Low-voltage switchgear and controlgear - Part 5-5: Control circuit devices and switching elements - Electrical emergency stop device with mechanical latching function

Is applicable to electrical control circuit devices and switching elements which are used to provide an emergency stop signal. Such devices may be either provided with their own enclosure, or installed according to the manufacturer's instructions. This consolidated version consists of the first edition (1997) and its amendment 1 (2005). Therefore, no need to order amendment in addition to this publication.

Appareillage à basse tension - Partie 5-5: Appareils et éléments de commutation pour circuits de commande - Appareil d'arrêt d'urgence électrique à accrochage mécanique

Est applicable aux appareils pour circuit de commande électrique et aux éléments de commutation qui sont utilisés afin de fournir un signal d'arrêt d'urgence. De tels appareils peuvent être soit des appareils équipés de leur propre enveloppe, soit des appareils montés selon les instructions du constructeur.  Cette version consolidée comprend la première édition (1997) et son amendement 1 (2005). Il n'est donc pas nécessaire de commander l'amendement avec cette publication.

General Information

Status
Published
Publication Date
05-Apr-2005
Current Stage
PPUB - Publication issued
Start Date
06-Apr-2005
Completion Date
06-Apr-2005

Overview

IEC 60947-5-5:1997+AMD1:2005 is an international standard developed by the International Electrotechnical Commission (IEC), focused on low-voltage switchgear and controlgear, specifically the electrical emergency stop device with mechanical latching function. This standard outlines detailed specifications for the construction, marking, and testing of emergency stop devices designed to provide immediate shutdown signals in hazardous situations. These devices are intended for integration into electrical control circuitry to enhance the safety of machines and industrial systems by enabling rapid interruption of processes to protect personnel, equipment, and operations.

This consolidated version, combining the original 1997 edition and Amendment 1 (2005), ensures users have a comprehensive reference without needing to purchase amendments separately.

Key Topics

  • Scope of Application

    • Applicable to electrical control circuit devices and switching elements used to initiate emergency stop signals.
    • Devices may have their own enclosures or require installation as per manufacturer’s instructions.
    • Excludes non-electrical emergency stop devices (e.g., hydraulic, pneumatic) and those without mechanical latching.
  • Types of Emergency Stop Devices

    • Button type emergency stop devices
    • Trip wire (cable operated) switches
    • Footswitches
  • Core Functional Requirements

    • Devices must incorporate a mechanical latching function: the actuator or mechanism remains engaged until it is manually reset, preventing accidental or premature reactivation.
    • Operation must be simple and enable a single-action, manual initiation of the stop signal.
  • Marking and Identification

    • Clear product marking and instructions for installation, operation, maintenance, and periodic testing.
    • Actuators must be colored red, with a highly visible yellow background when possible, adhering to international color-coding practices for emergency stops.
  • Testing and Performance

    • Requirements for robustness, shock, and vibration resistance.
    • Positive opening action, meaning contacts are physically forced open, reducing the risk of contact weld and ensuring reliable disconnection.
    • Verification procedures for proper latching, resetting, and signaling functions.

Applications

IEC 60947-5-5 is widely applied in a broad range of industrial environments to guarantee functional safety:

  • Machine Tools and Industrial Automation
    • Integration into control panels for CNC machines, conveyors, packaging lines, and robotic systems.
  • Manufacturing and Assembly Lines
    • Emergency stop systems on production machinery, presses, and process equipment.
  • Electrical Equipment Safety Upgrades
    • Retrofitting older machinery to meet updated safety regulations and best practices.
  • Compliance for OEMs and System Integrators
    • Essential for meeting basic safety requirements in new machinery as per machinery directives and workplace safety standards.
  • On-site and Remote Control Panels
    • Used in areas where operators might need to halt operations quickly and safely from different locations.

By following IEC 60947-5-5, manufacturers and facility operators can ensure that emergency stop devices offer consistent levels of safety, reliability, and usability, reducing risks of injury and damage.

Related Standards

The scope and requirements of IEC 60947-5-5 are closely tied to several other key international standards:

  • IEC 60947-1: General rules for low-voltage switchgear and controlgear
  • IEC 60947-5-1: Electromechanical control circuit devices
  • IEC 60204-1: Safety of machinery - Electrical equipment of machines
  • ISO 13850: Safety of machinery - Emergency stop function - Principles for design
  • IEC 60073: Coding principles for indicators and actuators
  • IEC 61310-1: Safety of machinery - Indication, marking and actuation

These complementary standards help achieve functional safety and ensure interoperability and uniformity across electrical equipment and safety systems on a global scale.


