Fire safety engineering -- Selection of design occupant behavioural scenarios

ISO/TS 29761:2015 describes a methodology for the selection of design occupant behavioural scenarios that are severe but credible for use in deterministic fire safety engineering analyses of any built environment including buildings, structures, or transportation vehicles. Occupant behavioural scenarios are linked to design fire scenarios. Guidance on the selection of design fire scenarios and design fires is covered in ISO 16733‑1. The steps in ISO 16733‑1 are followed in this Technical Specification with life safety of the occupants as the single fire safety objective under consideration. ISO/TR 16738 provides information on methods for the quantification of the different aspects of human evacuation behaviour in a design context. One part of that process involves the selection of occupant behavioural scenarios. This Technical Specification provides guidance for that aspect of the evaluation of an egress design. ISO/TS 29761:2015 addresses behaviours that occur after fire ignition and does not deal with behaviours that influence fire ignition.

Ingénierie de la sécurité incendie -- Sélection de scénarios de comportements des occupants de dimensionnement

L'ISO/TS 29761:2015 décrit une méthodologie de sélection de scénarios de comportements des occupants de dimensionnement, qui sont sévčres mais plausibles, pour ętre utilisés dans des analyses déterministes d'ingénierie de la sécurité incendie d'un environnement bâti quelconque, dont les bâtiments, les ouvrages ou les véhicules de transport. Les scénarios de comportements des occupants sont liés aux scénarios d'incendie de dimensionnement. Des préconisations concernant la sélection de scénarios d'incendie et de feux de dimensionnement sont fournies dans l'ISO 16733‑1. Les étapes de l'ISO 16733‑1 sont respectées dans l'ISO/TS 29761:2015, avec la sécurité des occupants comme unique objectif de sécurité incendie considéré. L'ISO/TR 16738 fournit des informations sur les méthodes utilisées lors de la conception pour la quantification des différents aspects du comportement humain en cas d'évacuation. Une partie de ce processus comprend la sélection de scénarios de comportements des occupants. L'ISO/TS 29761:2015 contient des préconisations concernant cet aspect de l'évaluation d'une stratégie d'évacuation. L'ISO/TS 29761:2015 traite des comportements qui surviennent aprčs l'allumage d'un feu, mais n'aborde pas les comportements qui influencent cet allumage.

General Information

Status
Published
Publication Date
01-Dec-2015
Current Stage
6060 - International Standard published
Start Date
06-Nov-2015
Completion Date
02-Dec-2015
Ref Project

Buy Standard

Technical specification
ISO/TS 29761:2015 - Fire safety engineering -- Selection of design occupant behavioural scenarios
English language
25 pages
sale 15% off
Preview
sale 15% off
Preview
Technical specification
ISO/TS 29761:2015 - Ingénierie de la sécurité incendie -- Sélection de scénarios de comportements des occupants de dimensionnement
French language
28 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (sample)

TECHNICAL ISO/TS
SPECIFICATION 29761
First edition
2015-12-15
Fire safety engineering — Selection of
design occupant behavioural scenarios
Ingénierie de la sécurité incendie — Sélection de scénarios de
dimensionnement du comportement des occupants
Reference number
ISO/TS 29761:2015(E)
ISO 2015
---------------------- Page: 1 ----------------------
ISO/TS 29761:2015(E)
COPYRIGHT PROTECTED DOCUMENT
© ISO 2015, Published in Switzerland

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized otherwise in any form

or by any means, electronic or mechanical, including photocopying, or posting on the internet or an intranet, without prior

written permission. Permission can be requested from either ISO at the address below or ISO’s member body in the country of

the requester.
ISO copyright office
Ch. de Blandonnet 8 • CP 401
CH-1214 Vernier, Geneva, Switzerland
Tel. +41 22 749 01 11
Fax +41 22 749 09 47
copyright@iso.org
www.iso.org
ii © ISO 2015 – All rights reserved
---------------------- Page: 2 ----------------------
ISO/TS 29761:2015(E)
Contents Page

Foreword ..........................................................................................................................................................................................................................................v

Introduction ................................................................................................................................................................................................................................vi

