HD 384.7.711 S1:2003
(Main)Electrical installations of buildings - Part 7-711: Requirements for special installations or locations - Exhibitions, shows and stands
Electrical installations of buildings - Part 7-711: Requirements for special installations or locations - Exhibitions, shows and stands
Gives requirements applying to the temporary electricalinstallations in exhibitions, shows and stands (including mobile and portable displays and equipment) to protect users.
Elektrische Anlagen von Gebäuden - Teil 7-711: Anforderungen für Betriebsstätten, Räume und Anlage besonderer Art - Ausstellungen, Shows und Stände
Installations électriques des bâtiments - Partie 7-711: Règles pour les installations et emplacements spéciaux - Expositions, spectacles et stands
Contient les prescriptions particulières applicables aux installations électriques temporaires des expositions, spectacles et stands (y compris les étalages et le matériels mobiles et portables) afin d'assurer la sécurité des utilisateurs.
Električne inštalacije zgradb – 7-711. del: Zahteve za posebne inštalacije ali prostore – Razstave, predstave in stojnice (IEC 60364-7-711:1998, spremenjen)
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-februar-2004
(OHNWULþQHLQãWDODFLMH]JUDGE±GHO=DKWHYH]DSRVHEQHLQãWDODFLMHDOL
SURVWRUH±5D]VWDYHSUHGVWDYHLQVWRMQLFH,(&VSUHPHQMHQ
Electrical installations of buildings -- Part 7-711: Requirements for special installations or
locations - Exhibitions, shows and stands
Elektrische Anlagen von Gebäuden -- Teil 7-711: Anforderungen für Betriebsstätten,
Räume und Anlage besonderer Art - Ausstellungen, Shows und Stände
Installations électriques des bâtiments -- Partie 7-711: Règles pour les installations et
emplacements spéciaux - Expositions, spectacles et stands
Ta slovenski standard je istoveten z: HD 384.7.711 S1:2003
ICS:
91.140.50 Sistemi za oskrbo z elektriko Electricity supply systems
97.200.99 Druga oprema za razvedrilo Other equipment for
entertainment
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
HARMONIZATION DOCUMENT HD 384.7.711 S1
DOCUMENT D'HARMONISATION
HARMONISIERUNGSDOKUMENT July 2003
ICS 29.020; 91.140.50
English version
Electrical installations of buildings
Part 7-711: Requirements for special installations or locations -
Exhibitions, shows and stands
(IEC 60364-7-711:1998, modified)
Installations électriques des bâtiments Elektrische Anlagen von Gebäuden
Partie 7-711: Règles pour les installations Teil 7-711: Anforderungen für
et emplacements spéciaux - Betriebsstätten, Räume und Anlage
Expositions, spectacles et stands besonderer Art -
(CEI 60364-7-711:1998, modifiée) Ausstellungen, Shows und Stände
(IEC 60364-7-711:1998, modifiziert)
This Harmonization Document was approved by CENELEC on 2003-02-01. CENELEC members are
bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for
implementation of this Harmonization Document on a national level.
Up-to-date lists and bibliographical references concerning such national implementation may be obtained on
application to the Central Secretariat or to any CENELEC member.
This Harmonization Document exists in three official versions (English, French, German).
CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malta,
Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2003 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. HD 384.7.711 S1:2003 E
Foreword
The text of the International Standard IEC 60364-7-711:1998, prepared by IEC TC 64, Electrical
installations and protection against electric shock, together with the common modifications prepared by
SC 64B, Protection against thermal effects, of Technical Committee CENELEC TC 64, Electrical installations
and protection against electric shock, was submitted to the formal vote and was approved by CENELEC as
HD 384.7.711 S1 on 2003-02-01.
The following dates were fixed:
– latest date by which the existence of the HD
has to be announced at national level (doa) 2003-08-01
– latest date by which the HD has to be implemented
at national level by publication of a harmonized
national standard or by endorsement (dop) 2004-02-01
– latest date by which the national standards conflicting
with the HD have to be withdrawn (dow) 2006-02-01
Subclauses which are additional to those in IEC 60364-7-711 are prefixed “Z”.