Keywords: IEC 60947-5-5, electrical emergency stop device, mechanical latching, low-voltage switchgear, industrial safety, control circuit devices, emergency stop standards, machine safety, IEC standards, emergency stop switch

Buy Documents

Standard

IEC 60947-5-5:1997+AMD1:2005 CSV - Low-voltage switchgear and controlgear - Part 5-5: Control circuit devices and switching elements - Electrical emergency stop device with mechanical latching function

English and French language (35 pages)
sale 15% off
Preview
sale 15% off
Preview

Get Certified

Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

SLG Prüf- und Zertifizierungs GmbH

German testing and certification body.

DAKKS Germany Verified

UL Solutions

Global safety science company with testing, inspection and certification.

ANAB United States Verified

Sponsored listings

Frequently Asked Questions

IEC 60947-5-5:1997+AMD1:2005 CSV is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Low-voltage switchgear and controlgear - Part 5-5: Control circuit devices and switching elements - Electrical emergency stop device with mechanical latching function". This standard covers: Is applicable to electrical control circuit devices and switching elements which are used to provide an emergency stop signal. Such devices may be either provided with their own enclosure, or installed according to the manufacturer's instructions. This consolidated version consists of the first edition (1997) and its amendment 1 (2005). Therefore, no need to order amendment in addition to this publication.

Is applicable to electrical control circuit devices and switching elements which are used to provide an emergency stop signal. Such devices may be either provided with their own enclosure, or installed according to the manufacturer's instructions. This consolidated version consists of the first edition (1997) and its amendment 1 (2005). Therefore, no need to order amendment in addition to this publication.

IEC 60947-5-5:1997+AMD1:2005 CSV is classified under the following ICS (International Classification for Standards) categories: 29.120.99 - Other electrical accessories; 29.130.20 - Low voltage switchgear and controlgear. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 60947-5-5:1997+AMD1:2005 CSV is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


NORME CEI
INTERNATIONALE IEC
60947-5-5
INTERNATIONAL
Edition 1.1
STANDARD
2005-04
Edition 1:1997 consolidée par l'amendement 1:2005
Edition 1:1997 consolidated with amendment 1:2005
Appareillage à basse tension –
Partie 5-5:
Appareils et éléments de commutation
pour circuits de commande –
Appareil d'arrêt d'urgence électrique
à accrochage mécanique
Low-voltage switchgear and controlgear –
Part 5-5:
Control circuit devices and switching elements –
Electrical emergency stop device with mechanical
latching function
Numéro de référence
Reference number
CEI/IEC 60947-5-5:1997+A1:2005

