Abstract

IEC 61915-2:2011 specifies root device profiles as defined by IEC 61915-1 for starters and similar equipment covered by the following product standards:
- electromechanical contactors and motor-starters (IEC 60947-4-1),
- AC semiconductor motor controllers and starters (IEC 60947-4-2),
- AC semiconductor controllers and contactors for non-motor loads (IEC 60947-4-3),
- control and protective switching devices (or equipment) (CPS) (IEC 60947-6-2),
- control units for built-in thermal protection (PTC) for rotating electrical machines (IEC 60947-8). The contents of the corrigendum of July 2012 have been included in this copy.

Status
Published
Publication Date
19-Oct-2011
Current Stage
PPUB - Publication issued - 60 Publication
Start Date
20-Oct-2011
Due Date
30-Nov-2011
Completion Date
30-Nov-2011

Buy Documents

Standard

IEC 61915-2:2011 - Low-voltage switchgear and controlgear - Device profiles for networked industrial devices - Part 2: Root device profiles for starters and similar equipment Released:10/20/2011

ISBN:978-2-88912-763-4
English and French language (72 pages)
sale 15% off
Preview
sale 15% off
Preview

Overview

IEC 61915-2:2011 is an international standard developed by the International Electrotechnical Commission (IEC) that specifies root device profiles for networked industrial devices, focusing on starters and similar equipment in low-voltage switchgear and controlgear systems. Building upon IEC 61915-1, this standard provides a common framework for describing the essential parameters and operational behavior of devices such as electromechanical contactors, motor-starters, semiconductor motor controllers, control and protective switching devices, and control units for built-in thermal protection. By defining standardized device profiles, IEC 61915-2:2011 promotes interoperability, simplified integration, and efficient configuration of industrial equipment within networked automation environments.

Key Topics

  • Root Device Profiles: Defines root device profiles for various types of starters and related equipment, ensuring a unified approach to parameterization and network communication.
  • Profile Types Covered:
    • Electromechanical contactors and motor-starters (IEC 60947-4-1)
    • AC semiconductor motor controllers and starters (IEC 60947-4-2)
    • AC semiconductor controllers and contactors for non-motor loads (IEC 60947-4-3)
    • Control and protective switching devices (CPS) (IEC 60947-6-2)
    • Control units for built-in thermal protection (PTC) for rotating machines (IEC 60947-8)
  • Common Parameters: Specifies both read-only (R) and read/write (RW) parameters to enable effective network operation and monitoring, including states such as ‘Ready’, ‘On’, ‘Fault’, ‘Local Control’, and ‘Auto Mode’.
  • Parameter Groups: Organizes parameters into logical groups such as monitoring information, measurements (like motor current), and command parameters (such as run forward/reverse, switch off, or self-test).
  • State Models: Provides state chart diagrams and transition tables for different device types to standardize operational behavior and diagnostics.

Applications

The practical value of IEC 61915-2:2011 lies in its ability to standardize communication and management of a wide range of low-voltage devices within industrial networks, particularly in automated manufacturing, process control, plant management, and energy distribution sectors. Key benefits and example applications include:

  • Interoperability: Enables devices from different manufacturers to communicate seamlessly within the same automation network, reducing integration complexity.
  • Simplified Maintenance & Configuration: Standardization of device parameters allows maintenance personnel and system integrators to handle configuration, monitoring, and diagnostics without proprietary tools.
  • Efficient Plant Upgrades: Facilitates scalable upgrades or retrofits by ensuring new devices conform to a common set of profiles and parameters.
  • Remote Control & Diagnostics: Supports robust remote operation, fault detection, and system health monitoring, essential for modern Industry 4.0 and IIoT (Industrial Internet of Things) environments.
  • Vendor-independent Expansion: System designers can integrate or substitute devices while maintaining consistent network behavior and minimizing validation efforts.

Related Standards

IEC 61915-2:2011 is closely linked with several other international standards that establish general requirements, safety, and functionality for low-voltage switchgear and controlgear, including:

  • IEC 61915-1: General rules for the development of device profiles, serving as the foundational framework for IEC 61915-2.
  • IEC 60947 Series:
    • IEC 60947-1: General rules for low-voltage switchgear and controlgear.
    • IEC 60947-4-1: Electromechanical contactors and motor-starters.
    • IEC 60947-4-2: AC semiconductor motor controllers and starters.
    • IEC 60947-4-3: AC semiconductor controllers and contactors for non-motor loads.
    • IEC 60947-6-2: Control and protective switching devices (CPS).
    • IEC 60947-8: Control units for built-in thermal protection (PTC) for rotating electrical machines.
  • IEC 60050-441: International Electrotechnical Vocabulary for switchgear and controlgear terms.

