Alarm and electronic security systems - Part 11-2: Electronic access control systems - Application guidelines

IEC 60839-11-2:2014 defines the minimum requirements and guidance for the installation and operation of electronic access control systems (EACS) and/or accessory equipment to meet different levels of protection. This standard includes requirements for planning, installation, commissioning, maintenance and documentation for the application of EACS installed in and around buildings and areas. The equipment functions are defined in IEC 60839-11-1.

Systèmes d'alarme et de sécurité électroniques - Partie 11-2: Systèmes de contrôle d'accès électronique - Lignes directrices d'application

L'IEC 60839-11-2:2014 définit les exigences et les lignes directrices minimales concernant l'installation et le fonctionnement des systèmes de contrôle d'accès électronique (EACS) et/ou des équipements annexes pour satisfaire à différents niveaux de protection. La présente norme inclut des exigences en matière de planification, d'installation, de mise en service, de maintenance et de documentation pour l'application d'EACS installés à l'intérieur et autour des bâtiments et des zones. Les fonctions des équipements sont définies dans l'IEC 60839-11-1.

General Information

Status
Published
Publication Date
23-Jul-2014
Current Stage
PPUB - Publication issued
Start Date
24-Jul-2014
Completion Date
24-Jul-2014
Ref Project

Buy Standard

Standard
IEC 60839-11-2:2014 - Alarm and electronic security systems - Part 11-2: Electronic access control systems - Application guidelines
English and French language
58 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (sample)

IEC 60839-11-2
Edition 1.0 2014-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Alarm and electronic security systems –
Part 11-2: Electronic access control systems – Application guidelines
Systèmes d'alarme et de sécurité électroniques –
Partie 11-2: Systèmes de contrôle d'accès électronique – Lignes directrices
d'application
IEC 60839-11-2:2014-07(en-fr)
---------------------- Page: 1 ----------------------
THIS PUBLICATION IS COPYRIGHT PROTECTED
Copyright © 2014 IEC, Geneva, Switzerland

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form

or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from

either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC

copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or

your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite

ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie

et les microfilms, sans l'accord écrit de l'IEC ou du Comité national de l'IEC du pays du demandeur. Si vous avez des

questions sur le copyright de l'IEC ou si vous désirez obtenir des droits supplémentaires sur cette publication, utilisez

les coordonnées ci-après ou contactez le Comité national de l'IEC de votre pays de résidence.

IEC Central Office Tel.: +41 22 919 02 11
3, rue de Varembé Fax: +41 22 919 03 00
CH-1211 Geneva 20 info@iec.ch
Switzerland www.iec.ch
About the IEC

The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes

International Standards for all electrical, electronic and related technologies.
About IEC publications

The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the

latest edition, a corrigenda or an amendment might have been published.
IEC Catalogue - webstore.iec.ch/catalogue Electropedia - www.electropedia.org

The stand-alone application for consulting the entire The world's leading online dictionary of electronic and

bibliographical information on IEC International Standards, electrical terms containing more than 30 000 terms and

Technical Specifications, Technical Reports and other definitions in English and French, with equivalent terms in 14

documents. Available for PC, Mac OS, Android Tablets and additional languages. Also known as the International

iPad. Electrotechnical Vocabulary (IEV) online.

IEC publications search - www.iec.ch/searchpub IEC Glossary - std.iec.ch/glossary

The advanced search enables to find IEC publications by a More than 55 000 electrotechnical terminology entries in

variety of criteria (reference number, text, technical English and French extracted from the Terms and Definitions

committee,…). It also gives information on projects, replaced clause of IEC publications issued since 2002. Some entries

and withdrawn publications. have been collected from earlier publications of IEC TC 37,

77, 86 and CISPR.
IEC Just Published - webstore.iec.ch/justpublished

Stay up to date on all new IEC publications. Just Published IEC Customer Service Centre - webstore.iec.ch/csc

details all new publications released. Available online and If you wish to give us your feedback on this publication or

also once a month by email. need further assistance, please contact the Customer Service

Centre: csc@iec.ch.
A propos de l'IEC

La Commission Electrotechnique Internationale (IEC) est la première organisation mondiale qui élabore et publie des

Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications IEC

Le contenu technique des publications IEC est constamment revu. Veuillez vous assurer que vous possédez l’édition la

plus récente, un corrigendum ou amendement peut avoir été publié.
Catalogue IEC - webstore.iec.ch/catalogue Electropedia - www.electropedia.org
Application autonome pour consulter tous les renseignements
Le premier dictionnaire en ligne de termes électroniques et
bibliographiques sur les Normes internationales,
électriques. Il contient plus de 30 000 termes et définitions en
Spécifications techniques, Rapports techniques et autres
anglais et en français, ainsi que les termes équivalents dans
documents de l'IEC. Disponible pour PC, Mac OS, tablettes
14 langues additionnelles. Egalement appelé Vocabulaire
Android et iPad.
Electrotechnique International (IEV) en ligne.
Recherche de publications IEC - www.iec.ch/searchpub
Glossaire IEC - std.iec.ch/glossary
Plus de 55 000 entrées terminologiques électrotechniques, en
La recherche avancée permet de trouver des publications IEC

en utilisant différents critères (numéro de référence, texte, anglais et en français, extraites des articles Termes et

comité d’études,…). Elle donne aussi des informations sur les Définitions des publications IEC parues depuis 2002. Plus

projets et les publications remplacées ou retirées. certaines entrées antérieures extraites des publications des

CE 37, 77, 86 et CISPR de l'IEC.
IEC Just Published - webstore.iec.ch/justpublished
Service Clients - webstore.iec.ch/csc
Restez informé sur les nouvelles publications IEC. Just

Published détaille les nouvelles publications parues. Si vous désirez nous donner des commentaires sur cette

Disponible en ligne et aussi une fois par mois par email. publication ou si vous avez des questions contactez-nous:

csc@iec.ch.
---------------------- Page: 2 ----------------------
IEC 60839-11-2
Edition 1.0 2014-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Alarm and electronic security systems –
Part 11-2: Electronic access control systems – Application guidelines
Systèmes d'alarme et de sécurité électroniques –
Partie 11-2: Systèmes de contrôle d'accès électronique – Lignes directrices
d'application
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CODE PRIX U
ICS 13.320 ISBN 978-2-8322-1774-0

Warning! Make sure that you obtained this publication from an authorized distributor.

Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.

® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale
---------------------- Page: 3 ----------------------
– 2 – IEC 60839-11-2:2014 © IEC 2014
CONTENTS

FOREWORD ........................................................................................................................... 4

INTRODUCTION ..................................................................................................................... 6

1 Scope .............................................................................................................................. 7

2 Normative references ...................................................................................................... 7

3 Terms and definitions ...................................................................................................... 7

4 Abbreviations .................................................................................................................. 8

5 System architecture ......................................................................................................... 8

6 Environmental and EMC considerations ........................................................................... 9

6.1 General ................................................................................................................... 9

6.2 Environmental Class I – Equipment situated in indoor but restricted to

residential/office environment ................................................................................. 9

6.3 Environmental Class II – Equipment situated indoor in general .................................. 9

6.4 Environmental Class III – Equipment situated outdoor – Sheltered or indoor

extreme conditions ................................................................................................ 10

6.5 Environmental Class IV – Equipment situated outdoor – General .......................... 10

6.6 EMC ..................................................................................................................... 10

7 System planning ............................................................................................................ 10

7.1 General ................................................................................................................. 10

7.2 Risk assessment and security grading .................................................................. 11

7.3 System design ...................................................................................................... 12

7.3.1 System and components selection ................................................................. 12

7.3.2 Operational considerations ............................................................................ 14

8 System installation ........................................................................................................ 16

8.1 General ................................................................................................................. 16

8.2 Installation planning .............................................................................................. 17

8.2.1 Equipment ..................................................................................................... 17

8.2.2 Cabling .......................................................................................................... 19

9 Commissioning and system handover ............................................................................ 19

9.1 Commissioning ..................................................................................................... 19

9.2 System handover .................................................................................................. 20

10 System operation and maintenance ............................................................................... 20

10.1 System operation .................................................................................................. 20