Numérotation des publications Publication numbering
Depuis le 1er janvier 1997, les publications de la CEI As from 1 January 1997 all IEC publications are
sont numérotées à partir de 60000. Ainsi, la CEI 34-1 issued with a designation in the 60000 series. For
devient la CEI 60034-1. example, IEC 34-1 is now referred to as IEC 60034-1.
Editions consolidées Consolidated editions
Les versions consolidées de certaines publications de la The IEC is now publishing consolidated versions of its
CEI incorporant les amendements sont disponibles. Par publications. For example, edition numbers 1.0, 1.1
exemple, les numéros d’édition 1.0, 1.1 et 1.2 indiquent and 1.2 refer, respectively, to the base publication,
respectivement la publication de base, la publication de the base publication incorporating amendment 1 and
base incorporant l’amendement 1, et la publication de the base publication incorporating amendments 1
base incorporant les amendements 1 et 2. and 2.
Informations supplémentaires Further information on IEC publications
sur les publications de la CEI
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept
constamment revu par la CEI afin qu'il reflète l'état under constant review by the IEC, thus ensuring that
actuel de la technique. Des renseignements relatifs à the content reflects current technology. Information
cette publication, y compris sa validité, sont dispo- relating to this publication, including its validity, is
nibles dans le Catalogue des publications de la CEI available in the IEC Catalogue of publications
(voir ci-dessous) en plus des nouvelles éditions, (see below) in addition to new editions, amendments
amendements et corrigenda. Des informations sur les and corrigenda. Information on the subjects under
sujets à l’étude et l’avancement des travaux entrepris consideration and work in progress undertaken by the
par le comité d’études qui a élaboré cette publication, technical committee which has prepared this
ainsi que la liste des publications parues, sont publication, as well as the list of publications issued,
également disponibles par l’intermédiaire de: is also available from the following:
• Site web de la CEI (www.iec.ch) • IEC Web Site (www.iec.ch)
• Catalogue des publications de la CEI • Catalogue of IEC publications
Le catalogue en ligne sur le site web de la CEI The on-line catalogue on the IEC web site
(www.iec.ch/searchpub) vous permet de faire des (www.iec.ch/searchpub) enables you to search by a
recherches en utilisant de nombreux critères, variety of criteria including text searches,
comprenant des recherches textuelles, par comité technical committees and date of publication. On-
d’études ou date de publication. Des informations en line information is also available on recently
ligne sont également disponibles sur les nouvelles issued publications, withdrawn and replaced
publications, les publications remplacées ou retirées, publications, as well as corrigenda.
ainsi que sur les corrigenda.
• IEC Just Published • IEC Just Published
Ce résumé des dernières publications parues This summary of recently issued publications
(www.iec.ch/online_news/justpub) est aussi dispo- (www.iec.ch/online_news/justpub) is also available
nible par courrier électronique. Veuillez prendre by email. Please contact the Customer Service
contact avec le Service client (voir ci-dessous) Centre (see below) for further information.
pour plus d’informations.
• Service clients • Customer Service Centre
Si vous avez des questions au sujet de cette If you have any questions regarding this
publication ou avez besoin de renseignements publication or need further assistance, please
supplémentaires, prenez contact avec le Service contact the Customer Service Centre:
clients:
Email: custserv@iec.ch Email: custserv@iec.ch
Tél: +41 22 919 02 11 Tel: +41 22 919 02 11
Fax: +41 22 919 03 00 Fax: +41 22 919 03 00
.
NORME CEI
INTERNATIONALE IEC
60947-5-5
INTERNATIONAL
Edition 1.1
STANDARD
2005-04
Edition 1:1997 consolidée par l'amendement 1:2005
Edition 1:1997 consolidated with amendment 1:2005
Appareillage à basse tension –
Partie 5-5:
Appareils et éléments de commutation
pour circuits de commande –
Appareil d'arrêt d'urgence électrique
à accrochage mécanique
Low-voltage switchgear and controlgear –
Part 5-5:
Control circuit devices and switching elements –
Electrical emergency stop device with mechanical
latching function
 IEC 2005 Droits de reproduction réservés  Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in any
utilisée sous quelque forme que ce soit et par aucun procédé, form or by any means, electronic or mechanical, including
électronique ou mécanique, y compris la photocopie et les photocopying and microfilm, without permission in writing from
microfilms, sans l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
CODE PRIX
CF
Commission Electrotechnique Internationale
PRICE CODE
International Electrotechnical Commission
Международная Электротехническая Комиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue

– 2 – 60947-5-5 © CEI:1997+A1:2005
SOMMAIRE
AVANT-PROPOS.4
INTRODUCTION .8

1 Domaine d'application .10
2 Références normatives.10
3 Définitions.12
4 Marquage et information sur le produit.16
4.1 Généralités .16
4.2 Indications sur les boutons .16
4.3 Prescriptions supplémentaires pour les interrupteurs à commande par câble.18
4.4 Prescriptions supplémentaires pour le code des couleurs.18
5 Prescriptions électriques .18
6 Prescriptions mécaniques.18
6.1 Prescriptions générales .18
6.2 Verrouillage.20
6.3 Prescriptions supplémentaires pour appareil d'arrêt d'urgence à bouton.20
6.4 Prescriptions supplémentaires pour les interrupteurs à commande par câble.20
6.5 Prescriptions supplémentaires pour les interrupteurs à pied.22
7 Essai de la conception mécanique .22
7.1 Généralités .22
7.2 Examen général de la conception .24
7.3 Essais de fonctionnement.24
7.4 Procédures de conditionnement.26
7.5 Essais de chocs .26
7.6 Essais de vibrations .26
7.7 Essais de verrouillage, de réarmement et de choc .28
7.8 Essais divers.32

Annexe A (Suppriméé).34

Figure 1 – Marteau pour les essais .30

Tableau 1 – Robustesse d’un organe de commande à bouton .24
Tableau 2 – Relation entre le trou de montage de l’arrêt d’urgence
et la hauteur du marteau.30

60947-5-5 © IEC:1997+A1:2005 – 3 –
CONTENTS
FOREWORD .5
INTRODUCTION .9

1 Scope .11
2 Normative references .11
3 Definitions.13
4 Marking and product information.17
4.1 General .17
4.2 Indications on buttons .17
4.3 Additional requirements for trip wire switches .19
4.4 Additional requirements for colour coding .19
5 Electrical requirements .19
6 Mechanical requirements.19
6.1 General requirements .19
6.2 Latching .21
6.3 Additional requirements for button type emergency stop device.21
6.4 Additional requirements for trip wire switches .21
6.5 Additional requirement for footswitches.23
7 Testing of the mechanical design.23
7.1 General .23
7.2 General design inspection .25
7.3 Operating tests.25
7.4 Conditioning procedures.27
7.5 Shock test .27
7.6 Vibration tests .27
7.7 Latching, resetting and impact tests.29
7.8 Miscellaneous tests .33