In this Harmonization Document the common modifications to the International Standard are indicated by
a vertical line in the left margin of the text.
Annexes designated „normative“ are part of the body of the standard.
In this standard, Annexes ZA and ZB are normative.
Annexes ZA and ZB have been added by CENELEC.
____________
- 3 - HD 384.7.711 S1:2003
Contents
Page
Introduction . 4
711.1 Scope, object and fundamental principles . 5
711.2 Definitions. 5
711.3 Assessment of general characteristics. 6
711.4 Protection for safety. 6
711.5 Selection and erection of electrical equipment. 8
711.6 Verification. 10
Annex ZA Normative references to international publications with their corresponding
European publications.11
Annex ZB Special national conditions .13
Introduction
The requirements of this part of IEC 60364 modify or replace certain of the general requirements of
IEC 60364.
The clause numbering of part 7-711 follows the pattern and corresponding references of IEC 60364.
The numbers following the particular number of part 7-711 are those of the corresponding parts or clauses
of IEC 60364.
The absence of reference to a part or a clause means that the general requirements of IEC 60364 are
applicable.
Numbering in parentheses corresponds to the numbering of the “non restructured” IEC 60364 dated
before 2002.
- 5 - HD 384.7.711 S1:2003
711 Exhibitions, shows and stands
711.1 Scope, object and fundamental principles
711.1.1 Scope
The particular requirements of this part of IEC 60364, in association with IEC 60364, parts 1 to 6, apply to
the temporary electrical installations in exhibitions, shows and stands (including mobile and portable
displays and equipment) to protect users.
Unless specifically stated, this part does not apply to exhibits for which requirements are given in the
relevant standards.
This part does not apply to the fixed electrical installation of the building, if any, in which the exhibition,
shows or stands may take place.
711.1.2 Normative references
See Annex ZA.
711.2 Definitions
For the purpose of this part of IEC 60364, the following definitions apply.
711.2.1
exhibition
event intended for the purpose of displaying and/or selling products etc., which can take place in any
suitable location, either a room, building or temporary structure
711.2.2
show
display or performance in any suitable location, either a room, building or temporary structure
711.2.3
stand
area or temporary structure used for display, marketing, sales, entertainment etc.
711.2.4
temporary structure
a unit or a part of a unit including mobile portable units, situated indoors or outdoors, designed and
intended to be assembled and dismantled
711.2.5
temporary electrical installation
electrical installation erected and dismantled at the same time as the stand or the display with which it is
associated
711.2.6
origin of the temporary electrical installation
point on the permanent installation or other source of supply from which electrical energy is delivered
711.3 (711.30) Assessment of general characteristics
711.313 Supplies
The nominal supply voltage of temporary electrical installations in exhibitions, shows and stands shall not
exceed 230/400 a.c. or 500 V d.c.
711.32 (711.5.512.2) Classification of external influences
The external influence conditions of the particular location where temporary electrical installations are
erected, e.g. presence of water, mechanical stresses, shall be taken into account.
711.4 Protection for safety
711.41 Protection against electric shock
711.413 Protection against indirect contact
711.413.1 Protection by automatic disconnection of supply
711.413.1.3 TN system
Where the type of system earthing is TN, the installation shall be TN-S.
[subclause 711.413.1.3.4 deleted]
711.413.1.6 Supplementary equipotential bonding
[subclause 711.413.1.6.1 deleted]
711.413.1.6.2 The extraneous-conductive-parts of a vehicle, wagon, caravan or container shall be
bonded to the protective conductor of the installation in more than one place if the type of construction
does not ensure continuity. The nominal cross-sectional area of conductors used for this purpose shall be
not less than 4 mm² copper.
If the vehicle, wagon, caravan or container is made substantially of insulating material, these requirements
do not apply to metal parts which are unlikely to become live in the event of a fault.
711.42 Protection against thermal effects
711.42.01
NOTE Attention is drawn to the increased risk of fire and burns in these locations and the need to comply with the requirements of
IEC 60364-4-42.
