NORME CEI
INTERNATIONALE
IEC
INTERNATIONAL
STANDARD
AMENDEMENT 2
AMENDMENT 2
1998-06
Amendement 2
Horloges de commutation pour tarification
et contrôle de charge
Amendment 2
Time switches for tariff and load control

 IEC 1998 Droits de reproduction réservés  Copyright - all rights reserved
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http: //www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
E
PRICE CODE
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue

– 2 – 61038 amend.2 © CEI:1998

AVANT-PROPOS
Le présent amendement a été établi par le comité d’études 13 de la CEI: Equipements de
mesure de l’énergie électrique et de commande des charges.

Le texte de cet amendement est issu des documents suivants:

FDIS Rapport de vote
13/1154/FDIS 13/1162/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l’approbation de cet amendement.
___________
Modifier le titre de cette norme sur la page de couverture, la page de titre et aux pages 4 et 8
comme suit:
COMPTAGE DE L'ÉLECTRICITÉ –
TARIFICATION ET CONTRÔLE DE CHARGE –
PRESCRIPTIONS PARTICULIÈRES POUR HORLOGES DE TARIFICATION
Page 6
2 Références normatives
Remplacer les normes CEI suivantes:
CEI 68-2-1:1974, par:
CEI 60068-2-1:1990, Essais d’environnement – Deuxième partie: Essais – Essais A: Froid
CEI 467C:1977, par
1)
CEI 60417-2, Symboles graphiques utilisables sur le matériel – Partie 2: Dessins originaux
CEI 695-2-1:1980, par:
CEI 60695-2-1/1:1994, Essais relatifs aux risques du feu – Partie 2: Méthodes d’essai –

Section 1/feuille 1: Essai au fil incandescent sur produits finis et guide
CEI 721-3-3: 1987, par:
CEI 60721-3-3: 1994, Classification des conditions d’environnement – Partie 3: Classification
des groupements des agents d’environnement et de leurs sévéritiés – Section 3: Utilisation à
poste fixe, protégé contre les intempéries
CEI 801-4:1988, par:
CEI 61000-4-4:1995, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
de mesure – Section 4: Essai d’immunité aux transitoires électriques rapides en salves –
Publication fondamentale en CEM
___________
1)
A publier.
61038 Amend. 2 © IEC:1998 – 3 –

FOREWORD
This amendment has been prepared by IEC technical committee 13: Equipment for electrical
energy measurement and load control.

The text of this amendment is based on the following documents:

FDIS Report on voting
13/1154/FDIS 13/1162/RVD
Full information on the voting for the approval of this amendment can be found in the report on
voting indicated in the above table.
___________
Amend the title of this standard on the cover page, the title page, and on pages 5 and 9 as
follows:
ELECTRICITY METERING –
TARIFF AND LOAD CONTROL –
PARTICULAR REQUIREMENTS FOR TIME SWITCHES
Page 7
2 Normative references
Replace the following IEC standards:
IEC 68-2-1:1974, by:
IEC 60068-2-1:1990, Environmental testing – Part 2: Tests – Tests A: Cold
IEC 417C:1977, by:
1)
IEC 60417-2,  Graphical symbols for use on equipment – Part 2: Symbol originals
IEC 695-2-1:1980, by:
IEC 60695-2-1/1:1994, Fire hazard testing – Part 2: Test methods – Section 1/Sheet 1: Glow-
wire end-product test and guidance
IEC 721-3-3:1987, by:
IEC 60721-3-3:1994, Classification of environmental conditions – Part 3: Classification of
groups of environmental parameters and their severities – Section 3: Stationary use at
weatherprotected locations
IEC 801-4:1988, by:
IEC 61000-4-4:1995, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 4: Electrical fast transient/burst immunity test – Basic EMC publication
___________
1)
To be published.
– 4 – 61038 amend.2 © CEI:1998

Page 18
4.2.4 Bornes, plaque(s) à bornes, borne de terre de protection

Remplacer le deuxième alinéa par ce qui suit:

La plaque à bornes doit être construite de telle façon que durant toute déformation survenue

dans les conditions assignées de fonctionnement, l’horloge de commutation satisfasse aux

prescriptions concernant l’isolation, les distances dans l’air et les lignes de fuite mentionnées

dans la présente norme.
Remplacer, à la page 20, au point e), «(voir n° 5019 de la CEI 417C)» par
«(voir 60417-2-IEC-5019).»
Page 28
Ajouter, après 4.4.2, le nouveau paragraphe suivant:
4.4.2.1 Domaine de fréquence d’alimentation
Les horloges de commutation doivent être prévues pour une fréquence d’alimentation assignée
de 50 Hz ou 60 Hz. Les horloges de commutation doivent fonctionner correctement à toutes les
valeurs de fréquence comprises entre 0,98 et 1,02 fois la fréquence d’alimentation assignée.
Page 28
4.4.4 Tension de coupure assignée (U )
c
Remplacer le texte existant par le suivant:
Le ou les interrupteurs doivent être conçus pour des tensions de coupure assignées suivant le
tableau 5 ci-dessous, et doivent fonctionner correctement jusqu’à 1,15 fois ces tensions
assignées.
Tableau 5 – Tensions de coupure assignées
Tensions de coupure assignées
30 V continue 120 V 230 V 400 V
La tension continue assignée de 30 V ne s’applique qu’à des interrupteurs utilisés pour le
contrôle de circuits de faible puissance. Le domaine de fonctionnement d’un tel circuit se situe
entre les tensions continues 12 V et 34,5 V. Ces interrupteurs peuvent être basés sur une
technologie électromécanique ou électronique pour une utilisation en courant continu

seulement.
Page 30
4.4.5 Courant de coupure assigné (I )
c
Remplacer le texte existant par le suivant:
Le ou les interrupteurs ayant un courant de coupure assigné choisi dans le tableau 6
ci-dessous doivent pouvoir établir, supporter en permanence ou couper les courants indiqués
dans ce tableau sous une tension de 1,15 U . Ce tableau concerne les interrupteurs des
c
circuits principaux.
Pour les interrupteurs de commande d’indicateur de maximum, le pouvoir de coupure est limité
à une valeur maximale de 1 A avec un facteur de puissance cos ϕ = 0,5 inductif.

61038 Amend. 2 © IEC:1998 – 5 –

Page 19
4.2.4 Terminals, terminal block(s), protective earth terminal

Replace the second paragraph by the following:

The terminal block shall be so constructed that the time switch during any deformation caused

by rated operating conditions shall comply with the insulation requirements and the clearance

and creepage distances within this standard.

Replace, on page 21, under item e), "(see No. 5019 of IEC 417C)" by

"(see 60417-2-IEC-5019)".
Page 29
Add, after 4.4.2 the following new subclause:
4.4.2.1 Supply frequency range
The time switches shall be designed for a
...