Annex A (Deleted) .35

Figure 1 – Hammer for tests .31

Table 1 – Robustness of a button type actuator.25
Table 2 – Relationship between the emergency stop mounting hole
and the hammer height .31

– 4 – 60947-5-5 © CEI:1997+A1:2005
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
APPAREILLAGE A BASSE TENSION –

Partie 5-5: Appareils et éléments de commutation
pour circuits de commande –
Appareil d'arrêt d'urgence électrique à accrochage mécanique

AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes internationales,
des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au public (PAS) et des
Guides (ci-après dénommés "Publication(s) de la CEI"). Leur élaboration est confiée à des comités d'études,
aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les organisations
internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent également aux
travaux. La CEI collabore étroitement avec l'Organisation Internationale de Normalisation (ISO), selon des
conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
s'assure de l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable de
l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications
nationales et régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI n’a prévu aucune procédure de marquage valant indication d’approbation et n'engage pas sa
responsabilité pour les équipements déclarés conformes à une de ses Publications.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de la CEI, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais
de justice) et les dépenses découlant de la publication ou de l'utilisation de cette Publication de la CEI ou de
toute autre Publication de la CEI, ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de la CEI peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 60947-5-5 a été établie par le sous-comité 17B: Appareillage à
basse tension, du comité d'études 17 de la CEI: Appareillage.
La présente version consolidée de la CEI 60947-5-5 comprend la première édition (1997)
[documents 17B/837/FDIS et 17B/856/RVD] et son amendement 1 (2005) [documents
17B/1389/FDIS et 17B/1399/RVD].
Le contenu technique de cette version consolidée est donc identique à celui de l'édition de
base et à son amendement; cette version a été préparée par commodité pour l'utilisateur.
Elle porte le numéro d'édition 1.1.
Une ligne verticale dans la marge indique où la publication de base a été modifiée par
l'amendement 1.
60947-5-5 © IEC:1997+A1:2005 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR –

Part 5-5: Control circuit devices and switching elements –
Electrical emergency stop device with mechanical latching function

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60947-5-5 has been prepared by subcommittee 17B: Low-voltage
switchgear and controlgear, of IEC technical committee 17: Switchgear and controlgear.
This consolidated version of IEC 60947-5-5 consists of the first edition (1997) [documents
17B/837/FDIS and 17B/856/RVD] and its amendment 1 (2005) [documents 17B/1389/FDIS and
17B/1399/RVD].
The technical content is therefore identical to the base edition and its amendment and has
been prepared for user convenience.
It bears the edition number 1.1.
A vertical line in the margin shows where the base publication has been modified by
amendment 1.
– 6 – 60947-5-5 © CEI:1997+A1:2005
La présente norme doit être utilisée conjointement avec la CEI 60947-1 et la CEI 60947-5-1.
Le comité a décidé que le contenu de la publication de base et de ses amendements ne sera
pas modifié avant la date de maintenance indiquée sur le site web de la CEI sous
"http://webstore.iec.ch" dans les données relatives à la publication recherchée. A cette date,
la publication sera
• reconduite,
• supprimée,
• remplacée par une édition révisée, ou
• amendée.
Le contenu du corrigendum de juillet 2007 a été pris en considération dans cet exemplaire.

60947-5-5 © IEC:1997+A1:2005 – 7 –
This standard should be used in conjunction with IEC 60947-1 and IEC 60947-5-1.
The committee has decided that the contents of the base publication and its amendments will
remain unchanged until the maintenance result date indicated on the IEC web site under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
– 8 – 60947-5-5 © CEI:1997+A1:2005
INTRODUCTION
La présente CEI 60947-5-5 traite spécifiquement des appareils d'arrêt d'urgence électriques
avec fonction mécanique de verrouillage et donne des prescriptions électriques et
mécaniques complémentaires à celles données dans les normes internationales suivantes:
– l’ISO 13850 donnant des prescriptions pour la fonction d'arrêt d'urgence d'une machine
quelle que soit l'énergie utilisée;
– la CEI 60204-1 donnant des prescriptions supplémentaires pour une fonction d'arrêt
d'urgence réalisé par l'équipement électrique d'une machine;
– la CEI 60947-5-1 spécifiant les caractéristiques électriques des appareils électro-
mécaniques pour circuits de commande.