IEC 61915-2:2011 is foundational for achieving harmonized, efficient, and scalable operation of networked industrial devices in low-voltage environments, ensuring robust integration and lifecycle management across diverse industrial systems.

Relations

Effective Date
05-Sep-2023

Buy Documents

Standard

IEC 61915-2:2011 - Low-voltage switchgear and controlgear - Device profiles for networked industrial devices - Part 2: Root device profiles for starters and similar equipment Released:10/20/2011

ISBN:978-2-88912-763-4
English and French language (72 pages)
sale 15% off
Preview
sale 15% off
Preview

Get Certified

Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

SLG Prüf- und Zertifizierungs GmbH

German testing and certification body.

DAKKS Germany Verified

UL Solutions

Global safety science company with testing, inspection and certification.

ANAB United States Verified

Sponsored listings

Frequently Asked Questions

IEC 61915-2:2011 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Low-voltage switchgear and controlgear - Device profiles for networked industrial devices - Part 2: Root device profiles for starters and similar equipment". This standard covers: IEC 61915-2:2011 specifies root device profiles as defined by IEC 61915-1 for starters and similar equipment covered by the following product standards: - electromechanical contactors and motor-starters (IEC 60947-4-1), - AC semiconductor motor controllers and starters (IEC 60947-4-2), - AC semiconductor controllers and contactors for non-motor loads (IEC 60947-4-3), - control and protective switching devices (or equipment) (CPS) (IEC 60947-6-2), - control units for built-in thermal protection (PTC) for rotating electrical machines (IEC 60947-8). The contents of the corrigendum of July 2012 have been included in this copy.

IEC 61915-2:2011 specifies root device profiles as defined by IEC 61915-1 for starters and similar equipment covered by the following product standards: - electromechanical contactors and motor-starters (IEC 60947-4-1), - AC semiconductor motor controllers and starters (IEC 60947-4-2), - AC semiconductor controllers and contactors for non-motor loads (IEC 60947-4-3), - control and protective switching devices (or equipment) (CPS) (IEC 60947-6-2), - control units for built-in thermal protection (PTC) for rotating electrical machines (IEC 60947-8). The contents of the corrigendum of July 2012 have been included in this copy.

IEC 61915-2:2011 is classified under the following ICS (International Classification for Standards) categories: 29.130.20 - Low voltage switchgear and controlgear. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 61915-2:2011 has the following relationships with other standards: It is inter standard links to IEC 61915-2:2011/COR1:2012. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

IEC 61915-2:2011 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


IEC 61915-2 ®
Edition 1.0 2011-10
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Low-voltage switchgear and controlgear – Device profiles for networked
industrial devices –
Part 2: Root device profiles for starters and similar equipment

Appareillage à basse tension – Profils d'appareil pour les appareils industriels
mis en réseau –
Partie 2: Profils racines d'appareil pour les démarreurs et les matériels similaires

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by
any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either IEC or
IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.

IEC Central Office
3, rue de Varembé
CH-1211 Geneva 20
Switzerland
Email: inmail@iec.ch
Web: www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
 Catalogue of IEC publications: www.iec.ch/searchpub
The IEC on-line Catalogue enables you to search by a variety of criteria (reference number, text, technical committee,…).
It also gives information on projects, withdrawn and replaced publications.
 IEC Just Published: www.iec.ch/online_news/justpub
Stay up to date on all new IEC publications. Just Published details twice a month all new publications released. Available
on-line and also by email.
 Electropedia: www.electropedia.org
The world's leading online dictionary of electronic and electrical terms containing more than 20 000 terms and definitions
in English and French, with equivalent terms in additional languages. Also known as the International Electrotechnical
Vocabulary online.
 Customer Service Centre: www.iec.ch/webstore/custserv
If you wish to give us your feedback on this publication or need further assistance, please visit the Customer Service
Centre FAQ or contact us:
Email: csc@iec.ch
Tel.: +41 22 919 02 11
Fax: +41 22 919 03 00
A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.
 Catalogue des publications de la CEI: www.iec.ch/searchpub/cur_fut-f.htm
Le Catalogue en-ligne de la CEI vous permet d’effectuer des recherches en utilisant différents critères (numéro de référence,
texte, comité d’études,…). Il donne aussi des informations sur les projets et les publications retirées ou remplacées.
 Just Published CEI: www.iec.ch/online_news/justpub
Restez informé sur les nouvelles publications de la CEI. Just Published détaille deux fois par mois les nouvelles
publications parues. Disponible en-ligne et aussi par email.
 Electropedia: www.electropedia.org
Le premier dictionnaire en ligne au monde de termes électroniques et électriques. Il contient plus de 20 000 termes et
définitions en anglais et en français, ainsi que les termes équivalents dans les langues additionnelles. Egalement appelé
Vocabulaire Electrotechnique International en ligne.
 Service Clients: www.iec.ch/webstore/custserv/custserv_entry-f.htm
Si vous désirez nous donner des commentaires sur cette publication ou si vous avez des questions, visitez le FAQ du
Service clients ou contactez-nous:
Email: csc@iec.ch
Tél.: +41 22 919 02 11
Fax: +41 22 919 03 00
IEC 61915-2 ®
Edition 1.0 2011-10
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Low-voltage switchgear and controlgear – Device profiles for networked
industrial devices –
Part 2: Root device profiles for starters and similar equipment

