink for air temperature measurement ........................................... 64 129 Figure I.1 – Connection circuit for superpositionBibliography ................................................ 65 130 131 132 Table 1 – Exponents for the corrections of temperature rise test results ............................... 32 133 Table A.1 – Winding hotspot temperature rises for some specific transformers 134 determined from conventional heat run test data combined with calculated winding 135 hotspot temperature rise, and from direct fibre-optic measurements ..................................... 34 136 Table C.1 – Example of cooling down curve calculation spreadsheet .................................... 47 137 Table C.3 – Example of cooling down curve calculation spreadsheet – method #2 ................ 48 138 Table D.1 – Minimum detectable value S of gases in liquid ................................................. 51 D 139 Table D.2 – Admissible limits for gas rate increases ............................................................. 51 142 INTERNATIONAL ELECTROTECHNICAL COMMISSION 143 ____________ 144 145 POWER TRANSFORMERS – 146 147 Part 2: Thermal performance measurement and test procedures for liquid- 148 immersed transformers 149 150 151 FOREWORD 152 1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising 153 all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international 154 co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and 155 in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports, 156 Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their 157 preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with 158 may participate in this preparatory work. International, governmental and non-governmental organizations liaising 159 with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for 160 Standardization (ISO) in accordance with conditions determined by agreement between the two organizations. 161 2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international 162 consensus of opinion on the relevant subjects since each technical committee has representation from all 163 interested IEC National Committees.
164 3) IEC Publications have the form of recommendations for international use and are accepted by IEC National 165 Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC 166 Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any 167 misinterpretation by any end user.
168 4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications 169 transparently to the maximum extent possible in their national and regional publications. Any divergence between 170 any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter. 171 5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity 172 assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any 173 services carried out by independent certification bodies.
174 6) All users should ensure that they have the latest edition of this publication.
175 7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and 176 members of its technical committees and IEC National Committees for any personal injury, property damage or 177 other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and 178 expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC 179 Publications.
180 8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is 181 indispensable for the correct application of this publication.
182 9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent 183 rights. IEC shall not be held responsible for identifying any or all such patent rights. 184 International Standard IEC 60076-2 has been prepared by IEC technical committee 14: Power 185 transformers.
186 This first edition cancels and replaces the third edition published in 2011. It is a technical 187 revision.
188 This edition includes the following significant technical changes with respect to the previous 189 edition based on guidance provided by IEC TC 14 AHG 36:
190 a) the title is changed to: Thermal performance measurement and test procedures for liquid- 191 immersed transformers; 192 b) the scope is changed to: This part of IEC 60076 applies to liquid-immersed transformers, 193 verifies compliance with temperature requirements and gives the methods for temperature 194 rise tests; 195 c) the clauses 4, 5, and 6 are moved from edition 2011 to IEC 60076-1 revised document 196 including the temperature rise limits and ambient temperature reference values ;
197 d) the procedures for the temperature rise test were improved in relation to the new thermal 198 requirements; 199 e) the core temperature test and corresponding temperature rise determination is introduced; 200 f) annexes B, D and E are modified, and three informative annexes F, G, H and I are added 201 in order to facilitate the standard application.
202 203 The text of this standard is based on the following documents:
FDIS Report on voting 204 205 Full information on the voting for the approval of this standard can be found in the report on 206 voting indicated in the above table.
207 This publication has been drafted in accordance with the ISO/IEC Directives, Part 2. 208 A list of all parts of the IEC 60076 series can be found, under the general title Power 209 transformers, on the IEC website.
210 The committee has decided that the contents of this publication will remain unchanged until the 211 stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data related to 212 the specific publication. At this date, the publication will be 213 • reconfirmed, 214 • withdrawn, 215 • replaced by a revised edition, or 216 • amended.
217
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates that it contains colours which are considered to be useful for the correct understanding of its contents. Users should therefore print this document using a colour printer.
220 POWER TRANSFORMERS – 221 222 Part 2: Thermal performance measurement and test procedures for liquid- 223 immersed transformers 224 225 226 1 Scope 227 This part of IEC 60076 applies to liquid-immersed transformers, verifies compliance with 228 temperature requirements and gives the methods for temperature rise tests.