711.42.02 Where SELV or PELV is used, the protection of conductors shall be provided by insulation
capable of withstanding a test voltage of 500 V a.c. for 1 min, or by barriers or enclosures affording a
degree of protection of at least IP4X or IPXXD.
- 7 - HD 384.7.711 S1:2003
711.462 (711.5.536.2) Isolation
711.462.5 (711.5.536.2.3) Every separate temporary structure, such as a vehicle, a stand or a unit,
intended to be occupied by one specific user and each distribution circuit supplying outdoor installations
shall be provided with their own readily accessible and properly identifiable means of isolation. The means
of isolation shall be selected and erected in accordance with IEC 60364-5-537, clause 537.2. Switches,
circuit-breakers, residual current devices etc. considered suitable for isolation by the relevant IEC
standards may be used.
711.47 Application of protective measures for safety
711.471 Measures of protection against electric shock
711.471.1 (711.4.410.3.2.1) Protection against electric shock in normal service
Protective measures against direct contact by means of obstacles (see IEC 60364-4-41, clause 412.3)
and by placing out of reach (see IEC 60364-4-41, clause 412.4) shall not be used.
711.471.2 (711.4.410.3.3) Protection against electric shock in case of a fault
Protective measures against indirect contact by non-conducting location (see IEC 60364-4-41,
clause 413.3) and by earth-free equipotential bonding (see IEC 60364-4-41, clause 413.4) shall not be
used.
711.48 Choice of protective measures as a function of external influences
711.481.3.1.3 (711.4.410.3.4.3)
Cables intended to supply temporary structures should be protected at
their origin by residual current devices whose rated residual operating current does not exceed 300 mA.
These devices shall provide a delay by using a device in accordance with IEC 60947-2, or be of the
S-type in accordance with IEC 61008-1 or IEC 61009-1 for discrimination with RCDs protecting final
circuits.
NOTE The recommendation for additional protection relates to the increased risk damage to cables in temporary locations.
711.481.3.1.4 (711.4.410.3.4.3) All circuits for socket-outlets rated up to 32 A and all final circuits other
than for emergency lighting shall be protected by an RCD with a rated residual operating current not
exceeding 30 mA.
711.482 (711.4.422) Protection against fire
711.482.2.8 (711.4.422.3.8) A motor which is automatically or remotely controlled and which is not
continually supervised shall be fitted with a manual reset protective device against excess temperature.
711.482.3.2 (711.4.422.4.2) Heat generation
Lighting equipment such as incandescent lamps, spotlights and small projectors, and other equipment or
appliances with high temperature surfaces shall be suitably guarded, and installed and located in
accordance with the relevant standard. All such equipment shall be arranged well away from combustible
material to prevent contact.
Showcases and signs shall be constructed of material having an adequate heat resistance, mechanical
strength, electrical insulation and ventilation, taking into account the combustibility of exhibits in relation to
the heat generation.
Stand installations containing a concentration of electrical apparatus, lighting fittings or lamps liable to
generate excessive heat shall not be installed unless adequate ventilation provisions are made, e.g. well-
ventilated ceiling constructed of incombustible material.
In all cases, the manufacturers’ instructions shall be followed.
711.5 Selection and erection of electrical equipment
711.51 Common rules
Control and protective switchgear shall be placed in closed cabinets which can only be opened by the use
of a key or a tool, except for those parts designed and intended to be operated by ordinary persons (BA1)
as defined in IEC 60364-3, clause 322.1.
[clause 711.514 deleted]
711.52 Wiring systems
Armoured cables or cables protected against mechanical damage shall be used wherever there is a risk of
mechanical damage.
Wiring cables shall be copper and have a minimum cross-sectional area of 1.5 mm², and they shall
comply with IEC 60227 or IEC 60245 as appropriate.
Flexible cords shall not be laid in areas accessible to the public unless they are protected against
mechanical damages.
711.521 Types of wiring systems
Where no fire alarm system is installed in a building used for exhibitions etc. cable systems shall be either
- flame retardant to IEC 60332-1 or IEC 60332-3, and low smoke to IEC 61034
or
-
single or multicore unarmoured cables enclosed in metallic or non-metallic conduit or trunking,
providing fire protection
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.