Appareillage à basse tension – Profils d'appareil pour les appareils industriels
mis en réseau –
Partie 2: Profils racines d'appareil pour les démarreurs et les matériels similaires

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CODE PRIX W
ICS 29.130.20 ISBN 978-2-88912-763-4

– 2 – 61915-2 © IEC:2011
CONTENTS
FOREWORD . 3
INTRODUCTION . 5
1 Scope . 6
2 Normative references . 6
3 Terms, definitions and abbreviated terms . 6
3.1 General . 6
3.2 Terms and definitions . 6
3.3 Abbreviated terms . 9
4 Root device profiles . 9
5 Common elements of the root device profile . 11
5.1 R parameters . 11
5.2 RW parameters . 17
5.3 Parameter groups . 20
5.4 State model . 22
5.4.1 Motor starter . 22
5.4.2 Soft starter . 24
5.4.3 Motor management starter . 24
6 Root device profiles . 27
6.1 Assemblies supported . 27
6.2 Motor starter . 28
6.3 Soft starter . 31
6.4 Motor management starter . 33
7 Tests . 35
Bibliography . 36

Figure 1 – State chart diagram of motor starter . 22
Figure 2 – State chart diagram of motor management starter . 24

Table 1 – List of root device profiles . 9
Table 2 – R parameters . 11
Table 3 – RW parameters . 17
Table 4 – Parameters groups . 20
Table 5 – State transition table of motor starter . 23
Table 6 – State transition table of motor management starter . 25
Table 7 – P(IEC 61915-2)00001 . 28
Table 8 – P(IEC 61915-2)00002 . 31
Table 9 – P(IEC 61915-2)00003 . 33

61915-2 © IEC:2011 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR –
DEVICE PROFILES FOR NETWORKED INDUSTRIAL DEVICES –

Part 2: Root device profiles for starters and similar equipment

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61915-2 has been prepared by the subcommittee 17B:
Low-voltage switchgear and controlgear, of the IEC technical committee 17: Switchgear and
controlgear.
The text of this standard is based on the following documents:
FDIS Report on voting
17B/1752/FDIS 17B/1755/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.

– 4 – 61915-2 © IEC:2011
A list of all parts of the IEC 61915 series can be found, under the general title Low-voltage
switchgear and controlgear – Device profiles for networked industrial devices, on the IEC
website.
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
The contents of the corrigendum of July 2012 have been included in this copy.

IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
61915-2 © IEC:2011 – 5 –
INTRODUCTION
This International Standard follows the rules and uses the framework of IEC 61915-1,
Low-voltage switchgear and controlgear – Device profiles for networked industrial devices –
Part 1: General rules for the development of device profiles. This International Standard is to
define the common set of functionality (data and behaviour) for motor starters and similar
devices thereby allowing system designers, system integrators and maintenance personnel to
handle profile-based devices without a special tool configuration.
This International Standard gives manufacturers and other organizations the common set of
functionality to represent their network capable devices. Manufacturers or other organizations
may use the root device profiles specified to add their manufacturer-specific extensions.

– 6 – 61915-2 © IEC:2011
LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR –
DEVICE PROFILES FOR NETWORKED INDUSTRIAL DEVICES –

Part 2: Root device profiles for starters and similar equipment

1 Scope
This part of IEC 61915 specifies root device profiles as defined by IEC 61915-1 for starters
and similar equipment covered by the following product standards:
– electromechanical contactors and motor-starters (IEC 60947-4-1),
– AC semiconductor motor controllers and starters (IEC 60947-4-2),
– AC semiconductor controllers and contactors for non-motor loads (IEC 60947-4-3),
– control and protective switching devices (or equipment) (CPS) (IEC 60947-6-2),
– control units for built-in thermal protection (PTC) for rotating electrical machines
(IEC 60947-8).
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including amendments) applies.
IEC 60947-1:2007, Low-voltage switchgear and controlgear – Part 1: General rules
Amendment 1 (2010)
IEC 61915-1:2007, Low-voltage switchgear and controlgear – Device profiles for networked
industrial devices – Part 1: General rules for the development of device profiles
3 Terms, definitions and abbreviated terms
3.1 General
For the purposes of this document, the terms, definitions, abbreviations and symbols given in
IEC 61915-1, as well as the following apply.
3.2 Terms and definitions
3.2.1
built-in thermal protection
protection of certain parts (called protected parts) of a rotating electrical machine against
excessive temperatures resulting from certain conditions of thermal overload, achieved by
means of a thermal protection system, the whole or part of which is a thermally sensitive
device (thermal detector or protector) incorporated within the machine
[IEC 60947-8:2003, 3.1.1, modified]
3.2.2
thermal protection system
system intended to ensure the built-in thermal protection of a rotating electrical machine by
means of a thermal detector (or thermal detectors) together with a control system, or by
means of a thermal protector (or thermal protectors)