60947-5-5 © IEC:1997+A1:2005 – 9 –
INTRODUCTION
The present IEC 60947-5-5 deals specifically with electrical emergency stop devices with
mechanical latching function and gives additional electrical and mechanical requirements to
those given in the following International Standards:
– ISO 13850 giving requirements for the emergency stop function of a machine, whatever
be the energy used;
– IEC 60204-1 giving additional requirements for an emergency stop function realized by
the electrical equipment of a machine;
– IEC 60947-5-1 specifying electrical characteristics of electromechanical control circuit
devices.
– 10 – 60947-5-5 © CEI:1997+A1:2005
APPAREILLAGE A BASSE TENSION –

Partie 5-5: Appareils et éléments de commutation
pour circuits de commande –
Appareil d'arrêt d'urgence électrique à accrochage mécanique

1 Domaine d'application
La présente section de la CEI 60947-5 donne des spécifications détaillées concernant la
construction électrique et mécanique des appareils d'arrêt d'urgence à accrochage
mécanique et leurs essais.
La présente norme est applicable aux appareils pour circuit de commande électrique et aux
éléments de commutation qui sont utilisés afin de provoquer un signal d'arrêt d'urgence.
De tels appareils peuvent être soit des appareils équipés de leur propre enveloppe, soit des
appareils montés selon les instructions du constructeur.
Cette norme ne s'applique pas aux:
– appareils d'arrêt d'urgence pour circuit de commande non électrique par exemple
hydraulique, pneumatique;
– appareils d'arrêt d'urgence sans accrochage mécanique.
Un appareil d'arrêt d'urgence peut également être utilisé pour fournir une fonction de coupure
d'urgence (voir annexe A).
2 Références normatives
Les documents de référence suivants sont indispensables pour l'application du présent
document. Pour les références datées, seule l'édition citée s'applique. Pour les références
non datées, la dernière édition du document de référence s'applique (y compris les éventuels
amendements).
CEI 60050(441):1984, Vocabulaire Electrotechnique International (VEI) – Chapitre 441:
Appareillage et fusibles
Amendement 1 (2000)
CEI 60068-2-1:1990, Essais d'environnement – Partie 2: Essais – Essais A: Froid
Amendement 1 (1993)
Amendement 2 (1994)
CEI 60068-2-2:1974, Essais d'environnement – Partie 2: Essais – Essai B: Chaleur sèche
Amendement 1 (1993)
Amendement 2 (1994)
CEI 60068-2-6:1995, Essais d'environnement – Partie 2: Essais – Essais Fc: Vibrations
(sinusoïdales)
CEI 60068-2-11:1981, Essais d'environnement – Partie 2: Essais – Essai Ka: Brouillard salin

60947-5-5 © IEC:1997+A1:2005 – 11 –
LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR –

Part 5-5: Control circuit devices and switching elements –
Electrical emergency stop device with mechanical latching function

1 Scope
This section of IEC 60947-5 provides detailed specifications relating to the electrical and
mechanical construction of emergency stop devices with mechanical latching function and to
their testing.
This standard is applicable to electrical control circuit devices and switching elements which
are used to initiate an emergency stop signal. Such devices may be either provided with their
own enclosure, or installed according to the manufacturer's instructions.
This standard does not apply to:
– emergency stop devices for non-electrical control circuit, for example hydraulic,
pneumatic;
– emergency stop devices without mechanical latching function.
An emergency stop device may also be used to provide an emergency switching off function
(see annex A).
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 60050(441):1984, International Electrotechnical Vocabulary (IEV) – Chapter 441:
Switchgear, controlgear, fuses
Amendment 1 (2000)
IEC 60068-2-1:1990, Environmental testing – Part 2: Tests – Test A: Cold
Amendment 1 (1993)
Amendment 2 (1994)
IEC 60068-2-2:1974, Environmental testing – Part 2: Tests – Test B: Dry heat
Amendment 1 (1993)
Amendment 2 (1994)
IEC 60068-2-6:1995, Environmental testing – Part 2: Tests – Test Fc: Vibration (sinusoidal)
IEC 60068-2-11:1981, Environmental testing – Part 2: Tests – Test Ka: Salt mist