229 2 Normative references 230 The following referenced documents are indispensable for the application of this document. For 231 dated references, only the edition cited applies. For undated references, the latest edition of 232 the referenced document (including any amendments) applies.
233 IEC 60076-1, Power transformers – Part 1: General 234 IEC 60076-7, Power transformers – Part 7: Loading guide for mineral-oil-immersed power 235 transformers 236 IEC 60076-8, Power transformers – Part 8: Application guide 237 IEC 61181, Mineral oil-filled electrical equipment – Application of dissolved gas analysis (DGA) 238 to factory tests on electrical equipment 239 IEC Guide 115, Application of measurement uncertainty to conformity assessment activities in 240 the electrotechnical sector 241 IEC 60076-19-1, Power transformers - Part 19 - 1: Rules for the determination of uncertainties 242 in the measurement of the losses of power transformers 243 IEC 60076-22-2, Power transformers - Part 22-2: Power transformer and reactor fittings - 244 Removable radiators 245 IEC 60076-22-3, Power transformers - Part 22-2: Power transformer and reactor fittings - 246 Insulating liquid to air heat exchangers 247 IEC 60076-22-6, Power transformers - Part 22-6: Power transformer and reactor fittings - 248 Electric fans for transformers 249 ISO 10880, Non-destructive testing — Infrared thermographic testing — General principles 250 IEC 60567, Oil-filled electrical equipment - Sampling of free gases and analysis of free and 251 dissolved gases in mineral oils and other insulating liquids – Guidance 252 255 3 Terms and definitions 256 For the purposes of this document, the terms and definitions given in IEC 60076-1 and the 257 following apply.
258 3.1 259 bottom liquid temperature 260 𝜽 261 temperature of the liquid entering the bottom winding 262 3.2 263 bottom liquid temperature rise 264 𝜟𝜽 265 difference between the bottom liquid temperature and the external cooling medium temperature 266 3.3 267 external cooling medium 268 fluid (air or water) external to the transformer cooling system (air or water) into which the heat 269 produced by the transformer losses is transferred 270 3.4 271 𝜽 272 temperature of the external cooling medium 273 temperature of the external cooling medium outside the influence from the transformer 274 3.5 275 top liquid temperature 276 𝜽 277 the temperature of the liquid at the top of the tank, representative of top liquid in the cooling 278 flow stream 279 3.6 280 top liquid temperature rise 281 𝜟𝜽 282 difference between the top liquid temperature and the external cooling medium temperature 283 3.7 284 average liquid temperature 285 𝜽 286 average temperature of the top liquid and bottom liquid temperatures 287 3.8 288 average liquid temperature rise 289 𝜟𝜽 290 difference between the average liquid temperature and the external cooling medium 291 temperature 292 3.9 293 average liquid temperature rise at shut down 294 ∆𝜽 295 difference between the average liquid temperature and the external cooling medium 296 temperature at shut down 297 3.10 298 winding temperature determined from resistance measurement 299 𝜽 300 winding temperature determined from resistance measurements at shut down 302 average liquid temperature at shut down 303 𝜽 304 average temperature of the top liquid and bottom liquid temperatures at shut down 305 3.12 306 average winding temperature 307 𝜽 308 winding temperature determined at the end of temperature rise test from the measurement of 309 winding d.c. resistance 310 3.13 311 average winding temperature rise 312 ∆𝜽 313 difference between the average winding temperature and the external cooling medium 314 temperature 315 3.14 316 average winding gradient 317 𝒈 318 difference between the average winding temperature and the average liquid temperature 319 3.15 320 winding hotspot to top liquid temperature gradient 321 ∆𝜽 322 difference between the winding hotspot temperature and the top liquid temperature 323 3.16 324 winding hottest temperature reading at shut down 325 𝜽 326 hottest measured winding temperature of winding conductors in contact with solid insulation or 327 liquid at shut down 328 3.17 329 top liquid temperature at shut down 330 𝜽 331 temperature of the insulating liquid at the top of the tank at shut down, representative of top 332 liquid in the cooling flow stream 333 3.18 334 hotspot factor 335 𝑯 336 dimensionless factor to estimate the local increase of the average winding gradient due to the 337 additional loss and variation in the liquid flow stream 338 3.19 339 winding hotspot temperature rise 340 ∆𝜽 341 difference between the winding hotspot temperature and the external cooling medium 342 temperature 343 3.20 344 no-load top liquid temperature 345 𝜽 346 temperature of the top liquid at the end of the no-load temperature rise test at the same tank 347 location as the top liquid temperature defined in 3.5 349 no-load bottom liquid temperature 350 𝜽 351 temperature of the bottom liquid at the end of the no-load temperature rise test at the same 352 tank location as the bottom liquid temperature defined in 3.1.