61915-2 © IEC:2011 – 7 –
[IEC 60947-8:2003, 3.1.2, modified]
3.2.3
thermal detector
electrical insulated device (component), sensitive to temperature only, which will initiate a
switching function in the control system when its temperature reaches a predetermined level
[IEC 60947-8:2003, 3.1.3]
3.2.4
control system
system to translate a particular point on the characteristic of a thermal detector to a switching
function on the supply to the rotating electrical machine
NOTE The system is capable of being reset (either manually or automatically) when the temperature falls to the
reset value.
[IEC 60947-8:2003, 3.1.5]
3.2.5
control unit
device which converts into a switching function the variation of the characteristic of a thermal
detector
NOTE A control unit may be an electromechanical type, a static type or a combination of both.
[IEC 60947-8:2003, 3.1.15, modified]
3.2.6
manufacturer
any person, company or organisation with ultimate responsibility as follows:
– to verify compliance with the appropriate standard or standards;
– to provide the product information according to Clause 5 of IEC 60947-1:2007
NOTE For instance, in the case of “protected starters” assembled according to the instructions of the component
providers, the manufacturer will be the entity that undertook the assembly.
[IEC 60947-1:2007, 2.1.21, modified]
3.2.7
switching device
device designed to make and/or break the current in one or more electric circuits
[IEC 60050-441:1984, 441-14-01, modified]
3.2.8
semiconductor switching device
switching device designed to make and/or break the current in an electric circuit by means of
the controlled conductivity of a semiconductor
[IEC 60050-441:1984, 441-14-03, modified]
3.2.9
(mechanical) contactor
mechanical switching device having only one position of rest, operated otherwise than by
hand, capable of making, carrying and breaking currents under normal circuit conditions
including operating overload conditions
NOTE Contactors may be designated according to the method by which the force for closing the main contacts is
provided.
– 8 – 61915-2 © IEC:2011
[IEC 60050-441:1984, 441-14-33]
3.2.10
semiconductor contactor
solid-state contactor
device which performs the function of a contactor by utilizing a semiconductor switching
device
NOTE A semiconductor contactor may also contain mechanical switching devices.
[IEC 60947-1:2007, 2.2.13]
3.2.11
starter
combination of all the switching means necessary to start and stop a motor, in combination
with suitable overload protection
NOTE Starters may be designated according to the method by which the force for closing the main contacts is
provided.
[IEC 60050-441:1984, 441-14-38]
3.2.12
short-circuit protective device
SCPD
device intended to protect a circuit or parts of a circuit against short-circuit currents by
interrupting them
[IEC 60947-1:2007, 2.2.21]
3.2.13
tripping (operation)
opening operation of a mechanical switching device initiated by a relay or release
[IEC 60947-1:2007, 2.4.22]
3.2.14
switchgear and controlgear
general term covering switching devices and their combination with associated control,
measuring, protective and regulating equipment, also assemblies of such devices and
equipment with associated interconnections, accessories, enclosures and supporting
structures
[IEC 60050-441:1984, 441-11-01]
3.2.15
motor management starter
starter including extended functions and with communication ability
NOTE Some extended functions are described in IEC 60947-1.
3.2.16
remote control
control of an operation at a point distant from the controlled switching device
[IEC 60050-441:1984, 441-16-07]
NOTE Remote control, in the context of this standard, means control by any communication system using the
profiles defined in this standard.