– 12 – 60947-5-5 © CEI:1997+A1:2005
CEI 60068-2-27:1987, Essais d'environnement – Partie 2: Essais – Essai Ea et guide: Chocs
CEI 60068-2-30:1980, Essais d'environnement – Partie 2: Essais – Essai Db et guide: Essai
cyclique de chaleur humide (cycle de 12 + 12 heures)
Amendement 1 (1985)
CEI 60073:2002, Principes fondamentaux et de sécurité pour l’interface homme-machine, le
marquage et l’identification – Principes de codage pour les dispositifs indicateurs et les
organes de commande
CEI 60204-1:1997, Sécurité des machines – Equipement électrique des machines – Partie 1:
Règles générales
Amendement 1 (1999)
CEI 60721-3-3:1994, Classification des conditions d'environnement – Partie 3: Classification
des groupements des agents d'environnement et de leurs sévérités – Utilisation à poste fixe,
protégé contre les intempéries
Amendement 1 (1995)
Amendement 2 (1996)
CEI 60947-1:2004, Appareillage à basse tension – Partie 1: Règles générales
CEI 60947-5-1:2003, Appareillage à basse tension – Partie 5-1: Appareils et éléments de com-
mutation pour circuits de commande – Appareils électromécaniques pour circuits de commande
CEI 61310-1:1995, Sécurité des machines – Indication, marquage et manoeuvre – Partie 1:
Spécifications pour les signaux visuels, audibles et tactiles
ISO 3864:1984, Couleurs et signaux de sécurité
ISO 13850:1996, Sécurité des machines – Arrêt d’urgence – Principes de conception
3 Définitions
Pour les besoins de la présente section de la CEI 60947-5, les définitions de la CEI 60947-1
et de la CEI 60947-5-1 s'appliquent, ainsi que les définitions complémentaires suivantes.
Référence
A
Appareil d’arrêt d’urgence. 3.2
Arrêt d’urgence (fonction ou signal). 3.1

I
Interrupteur à commande par câble. 3.10

M
Manœuvre positive d’ouverture (d’un élément de contact). 3.9

O
Organe de commande (d’un appareil d’arrêt d’urgence) . 3.4

P
Position activée. 3.6
Position de repos. 3.5

60947-5-5 © IEC:1997+A1:2005 – 13 –
IEC 60068-2-27:1987, Environmental testing – Part 2: Tests – Test Ea and guidance: Shock
IEC 60068-2-30:1980, Environmental testing – Part 2: Tests – Test Db and guidance: Damp
heat, cyclic (12+12-hour cycle)
Amendment 1 (1985)
IEC 60073:2002, Basic and safety principles for man-machine interface, marking and
identification – Coding principles for indicators and actuators
IEC 60204-1:1997, Safety of machinery – Electrical equipment of machines – Part 1: General
requirements
Amendment 1 (1999)
IEC 60721-3-3:1994, Classification of environmental conditions – Part 3: Classification of
groups of environmental parameters and their severities – Section 3: Stationary use at
weather protected location
Amendment 1 (1995)
Amendment 2 (1996)
IEC 60947-1:2004, Low-voltage switchgear and controlgear – Part 1: General rules
IEC 60947-5-1:2003, Low-voltage switchgear and controlgear – Part 5-1: Control circuit
devices and switching elements – Electromechanical control circuit devices
IEC 61310-1:1995, Safety of machinery – Indication, marking and actuation – Part 1:
Requirements for visual, auditory and tactile signals
ISO 3864:1984, Safety colours and safety signs
ISO 13850:1996, Safety of machinery – Emergency stop – Principles for design
3 Definitions
For the purpose of this section of IEC 60947-5, the following definitions apply in addition to
those given in IEC 60947-1 and in IEC 60947-5-1.
Reference
A
Actuated position. 3.6
Actuating system (of an emergency stop device) . 3.3
Actuator (of an emergency stop device). 3.4

D
Direct opening action (positive opening action) (of a contact element) . 3.9

E
Emergency stop (function or signal). 3.1
Emergency stop device. 3.2

L
Latching (of an emergency stop device). 3.7

– 14 – 60947-5-5 © CEI:1997+A1:2005
R
Réarmement (d’un appareil d’arrêt d’urgence). 3.8

S
Système de commande (d’un appareil d’arrêt d’urgence). 3.3

V
Verrouillage (d’un appareil d’arrêt d’urgence). 3.7

3.1
arrêt d'urgence (fonction ou signal): Fonction ou signal prévu:
– pour éviter ou réduire des risques (phénomènes dangereux), pouvant porter atteinte à
des personnes, à la machine ou au travail en cours;
– pour être déclenchée par une action humaine unique.
[ISO/CEI 13850: 3.1, modifiée]
3.2
appareil d'arrêt d'urgence
appareil pour circuit de commande manoeuvré manuellement et utilisé pour provoquer un
arrêt d'urgence
[ISO/CEI 13850: 3.2 modifiée]
NOTE Un appareil d'arrêt d'urgence peut également fournir des fonctions auxiliaires, par exemple redondance
et/ou signal par un ou des éléments de contact supplémentaire. Ce ou ces contacts peuvent être normalement
ouverts et/ou normalement fermés.
3.3
système de commande (d'un appareil d'arrêt d'urgence)
pièces mécaniques transmettant la force de commande aux éléments de contact
[VEI 441-15-21 modifiée]
3.4
organe de commande (d'un appareil d'arrêt d'urgence)
partie du système de commande qui est manoeuvrée par une partie du corps humain
[VEI 441-15-22 modifiée]
NOTE 1 L'organe de commande peut être par exemple un bouton, un câble, une corde, une barre ou une pédale.