1 Scope ................................................................................................................................................................................................................................. 1

2 Normative references ...................................................................................................................................................................................... 1

3 Terms and definitions ..................................................................................................................................................................................... 1

4 Fire safety engineering applications ............................................................................................................................................... 4

4.1 The role of occupant behaviour scenarios in fire safety design ................................................................... 4

4.2 The role of design occupant behavioural scenarios in fire safety design ............................................. 4

5 Focusing the steps of ISO 16733-1 for a life safety objective .................................................................................. 6

5.1 Overview of the procedure ........................................................................................................................................................... 6

5.2 Step 1 — Identify the specific safety challenges ........................................................................................................ 6

5.3 Step 2 — Location of fire ................................................................................................................................................................ 6

5.4 Step 3 — Type of fire ......................................................................................................................................................................... 7

5.5 Step 4 — Potential complicating hazards leading to other fire scenarios ........................................... 7

5.6 Step 5 — Systems and features impacting fire ............................................................................................................ 7

5.7 Step 6 — Occupant actions impacting fire ...................................................................................................................... 8

5.8 Steps 7 to 9 — Scenario selection ........................................................................................................................................... 8

6 Design occupant behavioural scenarios ...................................................................................................................................... 8

6.1 Characteristics of occupant behavioural scenarios ................................................................................................. 8

6.2 Identification of occupant behavioural scenarios .................................................................................................... 9

6.2.1 General...................................................................................................................................................................................... 9

6.2.2 Step A — Number of occupants and distribution of occupants ...........................................10

6.2.3 Step B — Characteristics of the occupant population ..................................................................11

6.2.4 Step C — Activities of occupants .....................................................................................................................11

6.2.5 Step D — Presence and training of staff ...................................................................................................12

6.3 Selection of design occupant behavioural scenarios ...........................................................................................12

6.3.1 General...................................................................................................................................................................................12

6.3.2 Step E — Occupant characteristics matrix .............................................................................................12

6.3.3 Considerations on selecting scenarios .......................................................................................................13

6.3.4 Final selection and documentation .................. .............................................................................................13

6.3.5 Sensitivity analysis of parameters affecting life safety objectives .....................................14

7 Design occupant behaviour ....................................................................................................................................................................15

7.1 General ........................................................................................................................................................................................................15

7.2 Basic characteristics ........................................................................................................................................................................18

7.2.1 General...................................................................................................................................................................................18

7.2.2 Pre-travel activity time ............................................................................................................................................19

7.2.3 Exit choice ...........................................................................................................................................................................19

7.2.4 Travel time .........................................................................................................................................................................19

7.2.5 Intervention by fire services and other emergency responders .........................................20

7.2.6 Intervention by others .............................................................................................................................................20

7.2.7 Completion of the evacuation ............................................................................................................................20

7.3 Parameters provided by the design occupant behavioural scenario ....................................................20

7.4 Parameters to be defined ............................................................................................................................................................20

7.4.1 Pre-travel activity time ............................................................................................................................................20

7.4.2 Exit choice ...........................................................................................................................................................................21

7.4.3 Travel speed ......................................................................................................................................................................21

7.4.4 Parameters that need to be defined when simplistic calculation models

are employed ....................................................................................................................................................................22

7.5 Estimates of evacuation time and occupant condition ......................................................................................22

7.5.1 General...................................................................................................................................................................................22

7.5.2 Simple calculation methods for evacuation time ..............................................................................22

7.5.3 Advanced calculation methods for evacuation time ......................................................................22

© ISO 2015 – All rights reserved iii
---------------------- Page: 3 ----------------------
ISO/TS 29761:2015(E)

7.5.4 Tests .........................................................................................................................................................................................23

Bibliography .............................................................................................................................................................................................................................24

iv © ISO 2015 – All rights reserved
---------------------- Page: 4 ----------------------
ISO/TS 29761:2015(E)
Foreword

ISO (the International Organization for Standardization) is a worldwide federation of national standards

bodies (ISO member bodies). The work of preparing International Standards is normally carried out

through ISO technical committees. Each member body interested in a subject for which a technical

committee has been established has the right to be represented on that committee. International

organizations, governmental and non-governmental, in liaison with ISO, also take part in the work.

ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of

electrotechnical standardization.

The procedures used to develop this document and those intended for its further maintenance are

described in the ISO/IEC Directives, Part 1. In particular the different approval criteria needed for the

different types of ISO documents should be noted. This document was drafted in accordance with the

editorial rules of the ISO/IEC Directives, Part 2 (see www.iso.org/directives).

Attention is drawn to the possibility that some of the elements of this document may be the subject of

patent rights. ISO shall not be held responsible for identifying any or all such patent rights. Details of

any patent rights identified during the development of the document will be in the Introduction and/or

on the ISO list of patent declarations received (see www.iso.org/patents).

Any trade name used in this document is information given for the convenience of users and does not

constitute an endorsement.

For an explanation on the meaning of ISO specific terms and expressions related to conformity

assessment, as well as information about ISO’s adherence to the WTO principles in the Technical

Barriers to Trade (TBT) see the following URL: Foreword - Supplementary information

The committee responsible for this document is ISO/TC 92, Fire safety, Subcommittee SC 4, Fire

safety engineering.
© ISO 2015 – All rights reserved v
---------------------- Page: 5 ----------------------
ISO/TS 29761:2015(E)
Introduction

In a fire safety engineering assessment, the ability of occupants to escape safely or find a designated

place of refuge is evaluated for each design fire scenario, taking account of the occupants expected to

be present in the building or other structure.

The purpose of this Technical Specification is to outline a general methodology for selecting design

fire scenarios for the specific fire safety objective of life safety of the occupants, and then developing

the occupant behavioural scenarios for which those design fire scenarios will be tested. ISO 16733-1

provides general guidance on the selection of design fire scenarios.

Since each design fire scenario might require several different occupant behavioural scenarios,

the number of possible design occupant behavioural scenarios in any built environment (a building,

structure or transportation vehicle) can be very large, and it is not possible to quantify them all.

This large set of possibilities needs to be reduced to a manageably small set of occupant behavioural

scenarios that are amenable to analysis. In a deterministic assessment, which is implicitly envisioned in

this Technical Specification, a manageable number of design occupant behavioural scenarios is selected.

For a full quantitative risk assessment, see ISO 16732-1.

The characterization of an occupant behavioural scenario involves a description of the initial occupant

distribution and the number and other characteristics of the population, including their reaction and

response capabilities. The occupant behavioural scenarios will be specifically determined for each

design fire scenario, which itself includes the interaction with the proposed fire protection features for

the built environment. The possible consequences of each fire scenario for each occupant behavioural

scenario need to be considered.

Following selection of the design occupant behavioural scenarios, it is necessary to describe the

assumed characteristics of the occupant behaviour on which the scenario quantification will be based.

These assumed occupant behaviour characteristics are referred to as “the design occupant behaviour”.

Design occupant behaviours are usually characterised in terms of pre-travel activity delay times

(response and reaction times) and occupant movement speeds. The design occupant behaviour needs

to be appropriate to the life safety objective of the fire safety engineering analysis and has to result in a

design solution that is conservative.
vi © ISO 2015 – All rights reserved
---------------------- Page: 6 ----------------------
TECHNICAL SPECIFICATION ISO/TS 29761:2015(E)
Fire safety engineering — Selection of design occupant
behavioural scenarios
1 Scope

This Technical Specification describes a methodology for the selection of design occupant behavioural

scenarios that are severe but credible for use in deterministic fire safety engineering analyses of any

built environment including buildings, structures, or transportation vehicles.

Occupant behavioural scenarios are linked to design fire scenarios. Guidance on the selection of design

fire scenarios and design fires is covered in ISO 16733-1. The steps in ISO 16733-1 are followed in

this Technical Specification with life safety of the occupants as the single fire safety objective under

consideration.

ISO/TR 16738 provides information on methods for the quantification of the different aspects of human

evacuation behaviour in a design context. One part of that process involves the selection of occupant

behavioural scenarios. This Technical Specification provides guidance for that aspect of the evaluation

of an egress design.