61915-2 © IEC:2011 – 9 –
3.2.17
local control
control of an operation at a point on or adjacent to the controlled switching device
[IEC 60050-441:1984, 441-16-06]
NOTE Local control, in the context of this standard, means the indication to a remote host controller that, as a
result of operator intervention, commands received will not be accepted or acted upon. Safety control functions
may still be active.
3.2.18
manual control
control of an operation by human intervention
[IEC 60050-441:1984, 441-16-04]
3.2.19
manual mode
switching commands are not accepted from the regular remote controller but from a manual
secondary source for the purpose for example of maintenance, test, commissioning or
configuring
NOTE 1 Manual mode, in the context of this standard, means that the starter does not react upon the switching
commands from the remote host controller like for instance "Run forward", "Run reverse" and "Switch Off".
NOTE 2 The manual secondary source of command is for example a remote engineering tool or a remote
operation terminal.
3.3 Abbreviated terms
O Optional
R Read
RW Read/write
r Reserved
Ready FRC Ready for remote control
4 Root device profiles
Table 1 lists the root device profiles defined in this standard.
Table 1 – List of root device profiles
Standard Root device profile
Identification Name
a
IEC 61915-2 P(IEC 61915-2)00001 Motor starter
P(IEC 61915-2)00002 Soft starter
P(IEC 61915-2)00003 Motor management starter
a
Motor starter may include some kind of soft starters.
Some elements of the root device profile are common to different profiles covered by this
standard:
– parameters,
– parameters groups.
Other elements are specific to the various parts of IEC 60947 series covered by this standard:
– header,
– 10 – 61915-2 © IEC:2011
– parameters assemblies,
– state model.
The remaining elements of the root device profile described in IEC 61915-1 are under
consideration:
– complex data types,
– functional elements,
– services.
61915-2 © IEC:2011                    – 11 –

5 Common elements of the root device profile
5.1 R parameters
The R parameters, specified in Table 2, are defined for the whole series of root device profiles covered by this standard.
Table 2 – R parameters
PARAMETERS
Parameter Data Units Offset Multiplier Range Access Required Parameter description
name type
Ready BOOL na na na na R O 1="READY"
FRC All the conditions that will permit the operation of a device by the remote
host controller have been fulfilled.
0="NOT READY"
The controller is not able to control the device because at least one
condition is not fulfilled.
NOTE 1 The manufacturer/application of the device will determine the
conditions that have to be fulfilled.
EXAMPLE The conditions which have to be fulfilled may include:
- communication to host established,
- remote control selected,
- etc.
NOTE 2 Remote monitoring may be possible even if the device is
"NOT READY". For example the parameter “Motor current” may be
transmitted while the device is being operated under local control.

– 12 –                 61915-2 © IEC:2011

PARAMETERS
Parameter Data Units Offset Multiplier Range Access Required Parameter description
name type
On BOOL na na na na R O 1="ON"
For an electromechanical switching device, the main circuit contacts are
closed.
For a semiconductor switching device, the switches are in the conducting
state.
0="OFF"
For an electromechanical switching device, the main circuit contacts are
open.
For a semiconductor switching device, the switches are in non-conducting
state.
NOTE 1 “ON” doesn’t imply that the motor is running. In simple devices,
such as certain direct-on-line starters, the assumption may be made that
when the starter is "ON", power is available at the incoming connections and
the motor is running. In more complex devices, monitoring of parameters like
"Current" can indicate that the motor is properly running.
NOTE 2 In semiconductor starters, "ON" implies that current is flowing to
the motor.
NOTE 3 ”On” parameter is used for motor starter.

Off BOOL na na na na R O 1="OFF"
For an electromechanical switching device, the main circuit contacts are

open.
For a semiconductor switching device, the switches are in non-conducting
state.
0="ON"
For an electromechanical switching device, the main circuit contacts are
closed. The motor may run forward or run reverse.
For a semiconductor switching device, the switches are in the conducting
state.
NOTE 1 When changing the motion direction of the motor a short
interruption of “ON” may occur.
NOTE 2 ”Off” parameter is used for motor management starter.

61915-2 © IEC:2011                    – 13 –

PARAMETERS
Parameter Data Units Offset Multiplier Range Access Required Parameter description
name type
Running BOOL na na na na R O The main circuit contacts of the electromechanical starter are closed or the
forward semiconductor switches of the semiconductor starter are in the conducting
state.
In unidirectional systems.
1="RUNNING FORWARD", energy is being supplied to the motor.
0=”OFF"
In bi-directional systems, energy is being supplied to the motor so that its
direction of rotation is forward. Running forward and running reverse shall
be considered together:
running forward=0 and running reverse =0  “OFF”
running forward=1 and running reverse =0  “RUNNING FORWARD”
running forward=0 and running reverse =1  “RUNNING REVERSE”
running forward =1 and running reverse =1  Shall be defined by the
manufacturer
Running BOOL na na na na R O The main circuit contacts of the electromechanical starter are closed or the
reverse semiconductor switches of the semiconductor starter are in the conducting
state.
In bi-directional systems, energy is being supplied to the motor so that its
direction of rotation is reverse. Running forward and running reverse shall
be considered together:
See “Running forward”
NOTE In unidirectional systems, this parameter is not used.

Fault BOOL na na na na R O 1="FAULT"
A trip fault condition exists.
0="NO FAULT"
No trip fault condition exists.
NOTE A trip fault condition is any condition (for example short-circuit)
which requires the opening of the main circuit.