10.2 System maintenance ............................................................................................. 21

11 Documentation .............................................................................................................. 21

11.1 General ................................................................................................................. 21

11.2 Documentation for planning .................................................................................. 21

11.3 Documentation for commissioning/system handover ............................................. 22

11.4 Documentation for maintenance ............................................................................ 22

Annex A (normative) Allowed exceptions for installed systems ............................................. 23

A.1 General ................................................................................................................. 23

A.2 Claims of compliance ............................................................................................ 23

A.3 Allowed exceptions ............................................................................................... 23

Annex B (informative) Standby battery capacity calculations ................................................ 27

Bibliography .......................................................................................................................... 29

---------------------- Page: 4 ----------------------
IEC 60839-11-2:2014 © IEC 2014 – 3 –

Figure 1 – Typical arrangement of components and interfaces of an EACS ............................. 9

Figure 2 – Risk assessment chart ......................................................................................... 11

Figure 3 – Example of system grade selection ...................................................................... 13

Figure 4 – Equipment location versus security grade of protected area ................................. 17

Table 1 – Security grading .................................................................................................... 12

Table 2 – Power supply requirements for installed EACS ...................................................... 18

Table A.1 – Allowed exceptions for access point interface requirements ............................... 24

Table A.2 – Allowed exceptions for indication and annunciation requirements ....................... 24

Table A.3 – Allowed exceptions for recognition requirements ................................................ 25

Table A.4 – Duress signalling requirements .......................................................................... 25

Table A.5 – Overriding requirements ..................................................................................... 25

Table A.6 – Communication requirements ............................................................................. 25

Table A.7 – Allowed exceptions for system self-protection requirements ............................... 25

Table A.8 – Allowed exceptions for power supply requirements ............................................ 26

---------------------- Page: 5 ----------------------
– 4 – IEC 60839-11-2:2014 © IEC 2014
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
ALARM AND ELECTRONIC SECURITY SYSTEMS –
Part 11-2: Electronic access control systems –
Application guidelines
FOREWORD

1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising

all national electrotechnical committees (IEC National Committees). The object of IEC is to promote

international co-operation on all questions concerning standardization in the electrical and electronic fields. To

this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,

Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC

Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested

in the subject dealt with may participate in this preparatory work. International, governmental and non-

governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely

with the International Organization for Standardization (ISO) in accordance with conditions determined by

agreement between the two organizations.

2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international

consensus of opinion on the relevant subjects since each technical committee has representation from all

interested IEC National Committees.

3) IEC Publications have the form of recommendations for international use and are accepted by IEC National

Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC

Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any

misinterpretation by any end user.

4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications

transparently to the maximum extent possible in their national and regional publications. Any divergence

between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in

the latter.

5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity

assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any

services carried out by independent certification bodies.

6) All users should ensure that they have the latest edition of this publication.

7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and

members of its technical committees and IEC National Committees for any personal injury, property damage or

other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and

expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC

Publications.

8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is

indispensable for the correct application of this publication.

9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of

patent rights. IEC shall not be held responsible for identifying any or all such patent rights.

International Standard IEC 60839-11-2 has been prepared by IEC technical committee 79:

Alarm and electronic security systems.
The text of this standard is based on the following documents:
FDIS Report on voting
79/476/FDIS 79/489/RVD

Full information on the voting for the approval of this standard can be found in the report on

voting indicated in the above table.

This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.

---------------------- Page: 6 ----------------------
IEC 60839-11-2:2014 © IEC 2014 – 5 –

A list of all parts in the IEC 60839 series, published under the general title Alarm and

electronic security systems, can be found on the IEC website.

Future standards in this series will carry the new general title as cited above. Titles of existing

standards in this series will be updated at the time of the next edition.

The committee has decided that the contents of this publication will remain unchanged until

the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data

related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.

IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates

that it contains colours which are considered to be useful for the correct

understanding of its contents. Users should therefore print this document using a

colour printer.
---------------------- Page: 7 ----------------------
– 6 – IEC 60839-11-2:2014 © IEC 2014
INTRODUCTION

This standard is part of the IEC 60839 series, written to include the following parts:

Part 11-1: Electronic access control systems – System and components requirements

Part 11-2: Electronic access control systems – Application guidelines

This part of IEC 60839 describes the general requirements for planning, installation, operation,

maintenance and documentation for the application of electronic access control systems

(EACS).