This Technical Specification addresses behaviours that occur after fire ignition and does not deal with

behaviours that influence fire ignition.
2 Normative references

The following documents, in whole or in part, are normatively referenced in this document and are

indispensable for its application. For dated references, only the edition cited applies. For undated

references, the latest edition of the referenced document (including any amendments) applies.

ISO 13571:2012, Life-threatening components of fire — Guidelines for the estimation of time to compromised

tenability in fires
ISO 13943, Fire safety — Vocabulary

ISO 16733-1:2015, Fire safety engineering — Selection of design fire scenarios and design fires — Part 1:

Selection of design fire scenarios

ISO/TR 16738, Fire-safety engineering — Technical information on methods for evaluating behaviour and

movement of people.
3 Terms and definitions

For the purposes of this document, the terms and definitions given in ISO 13943, ISO/TR 16738 and the

following apply.

NOTE Some of the definitions have been updated to reflect the current understanding of the terms as

employed in fire safety engineering. Some are duplicated here for the convenience of users of this document.

© ISO 2015 – All rights reserved 1
---------------------- Page: 7 ----------------------
ISO/TS 29761:2015(E)
3.1
ASET
available safe escape time

for an individual occupant, the calculated time interval between the time of ignition and the time at

which conditions become such that the occupant is estimated to be incapacitated, i.e. unable to take

effective action to escape to a safe refuge or place of safety

Note 1 to entry: The time of ignition may be known, e.g. in the case of a fire model or a fire test, or it may be

assumed, e.g. it may be based upon an estimate working back from the time of detection. The basis on which the

time of ignition is determined needs to be stated.

Note 2 to entry: This definition equates incapacitation with failure to escape. Other criteria for ASET are possible.

If an alternate criterion is selected, it needs to be stated.

Note 3 to entry: Each occupant can have a different value of ASET, depending on that occupant’s personal

characteristics.
[SOURCE: ISO 13943:2008, 4.20, modified]
3.2
built environment
building or other structure

EXAMPLE Off-shore platforms; civil engineering works, such as tunnels, bridges, and mines; and means of

transportation, such as motor vehicles and marine vessels.

Note 1 to entry: ISO 6707-1 contains a number of terms and definitions for concepts related to the built environment.

[SOURCE: ISO 13943:2008, 4.26]
3.3
design fire

quantitative description of assumed fire characteristics within the design fire scenario (3.4)

Note 1 to entry: It is, typically, an idealized description of the variation with time of important fire variables,

such as heat release rate, flame spread rate, smoke production rate, toxic gas yields, and temperature.

[SOURCE: ISO 13943:2008, 4.64]
3.4
design fire scenario

specific fire scenario (3.7) on which a deterministic fire safety engineering analysis is conducted

Note 1 to entry: As the number of possible fire scenarios can be very large, it is necessary to select the most

important scenarios (the design fire scenarios) for analysis. The selection of design fire scenarios is tailored to

the fire-safety design objectives and accounts for the likelihood and consequences of potential scenarios.

[SOURCE: ISO 13943:2008, 4.65]
3.5
design occupant behaviour

quantitative description of occupant behavioural characteristics within the design occupant behavioural

scenario (3.6)

Note 1 to entry: It is, typically, an idealized description of the time needed for evacuation or refuge, comprising

components for recognition, response, and travel. The actual variables include delay time, travel distance, and

travel speed.

EXAMPLE Young, intoxicated people in a stadium might delay longer before beginning to evacuate than

those who are not intoxicated; older people in a nursing home may travel more slowly than other mobile adults

would; intoxicated people may have more difficulty with decision-making and, as a result, might take more time

to make exit choices.
2 © ISO 2015 – All rights reserved
---------------------- Page: 8 ----------------------
ISO/TS 29761:2015(E)
3.6
design occupant behavioural scenario

specific occupant behavioural scenario on which a deterministic fire safety engineering analysis

will be conducted
3.7
fire scenario

qualitative description of the course of a fire with respect to time, identifying key events that

characterise the studied fire and differentiate it from other possible fires

Note 1 to entry: It typically defines the ignition and fire growth processes, the fully developed fire stage, the fire

decay stage, and the environment and systems that impact on the course of the fire.