– 14 –                 61915-2 © IEC:2011

PARAMETERS
Parameter Data Units Offset Multiplier Range Access Required Parameter description
name type
Warning BOOL na na na na R O 1="WARNING"
A warning condition exists.
0="NO WARNING"
No warning condition exists.
NOTE 1 A warning condition is a condition which is abnormal but which
does not require the immediate opening of the main circuit
(branch/feeder/load/motor) from the supply.
NOTE 2 A warning condition may develop into a fault condition if remedial
action is not taken.
Overload BOOL na na na na R O 1="OVERLOAD WARNING"
warning Any overload parameter is not within the preconfigured limits.
0="NO OVERLOAD WARNING"
NOTE An overload warning condition may develop into a fault condition if
remedial action is not taken.
Local BOOL na na na na R O 1="LOCAL CONTROL ON"
control The indication to a remote host controller that, as a result of operator
intervention, commands received will not be accepted or acted upon.
0="LOCAL CONTROL OFF"
NOTE Safety control functions may still be active.

Auto mode BOOL na na na na R O 1="AUTO MODE ON"
Indication to a remote host controller that the switching commands are
accepted.
0="MANUAL MODE"
NOTE The switching from the automatic mode to the manual mode is set
for example from the manual secondary source of command, the remote
host controller or from another source.

61915-2 © IEC:2011                    – 15 –

PARAMETERS
Parameter Data Units Offset Multiplier Range Access Required Parameter description
name type
Ramping BOOL na na na na R O 1="RAMPING ON"
The condition when a semiconductor controller is accelerating or
decelerating the motor by altering the voltage at the motor terminals to
increase or decrease the motor torque.
0="RAMPING OFF"
NOTE 1 Refers to the “Soft starting” and “Soft stopping” modes of
operation, and not to any voltage variation activity occurring while the motor
is running at full-speed.
NOTE 2 This information may also be used for the starting period of
electromechanical switching devices.

At BOOL na na na na R O 1="REFERENCE REACHED"
reference The condition when a semiconductor controller is neither accelerating or
decelerating the motor by altering the voltage at the motor terminals to
increase or decrease the motor torque.
0="RAMPING"
NOTE Refers to the “Soft starting” and “Soft stopping” modes of operation,
and not to any voltage variation activity occurring while the motor is running
at full-speed such as “Optimising”.

Lock-out BOOL na na na na R O Purposely introduced time delay between different operations, for example
time “Run Forward” and “Run Reverse”.
1="LOCK-OUT TIME ACTIVE"
Monitoring information indicating that the lock-out time is active.
0="LOCK-OUT TIME INACTIVE"
Input N BOOL na na na na R O Monitoring signal of the digital input N (N is the input number which can be
0, 1, 2 .).
0="NO SIGNAL ON INPUT N"
1="SIGNAL ON INPUT N"
– 16 –                 61915-2 © IEC:2011

PARAMETERS
Parameter Data Units Offset Multiplier Range Access Required Parameter description
name type
Motor UDINT A 0 0,1 0 - R O The average instantaneous value of the 3-phase-currents in the motor.
4,29 10
current
NOTE 1 The average value of current can be derived in a variety of ways,
e.g. by a computed true average value or from a line current chosen by an
operator or manufacturer as being representative of the average
instantaneous motor current.
NOTE 2 The maximum possible value of the motor current is
429 496 729,5 A.
BIT
Motor % 0 100/32 0 - 63 R O The motor current expressed as a percentage of the motor rated current, I .
e
STRING
current
NOTE When the value of the parameter is 63, the current value may be
(% I )
e
interpreted as higher than 195 %.

Line BIT % 0 100/32 0 - 63 R O The motor current expressed as a percentage of the motor rated current, I ,
e
STRING
current LN in a specific phase (LN is the number of the phase L1, L2 or L3).
(% I )
e
NOTE When the value of the parameter is 63, the current value may be
interpreted as higher than 195 %.

Motor UINT % 0 1 0 - R O Actual motor current of the largest loaded phase as a percentage [%] of the
current 65 535 set current I .
s
(% I )
s
61915-2 © IEC:2011                    – 17 –

5.2 RW parameters
The RW parameters, specified in Table 3, are defined for the whole series of root device profiles covered by this standard.
Table 3 – RW parameters
PARAMETERS
Parameter Data Units Offset Multiplier Range Access Required Parameter description
name type
Run BOOL na na na na RW O 1="ACTIVATE RUN FORWARD"
forward Instructs the starter to energise the motor in the forward direction.
Energy is being supplied to the motor so that its direction of rotation is
forward.
0="DISACTIVATE RUN FORWARD"
Run BOOL na na na na RW O 1="ACTIVATE RUN REVERSE"
reverse Instructs the starter to energise the motor in the reverse direction.
Energy is being supplied to the motor so that its direction of rotation is
reverse.
0="DISACTIVATE RUN REVERSE"
NOTE 1 In unidirectional systems, this command is not used.
NOTE 2 The manufacturer specifies the behaviour of the device when both
parameters Run forward and Run reverse are activated.