The performance of the EACS is determined by the security grades allocated to the access

points. A risk assessment that identifies the risks and perceived threats should first be carried

out in order to establish the appropriate security grades.

Four security grades are available based upon the knowledge and tools available to a person

intent upon gaining unauthorised access and the type of application, taking into account

specific organizational aspects and the value of the assets.

Separate guidance is provided for each activity along with recommendations for the

documentation needed. A brief description of each section covering the activities is provided

below:

System planning: this section is intended to assist the designer with the selection of an

electronic access control system (EACS) that provides the control of access and security

integrity commensurate with the value of the assets requiring protection and the associated

risks. See Clause 7.

System design should minimise potential vulnerabilities that could be exploited to circumvent

the access control measures. It is recommended that safeguards are incorporated to give

early warning of attempts to circumvent the access control measures. See 7.3.

System installation: this section is intended to help those responsible for installing the EACS

by identifying issues which should be considered prior to commencing the installation and

during the installation of the system in order to ensure the EACS is correctly implemented as

specified during system planning. See Clause 8.

Commissioning and system handover: this section provides guidance to ensure the level of

performance required in the system planning is obtained and that the end user is provided

with the necessary documentation, records and operating instructions during the handover of

the EACS. See Clause 9.

System operation and maintenance: includes information regarding the responsibilities of the

end user of the EACS to ensure the system is operated correctly and adequately maintained.

It covers inspection, service and the use of remote diagnostics in order that the level of

performance determined during the system planning stages can be maintained. See Clause

10.
---------------------- Page: 8 ----------------------
IEC 60839-11-2:2014 © IEC 2014 – 7 –
ALARM AND ELECTRONIC SECURITY SYSTEMS –
Part 11-2: Electronic access control systems –
Application guidelines
1 Scope

This part of IEC 60839 defines the minimum requirements and guidance for the installation

and operation of electronic access control systems (EACS) and/or accessory equipment to

meet different levels of protection.

This standard includes requirements for planning, installation, commissioning, maintenance

and documentation for the application of EACS installed in and around buildings and areas.

The equipment functions are defined in the IEC 60839-11-1.

When the EACS includes functions relating to hold-up or the detection of intruders, the

requirements in standards relating to intrusion and hold-up are also applicable.

This standard provides application guidelines intended to assist those responsible for

establishing an EACS to ascertain the appropriate design and planning of the EACS, both in

terms of levels of protection and levels of performance necessary to provide the degree of

access control and protection considered appropriate for each installation. This is achieved by

scaling or classifying the features of electronic access control systems related to the security

functionality (e.g. recognition, access point actuation, access point monitoring, duress

signaling and system self-protection) in line with the known or perceived threat conditions.

This standard does not cover the methods and procedures for conducting a risk assessment.

2 Normative references

The following documents, in whole or in part, are normatively referenced in this document and

are indispensable for its application. For dated references, only the edition cited applies. For

undated references, the latest edition of the referenced document (including any
amendments) applies.

IEC 60839-11-1:2013, Alarm and electronic security systems – Part 11-1: Electronic access

control systems – System and components requirements
3 Terms and definitions

For the purposes of this document the terms and definitions given in IEC 60839-11-1, as well

as the following, apply.
3.1
area zone
part of a protected area which has its own set of access levels

Note 1 to entry: It may have a different security grade than other area zones within the same protected area.

3.2
competent organization

organization possessing sufficient resources and staff with adequate expertise and training in

the maintenance of EACS
---------------------- Page: 9 ----------------------
– 8 – IEC 60839-11-2:2014 © IEC 2014
3.3
fail-safe
fail-open
locking device designed to automatically release upon power failure
3.4
fail-secure
fail-locked
locking device designed to remain secure upon power failure
3.5
protected area
controlled area

area defined by a physical boundary, through which passage is controlled by means of one or

more access points/portals

Note 1 to entry: It may contain several separate area zones with the same or different security grades. Refer to

the area zone definition in 3.1.
3.6
system owner

person or group of people that make the decision about what is appropriate for the respective

premises to be used in order to get the desired access control/protection/price/etc.