3.5
position de repos
position d'un appareil d'arrêt d'urgence, ou d'une partie de celui-ci, qui n'a pas été
manoeuvré
NOTE En position repos, la machine (ou le matériel) peut fonctionner.
3.6
position activée
position d'un appareil d'arrêt d'urgence, ou d’une partie de celui-ci, après avoir été
manoeuvré
NOTE Lorsque l’appareil d’arrêt d’urgence est en position activée, la machine (ou le matériel) reste à l'état
repos.
60947-5-5 © IEC:1997+A1:2005 – 15 –
R
Resetting (of an emergency stop device). 3.8
Rest position. 3.5

T
Trip wire switch. 3.10

3.1
emergency stop (function or signal)
function or signal which is intended:
– to avert or to reduce hazards to persons, damage to machinery or to work in progress;
– to be initiated by a single human action.
[ISO/IEC 13850:3.1, modified]
3.2
emergency stop device
a manually operated control circuit device used to initiate an emergency stop function
[ISO/IEC 13850:3.2, modified]
NOTE An emergency stop device may also provide auxiliary functions, for example for redundancy and/or for
signalling through additional contact element(s). Such additional contact(s) may be normally open and/or normally
closed.
3.3
actuating system (of an emergency stop device)
the mechanical parts which transmit the actuating force to the contact elements
[IEV 441-15-21 modified]
3.4
actuator (of an emergency stop device)
the part of the actuating system which is actuated by a part of the human body
[IEV 441-15-22 modified]
NOTE 1 Examples of an actuator may be a button, a wire, a rope, a bar, a foot pedal.

3.5
rest position
the position of an emergency stop device, or of a part of it, which has not been actuated
NOTE In rest position, the machine (or equipment) may work.
3.6
actuated position
the position of an emergency stop device, or of a part of it, after it has been actuated
NOTE In the actuated position of the emergency stop device the machine (or equipment) remains at rest.

– 16 – 60947-5-5 © CEI:1997+A1:2005
3.7
verrouillage (d'un appareil d'arrêt d'urgence)
fonction ou dispositif qui enclenche et maintient le système de commande en position activée
jusqu'au réarmement par une manoeuvre manuelle séparée
3.8
réarmement (d’un appareil d’arrêt d’urgence)
manœuvre manuelle permettant au système de commande de l'appareil d'arrêt d'urgence de
retourner de la position activée à la position de repos
NOTE Le réarmement peut se faire, par exemple, par la rotation d’une clef, ou de l'organe de commande, en
tirant l'organe de commande ou en poussant un bouton spécial de réarmement.
3.9
manoeuvre positive d'ouverture (d'un élément de contact)
accomplissement de la séparation des contacts résultant directement d'un mouvement de
l'organe de commande et effectué au moyen de pièces non élastiques (par exemple sans
l'intermédiaire de ressort)
[K.2.2 de la CEI 60947-5-1].
3.10
interrupteur à commande par câble
interrupteur actionné par câble
appareil d’arrêt d’urgence dans lequel l’organe de commande est une corde, un câble ou un
moyen similaire
4 Marquage et information sur le produit
4.1 Généralités
Les informations nécessaires à l'installation, au fonctionnement, à l'entretien et/ou à la
périodicité des essais doivent être fournies sur ou avec l'appareil d'arrêt d'urgence.
La vérification de l'article 4 doit être faite selon 7.2.1.
NOTE 1 Dans certains cas, il peut être nécessaire de fournir des informations supplémentaires, par exemple:
– avec des étiquettes,
– avec des drapeaux liés aux câbles ou cordes pour améliorer leur visibilité,
– avec le symbole graphique 60417-CEI-5638 (voir Tableau 6 de la CEI 61310-1).
NOTE 2 Voir aussi 9.2.5.4 de la CEI 60204-1.
4.2 Indications sur les boutons
4.2.1 Les boutons utilisés comme organes de commande d'un appareil d'arrêt d'urgence
doivent être de couleur rouge. La surface située derrière l'organe de commande, lorsqu'il en
existe une et pour autant que ce soit praticable, doit être de couleur jaune.
4.2.2 La direction du déverrouillage doit être clairement identifiée lorsque le réarmement est
obtenu par rotation du bouton.
NOTE Voir aussi la CEI 60073 et l'ISO 3864.