Switch Off BOOL na na na na RW O 1="SWITCH OFF"
Instructs the device to switch off.
The commands "Run forward" and "Run reverse" will not be performed.
0="SWITCH ON POSSIBLE"
The commands "Run forward" or "Run reverse" will be performed.

Brake BOOL na na na na RW O 1="RELEASE"
release Instructs the starter to release the brake on the motor.
0="BRAKE"
– 18 –                 61915-2 © IEC:2011

PARAMETERS
Parameter Data Units Offset Multiplier Range Access Required Parameter description
name type
Reset BOOL na na na na RW O 1="FAULT RESET"
Instructs the starter to reset all resettable trips/faults.
0="FAULT RESET INACTIVE"
NOTE No presence of trip or fault is a condition for "READY".

Emergency
BOOL na na na na RW O 1="EMERGENCY START"
start
Instructs the starter to override any fault condition and allows starting or
ignore any fault condition during running.
0="EMERGENCY START INACTIVE"
NOTE 1 This command is required in process and other industries where
sacrificial demands can be made on motors and associated equipment in
order to achieve an orderly outcome in emergency circumstances.
NOTE 2 The use of this parameter is manufacturer or consortium specific.

Low speed BOOL na na na na RW O 1="RUN LOW SPEED"
Instructs the starter to select low speed running of a two-speed motor.
0="RUN HIGH SPEED"
NOTE The use of this parameter is manufacturer or consortium specific.

Self test BOOL na na na na RW O 1=”ACTIVATE TEST"
Instructs the starter to initiate an internal test routine within the starter.
0=”INACTIVATE TEST"
NOTE 1 “INACTIVATE TEST” includes the possibility that if the test routine
is running it will be finalised.
NOTE 2 The use of this parameter is manufacturer or consortium specific.

61915-2 © IEC:2011                    – 19 –

PARAMETERS
Parameter Data Units Offset Multiplier Range Access Required Parameter description
name type
Auto BOOL na na na na RW O 1="AUTO COMMAND ON"
command Instructs the starter to accept the switching commands "Run forward",
"Run reverse" and "Switch Off" received from the remote host.
0="MANUAL COMMAND ON"
Instructs the starter not to accept the switching commands "Run forward",
"Run reverse" and "Switch Off” received from the remote host.
The starter reports the state in the monitoring information "Auto mode".
NOTE This parameter belongs to the category “Operating mode selection”,
see IEC 61915-1:2007, Annex E.
Output N BOOL na na na na RW O Command signal to Output N of the starter (N is the output number which
can be 0, 1, 2 .).
0="OUTPUT N OFF"
1="OUTPUT N ON"
– 20 –                 61915-2 © IEC:2011

5.3 Parameter groups
As shown in Table 4, three parameter groups are defined:
• monitoring information,
• measurements,
• commands.
Table 4 – Parameters groups
PARAMETER GROUPS
Group name Group type Number of members Required Description Additional information

Monitoring
P 14 O Binary monitoring parameters
information
Member names
Ready FRC
On
Off
Running forward
Running reverse
Fault
Warning
Overload warning
Local control
Auto mode
Ramping
At reference
Lock-out time
Input N
61915-2 © IEC:2011                    – 21 –

Group name Group type Number of members Required Description Additional information

Measurements P 6 O Analogue monitoring parameters
Member names
Motor current
Motor current (%I )
e
Line current L1 (%I )
e
Line current L2 (%I )
e
Line current L3 (%I )
e
Motor current (%I )
s
Group name Group type Number of members Required Description Additional information
Commands P 10 O Commands parameters
Member names
Run forward
Run reverse
Switch Off
Brake release
Reset
Emergency start
Low speed
Self test
Auto command
Output N
– 22 –                 61915-2 © IEC:2011

5.4 State model
5.4.1 Motor starter
Figure 1 and Table 5 describe the state chart diagram of a motor starter.
1:Not_ready
2:Ready_FRC
3:Off
6:Fallback_position
5:Tripped
4:On
IEC  2451/11
Figure 1 – State chart diagram of motor starter