4 Abbreviations

For the purposes of this document, the abbreviations given in IEC 60839-11-1, as well as the

following apply.
ACU Access control unit
EACS Electronic access control system
EMC Electromagnetic compatibility
REX Request to exit
5 System architecture

An access control system comprises all the constructional and organizational facilities

together with equipment required for controlling access. Refer to Figure 1 for an example of a

typical arrangement of components and interfaces of an EACS.

The physical protection and mechanical strength of actuators, sensors, etc., should be

commensurate for the security grade of each access point. Consideration should be given to

the physical strength of the surrounding building (e.g. walls, door construction, etc).

---------------------- Page: 10 ----------------------
IEC 60839-11-2:2014 © IEC 2014 – 9 –
Other EACS Other systems
User interface
User
(e.g. readers)
Access point(s)
- actuators Access control system
- sensors
ACU
REX
System
Power supply
management
Mains
IEC

IEC 60839-11-1:2013, Table 8, states that: “The access control unit shall be provided with standby power source

capable of operating the unit and its accessories under specified full load condition for the period of time” required

according to the security grade of the EACS. It is recommended that monitored standby power sources be provided

to all actuators and monitoring console(s).
Figure 1 – Typical arrangement of components and interfaces of an EACS
6 Environmental and EMC considerations
6.1 General

Each component of an EACS is expected to operate correctly in its service environment and

that it will continue to do so for a reasonable time. Components shall be suitable for one of

the following environmental classes.
6.2 Environmental Class I – Equipment situated in indoor but restricted to
residential/office environment

Environmental Class I comprises environmental influences normally experienced indoors

when the temperature is well maintained (e.g. in a residential or commercial property).

NOTE Temperatures can be expected to vary between +5 °C and +40 °C.
6.3 Environmental Class II – Equipment situated indoor in general

Environmental Class II comprises environmental influences normally experienced indoors

when the temperature is not well maintained (e.g. in corridors, halls or staircases and where

condensation can occur on windows and in unheated storage areas or warehouses where

heating is intermittent).
NOTE Temperatures can be expected to vary between –10 °C and +55 °C.
---------------------- Page: 11 ----------------------
– 10 – IEC 60839-11-2:2014 © IEC 2014
6.4 Environmental Class III – Equipment situated outdoor – Sheltered or indoor
extreme conditions

Environmental Class III comprises environmental influences normally experienced out of

doors when the EACS components are not fully exposed to the weather or indoors where

environmental conditions are extreme.
NOTE Temperatures can be expected to vary between –25 °C and +55 °C.
6.5 Environmental Class IV – Equipment situated outdoor – General

Environmental Class IV comprises environmental influences normally experienced out of

doors when the EACS components are fully exposed to the weather.

NOTE Temperatures can be expected to vary between –25 °C and +70 °C depending on the region. The

temperature range can be extended to plus and/or minus for different geographical or climatic zones.

6.6 EMC

It is recommended that installation good practice be followed to reduce the unwanted effects

of electrical interference, e.g. interconnection wiring should not be run in the same conduit or

trunking as cables carrying mains supplies, or network and data cables carrying high

frequency signals unless they are physically separated and/or suitably screened so as to

prevent cross interference.

Additional filtering and/or screening of interconnecting cables might be necessary for

applications known to have high levels of conducted or radiated electrical interference, e.g. an

industrial plant operating high power electrical equipment.

The manufacturers’ guidelines for electromagnetic compatibility should be followed.

7 System planning
7.1 General

The objectives of the system planning stage are to determine the extent of EACS, to select

components of the appropriate functionality/performance criteria, security grade and

environmental classification and to prepare a system design proposal.

An access control system comprises all the logical functionality, constructional and

organizational facilities together with the physical equipment required for controlling access.

Particular care should be taken to minimize inconvenience to authorized users.
The implementation of an access control system should be
...

Questions, Comments and Discussion