60947-5-5 © IEC:1997+A1:2005 – 17 –
3.7
latching (of an emergency stop device)
function or means which engages and maintains the actuating system in the actuated position
until reset by a separate manual action
3.8
resetting (of an emergency stop device)
manual action to return the actuating system of the emergency stop device from the actuated
position to the rest position
NOTE Examples of resetting include the rotation of a key, or of the actuator, pulling the actuator or pushing a
special reset button.
3.9
direct opening action (positive opening action) (of a contact element)
the achievement of contact separation as a direct result of a specified movement of the
switch actuator through non-resilient members (e.g. non dependent upon springs)
[K.2.2 of IEC 60947-5-1]
3.10
trip wire switch
rope pull switch
pull cord operated switch
emergency stop device in which the actuator is a rope, a wire or similar means
4 Marking and product information
4.1 General
Information for installation, operation, maintenance and/or periodic testing shall be provided
when necessary on or with the emergency stop device.
The verification of clause 4 shall be conducted according to 7.2.1.
NOTE 1 In certain circumstances, it may be necessary to provide additional information, for example:
– by labels,
– by marker flags attached to wires or ropes to improve their visibility,
– by the graphical symbol 60417-IEC-5638 (see Table 6 of IEC 61310-1).
NOTE 2 See also 9.2.5.4 of IEC 60204-1.
4.2 Indications on buttons
4.2.1 Buttons used as actuators of an emergency stop device shall be coloured red. When a
background exists behind the actuator, and as far as it is practicable, it shall be coloured
yellow.
4.2.2 The direction of unlatching shall be clearly identified when resetting is achieved by
rotation of the button.
NOTE See also IEC 60073 and ISO 3864.

– 18 – 60947-5-5 © CEI:1997+A1:2005
4.3 Prescriptions supplémentaires pour les interrupteurs à commande par câble
Les informations fournies par le constructeur doivent inclure:
– la longueur maximale du câble ou de la corde;
– la tension correcte du câble ou de la corde;
– les distances entre supports;
– la recommandation d'utiliser seulement des parcours droits de câble ou corde;
– éventuellement un guide sur l'entretien des poulies et des oeillets, et les mesures
nécessaires afin de s'assurer que le câble ou la corde reste en position correcte.
4.4 Prescriptions supplémentaires pour le code des couleurs
Un bouton de réarmement, s'il y en a un, par exemple avec un interrupteur à commande par
câble, doit être coloré en bleu.
Lorsqu'un code de couleur est utilisé pour ajuster un interrupteur à commande par câble:
– le vert doit indiquer l'ajustement correct de la position repos; et
– le jaune doit indiquer l'ajustement correct de la position activée.
5 Prescriptions électriques
5.1 Les catégories d'emploi doivent être AC-15 et/ou DC-13 et/ou DC-14 selon la CEI 60947-5-1.
5.2 Tous les éléments de contact normalement fermés d'un appareil d'arrêt d'urgence
doivent avoir une manoeuvre positive d'ouverture selon l'annexe K de la CEI 60947-5-1.
Les essais doivent être effectués selon l'annexe K de la CEI 60947-5-1.
5.3 Le degré de protection fourni par l'appareil d'arrêt d'urgence doit être déclaré par le
constructeur selon l'annexe C et la CEI 60947-1.
5.4 Les essais pour les caractéristiques électriques doivent être effectués selon la CEI 60947-5-1.
NOTE Le paragraphe 7.2.7 de la CEI 60947-5-1 est applicable seulement aux auxiliaires de commande aptes au
sectionnement.
6 Prescriptions mécaniques
6.1 Prescriptions générales
6.1.1 Des moyens doivent être prévus afin de permettre d'installer l'appareil d'arrêt
d'urgence de façon sûre dans sa position de montage prévue.
L'essai doit être effectué selon 7.2.1.
6.1.2 L'appareil d'arrêt d'urgence doit satisfaire aux prescriptions de 7.3, 7.4, 7.5, 7.6 et,
selon le cas, de 7.7.5.
6.1.3 Il doit être possible de manoeuvrer et de réarmer l'appareil d'arrêt d'urgence dans
toutes les conditions normales de service.
L'essai doit être effectué selon 7.2 à 7.7.4.

60947-5-5 © IEC:1997+A1:2005 – 19 –
4.3 Additional requirements for trip wire switches
Information provided by the manufacturer shall include:
– the maximum length of wire or rope;
– the correct tension of wire or rope;
– the distances between supports;
– recommendation to use only straight runs of wire or rope;
– if applicable, guidance on maintenance for pulleys and eyelets, and the measures
necessary to ensure that the wire or rope remains in proper position.
4.4 Additional requirements for colour coding
A resetting button, for example where applicable with a trip wire
...

Questions, Comments and Discussion