Amendment 2 - Electronic ripple control receivers for tariff and load control

Amendement 2 - Récepteurs électroniques de télécommande centralisée pour tarification et contrôle de charge

General Information

Status
Replaced
Publication Date
04-Jun-1998
Current Stage
DELPUB - Deleted Publication
Completion Date
15-May-2004
Ref Project

Relations

Buy Standard

Standard
IEC 61037:1990/AMD2:1998 - Amendment 2 - Electronic ripple control receivers for tariff and load control Released:6/5/1998 Isbn:2831844002
English and French language
9 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NORME CEI
INTERNATIONALE
IEC
INTERNATIONAL
STANDARD
AMENDEMENT 2
AMENDMENT 2
1998-06
Amendement 2
Récepteurs électroniques de télécommande
centralisée pour tarification
et contrôle de charge
Amendment 2
Electronic ripple control receivers
for tariff and load control
 IEC 1998 Droits de reproduction réservés  Copyright - all rights reserved
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http: //www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
E
PRICE CODE
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue

– 2 – 61037 amend. 2 © CEI:1998

AVANT-PROPOS
Le présent amendement a été établi par le comité d’études 13 de la CEI: Equipements de

mesure de l’énergie électrique et de commande des charges.

Le texte de cet amendement est issu des documents suivants:

FDIS Rapport de vote
13/1152/FDIS 13/1160/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l’approbation de cet amendement.
___________
Modifier le titre de cette norme sur la page de couverture, la page de titre et aux pages 4 et 8
comme suit:
COMPTAGE DE L'ÉLECTRICITÉ –
TARIFICATION ET CONTRÔLE DE CHARGE –
PRESCRIPTIONS PARTICULIÈRES POUR RÉCEPTEURS ÉLECTRONIQUES
DE TÉLÉCOMMANDE CENTRALISÉE
Page 8
2 Références normatives
Remplacer les normes CEI suivantes:
CEI 68-2-1:1974, par:
CEI 60068-2-1:1990, Essais d’environnement – Deuxième partie: Essais – Essais A: Froid
CEI 417:1973, par:
1)
CEI 60417-2, Symboles graphiques utilisables sur le matériel – Partie 2: Dessins originaux
CEI 695-2-1:1980, par:
CEI 60695-2-1/1:1994, Essais relatifs aux risques du feu – Partie 2: Méthodes d’essai –

Section 1/feuille 1: Essai au fil incandescent sur produits finis et guide
CEI 721-3-3:1987, par:
CEI 60721-3-3:1994, Classification des conditions d’environnement – Partie 3: Classification
des groupements des agents d’environnement et de leurs sévérités – Section 3: Utilisation à
poste fixe, protégé contre les intempéries
CEI 801-4:1988, par:
CEI 61000-4-4:1995, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
de mesure – Section 4: Essai d’immunité aux transitoires électriques rapides en salves –
Publication fondamentale en CEM
___________
1)
A publier.
61037 Amend. 2 © IEC:1998 – 3 –

FOREWORD
This amendment has been prepared by IEC technical committee 13: Equipment for electrical

energy measurement and load control.

The text of this amendment is based on the following documents:

FDIS Report on voting
13/1152/FDIS 13/1160/RVD
Full information on the voting for the approval of this amendment can be found in the report on
voting indicated in the above table.
___________
Amend the title of this standard on the cover page, the title page, and pages 5 and 9 as follows:
ELECTRICITY METERING –
TARIFF AND LOAD CONTROL –
PARTICULAR REQUIREMENTS FOR ELECTRONIC
RIPPLE CONTROL RECEIVERS
Page 9
2 Normative references
Replace the following IEC standards:
IEC 68-2-1:1974, by:
IEC 60068-2-1:1990, Environmental testing – Part 2: Tests – Tests A: Cold
IEC 417:1973, by:
1)
IEC 60417-2,  Graphical symbols for use on equipment – Part 2: Symbol originals
IEC 695-2-1:1980, by:
IEC 60695-2-1/1:1994, Fire hazard testing – Part 2: Test methods – Section 1/Sheet 1: Glow-
wire end-product test and guidance

IEC 721-3-3:1987, by:
IEC 60721-3-3:1994, Classification of environmental conditions – Part 3: Classification of
groups of environmental parameters and their severities – Section 3: Stationary use at
weatherprotected locations
IEC 801-4:1988, by:
IEC 61000-4-4:1995, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 4: Electrical fast transient/burst immunity test – Basic EMC publication
___________
1)
To be published.
– 4 – 61037 amend. 2 © CEI:1998

Page 22
4.2.3 Bornes, plaque(s) à bornes, borne de terre de protection

Remplacer le deuxième alinéa par ce qui suit:

La plaque à bornes doit être construite de telle façon que durant toute déformation survenue

dans les conditions assignées de fonctionnement, le récepteur de télécommande centralisée

satisfasse aux prescriptions concernant l’isolation, les distances dans l’air et les lignes de fuite

mentionnées dans la présente norme.

Remplacer, à la page 24, au point e), «(voir CEI 417C n° 5019)» par «(voir 60417-2-IEC-
5019).»
Page 30
Ajouter, après 4.4.2, le nouveau paragraphe suivant:
4.4.2.1 Domaine de fréquence d’alimentation
Les récepteurs doivent être prévus pour une fréquence d’alimentation assignée de 50 Hz ou
60 Hz. Les récepteurs doivent fonctionner correctement à toutes les valeurs de fréquence
comprises entre 0,98 et 1,02 fois la fréquence d’alimentation assignée.
4.4.4 Tension de coupure assignée (U )
c
Remplacer le texte existant par le suivant:
Le ou les interrupteurs doivent être conçus pour des tensions de coupure assignées suivant le
tableau 4 ci-dessous, et doivent fonctionner correctement jusqu’à 1,15 fois ces tensions
assignées.
Tableau 4 – Tensions de coupure assignées
Tensions de coupure assignées
30 V continue 120 V 230 V 400 V
La tension continue assignée de 30 V ne s’applique qu’à des interrupteurs utilisés pour le
contrôle de circuits de faible puissance. Le domaine de fonctionnement d’un tel circuit se situe

entre les tensions continues 12 V et 34,5 V. Ces interrupteurs peuvent être basés sur une
technologie électromécanique ou électronique pour une utilisation en courant continu
seulement.
4.4.5 Courant de coupure assigné (I )
c
Remplacer le texte existant par le suivant:
Le ou les interrupteurs ayant un courant de coupure assigné choisi dans le tableau 5
ci-dessous doivent pouvoir couper, supporter en permanence ou établir les courants indiqués
dans ce tableau sous une tension de 1,15 U .
c
61037 Amend. 2 © IEC:1998 – 5 –

Page 23
4.2.3 Terminals, terminal block(s), protective earth terminal

Replace the second paragraph by the following:

The terminal block shall be so constructed that the ripple control receiver during any

deformation caused by rated operating conditions shall comply with the insulation requirements

and the clearance and creepage distances within this standard.

Replace, on page 25, under item e), "(see IEC 417C No. 5919)" by "(see 60417-2-IEC-5019)".

Page 31
Add, after 4.4.2 the following new subclause:
4.4.2.1 Supply frequency ran
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.