61915-2 © IEC:2011                    – 23 –

Table 5 – State transition table of motor starter
STATE NAME STATE DESCRIPTION
0:Init Pseudo state: self test; initialisation of variables and values; state check; no communication established.
1:Not_ready Not all required conditions for remote operating are fulfilled. Monitoring and configuration may be possible.
The parameter "Ready FRC" is set to 0="NOT READY".
2:Ready_FRC The starter is ready for remote control and for monitoring by the host controller. Monitoring and configuration may be possible.
The parameter "Ready FRC" is set to 1="READY".
3:Off Starter de-energized (e.g. main contacts open). The parameter "On" is set to 0="OFF".
4:On Starter energized (e.g. main contacts are closed). The parameter "On" is set to 1="ON".
5:Tripped Starter de-energized (e.g. main contacts open). The parameter "Fault" is set to 1="FAULT.
NOTE Trip reset required.
6:Fallback_position The starter is in the fallback position which has been preconfigured.
NOTE For example a communication fault has occurred.
99:Exit Pseudo state: the state machine is disbanded.
TRANSITION SOURCE STATE TARGET STATE EVENT (events and conditions that cause the transition to occur)
1 0:Init 1:Not_ready Automatic transition.
2 1:Not_ready 2:Ready_FRC All required conditions for remote operating are fulfilled:
– Communication to host established
– etc.
NOTE How the host communication is established is technology dependent.
3 5:Tripped 3:Off Tripping condition removed and trip reset proceeded.
4 3:Off 5:Tripped Fault condition prevents switching on.
5 4:On 5:Tripped Fault condition occurs.
6 3:Off 4:On Switch on command is received from host.
7 4:On 3:Off Switch off command is received from host.
20 2:Ready_FRC 6:Fallback_position Communication to host lost.
21 6:Fallback_position 1:Not_ready Communication to host is re-established and fallback reset proceeded.
99 From all state 99:Exit Power off or switched to local control or severe device fault occurs.

– 24 –                 61915-2 © IEC:2011

5.4.2 Soft starter
Subclause 5.4.1 is applicable.
5.4.3 Motor management starter
Figure 2 and Table 6 describe the state chart diagram of a motor management starter.
1:Not_ready
2:Ready_FRC
3:Manual
4:Auto
2a 2b
5:Off
7:Tripped
8 9 20
8:Fallback_position
6:On
IEC  2452/11
Figure 2 – State chart diagram of motor management starter

61915-2 © IEC:2011                    – 25 –

Table 6 – State transition table of motor management starter
STATE NAME STATE DESCRIPTION
0:Init Pseudo state: self test; initialisation of variables and values; state check; no communication established.
1:Not_ready Not all required conditions for remote operating are fulfilled. Monitoring and configuration may be possible.
The parameter "Ready FRC" is set to 0="NOT READY".
2:Ready_FRC The starter is ready for remote control and for monitoring by the host controller. Monitoring and configuration may be possible.
The parameter "Ready FRC" is set to 1="READY".
3:Manual The starter is in manual. The parameter "Auto mode" is set to 0="MANUAL MODE".
NOTE Starter is controlled otherwise than by the host controller concerning Run forward, Run reverse and Off.
4:Auto Starter is in auto; the parameter "Auto mode" is set to 1="AUTO MODE ON".
NOTE Starter is controlled by the host controller.
5:Off Starter de-energized (e.g. main contacts open). The parameter "Off" is set to 1="OFF".
6:On Starter energized (e.g. main contacts are closed). The parameter "Off" is set to 0="ON" and the parameter "running forward" is set
to 1="RUNNING FORWARD" or the parameter "running reverse" is set to 1="RUNNING REVERSE".
7:Tripped Starter de-energized (e.g. main contacts open). The parameter "Fault" is set to 1="FAULT.
NOTE Trip reset is required.
8:Fallback_position The starter is in the fallback position which has been preconfigured.
NOTE 1 For example a communication fault has occurred
NOTE 2 Preconfigurations include:
– hold last state,
– turn to predefined state (On, Off, .),
– etc.
99:Exit Pseudo state: the state machine is disbanded.

– 26 –                 61915-2 © IEC:2011

TRANSITION SOURCE STATE TARGET STATE EVENT (events and conditions that cause the transition to occur)
1 0:Init 1:Not_ready Automatic transition.
2 1:Not_ready Decision 2 All required conditions for remote operating are fulfilled:
– communication to host established
– etc.
NOTE How the host communication is established is technology dependent.
2a Decision 2 3:Manual “Auto” command is OFF.
2b Decision 2 4:Auto “Auto” command is ON.
3 3:Manual 4:Auto The “AUTO COMMAND ON” command is received from host or the parameter "Auto mode" is set to
1 = "AUTO MODE ON" by the motor management starter.
4 4:Auto 3:Manual The “MANUAL COMMAND ON” command is received from host or the parameter "Auto mode" is
set to 0 = "MANUAL MODE" by the motor management starter.
5 7:Tripped 5:Off Tripping condition is removed and trip reset proceeded.
6 5:Off 7:Tripped Fault condition prevents switching on.
7 6:On 7:Tripped Tripping condition occurs.
8 5:Off 6:On The "SWITCH ON POSSIBLE" command is received from host.
9 6:On 5:Off The "SWITCH OFF" command is received from host.
20 2:Ready_FRC 9:Fallback_position Communication to host is lost.
21 9:Fallback_position 1:Not_ready Communication to host is re-established and fallback reset proceeded.
99 From
...