353 3.22 354 internal core hotspot temperature 355 𝜽 356 hottest core internal temperature determined from the no load temperature rise at highest core 357 excitation and the liquid temperatures relevant to the operating condition 358 3.23 359 internal core hotspot temperature rise 360 ∆𝜽 361 the difference between the internal core hotspot temperature and the external cooling medium 362 temperature 363 3.24 364 shut down 365 instant when the power supply is switched off 366 3.25 367 cooling method 368 cooling media type and flow principles, coded by capital letters 369 4 Thermal performance measurement 370 4.1 General 371 The following subclauses describe the procedures for the determination of temperature and 372 temperature rise values during factory testing and also the methods for substituting service 373 loading conditions by equivalent test procedures.
374 The thermal performance measurement is carried out to verify the guaranteed temperature rises 375 in insulation liquid and windings as given in Clause 5.4.3 of IEC 60076-1.
376 NOTE Altitude correction of cooling conditions is given in Clause 5.5 of IEC 60076-1 377 The temperature rise test can also reveal overheating within the transformer due to conditions 378 such as stray flux heating and poor connections. The transformer loading capability can be 379 verified by direct measurement or by application of corresponding thermal models using the 380 data from the test.
381 During a temperature rise test various temperatures may be measured or derived, including:
382 • External cooling medium temperature 383 • Top liquid temperature 384 • Bottom liquid temperature 385 • Average liquid temperature 386 • Average winding temperatures 387 • Internal structural part temperatures 388 • Tank temperature 389 • Internal core hotspot temperature 390 • Winding hotspot temperature 391 NOTE Some of these measurements depend on the presence of temperature sensors 392 During the temperature rise test, the transformer shall be equipped with any relevant protective 393 devices that would be present in service and are within the scope of the contract between 394 customer and manufacturer. Any indication from these devices during the test shall be noted 395 and the case investigated.
396 For transformers designed with alternative cooling method ratings, a temperature rise test shall be 397 performed for each cooling method rating to determine the corresponding temperature rises and 398 thermal parameters. By agreement between manufacturer and customer, the testing may be reduced 399 to the test at the nominal power of the transformer if customer accepts to use the calculated 400 parameters for the other cooling method power ratings.
402 4.2 Temperature of the external cooling media (air or water) 403 The external cooling medium is defined by the third letter code in the cooling method (see IEC 60076- 404 1, Clause 5.2.2) 405 4.2.1 Air temperature 406 For the temperature rise test, the external cooling medium temperature shall be between 10 °C and 407 the maximum external cooling medium temperature at which the winding hotspot temperature shall not 408 exceed the long-time emergency loading temperature limit specified in IEC 60076-7, or the limit 409 specified by the customer, at any point during the test.
410 Where direct winding hotspot measurement is not provided, compliance with this limit shall be 411 assessed by calculation using the measured external cooling medium temperature, the measured 412 liquid temperature, and the calculated winding hotspot-to-top-liquid temperature gradient. The 413 calculation basis shall be documented in the test report.
414 Precautions shall be taken to minimize variations of cooling-air temperature, during the whole test 415 period. Rapid variations in readings shall be prevented by using heat sinks or ambient cans for the 416 temperature sensors. The thermal time constant of the heat sinks shall be approximately 2,5 h, 417 suitable for all transformer designs. A report stating the heat-sink thermal time constant shall be 418 provided by the manufacturer. Informative Annex H provides an example of a heat-sink design that 419 fulfils the time-constant requirement.
...