[SOURCE: ISO 13943:2008, 4.129]
3.8
occupant behavioural scenario

qualitative description of occupant behaviour and response over time, including the number of

occupants and the physical and cognitive characteristics that affect their decision-making and actions in

response to fire cues, identifying key characteristics that differentiate members from other occupants

Note 1 to entry: It typically describes the number and other characteristics and capabilities of group members

that would impact the decision-making and behavioural processes (i.e. elderly occupants might be less likely to

hear an alarm and may move more slowly than younger occupants; staff may recognize and react to an alarm

more quickly and engage in rescue activities before evacuating themselves).
3.9
pre-travel activity time
PTAT

for an individual occupant, the interval between the time at which a warning of a fire is given and the

time at which the first move is made by that occupant towards an exit

Note 1 to entry: This consists of two components: recognition time (3.10) and response time (3.11).

Note 2 to entry: For groups of occupants, the following two phases can be recognized:

— pre-travel activity time of the first occupants to move;

— pre-travel activity time distribution between the first and last occupants to move.

[SOURCE: ISO/TR 16738:2009, 3.9]
3.10
recognition time

interval between the time at which a warning of a fire is given and the first response to the warning

[SOURCE: ISO/TR 16738:2009, 3.10]

Note 1 to entry: This concept is thoroughly discussed in ISO/TR 16738:2009, Annex B.

3.11
response time

interval between the time at which the first response to the event occurs and the time at which travel

begins to a safe location (3.13)
[SOURCE: ISO/TR 16738:2009, 3.11]

Note 1 to entry: This concept is thoroughly discussed ISO/TR 16738:2009, Annex B.

© ISO 2015 – All rights reserved 3
---------------------- Page: 9 ----------------------
ISO/TS 29761:2015(E)
3.12
RSET
required safe escape time

calculated time period required for an individual occupant to travel from their location at the time of

ignition to a safe refuge or place of safety
[SOURCE: ISO 13943:2008, 4.277]
3.13
safe location

location remote or separated from the effects of a fire so that such effects no longer pose a threat

Note 1 to entry: The safe location may be inside or outside the building depending upon the evacuation strategy.

[SOURCE: ISO/TR 16738:2009, 3.12]
3.14
travel time

time needed, once movement towards an exit has begun, for an occupant of a specified part of a building

to reach a safe location (3.13)
[SOURCE: ISO/TR 16738:2009, 3.14]
4 Fire safety engineering applications
4.1 The role of occupant behaviour scenarios in fire safety design

When a built environment is designed, it has expected (planned) uses and users. In order to complete

an evaluation of an engineered design, design fire scenarios are developed to demonstrate that the

design will meet its fire safety design objectives. This process is outlined in ISO 16733-1.

When life safety is one of the design objectives, the evaluation demonstrates the extent to which occupants

are protected from the fire and its effects. The evaluation should include: the users and/or occupants of

the building, their roles, needs, and anticipated abilities, and, if and how the occupants will react and

respond to a fire. These factors enable determining the degree of life safety provided by the design.

Just as the fire safety evaluation requires fire scenarios appropriate to the building’s design and

intended use, the evaluation also requires scenarios of occupant behaviour that reflect the expected

population and their characteristics, as described in this Technical Specification.

4.2 The role of design occupant behavioural scenarios in fire safety design

The evaluation of the life safety provided by an engineered design requires an assessment as to

whether occupants are protected for the period of time, after fire ignition, until they reach a designated

place of safety.

The location of occupants within a building, at any one time, and the way occupant location changes

with time during normal use and emergency situations depends on the interaction of a variety of

parameters related to the characteristics of the building and the occupants, the fire safety management

system proposed for the building and the developing fire scenario. There are essentially five categories

of information required to determine the location (and condition) of occupants during a fire:

a) the building characteristics;
b) fire safety management strategy/procedure;
c) the occupant characteristics;
d) the fire dynamics, including smoke transport;
4 © ISO 2015 – All rights reserved
---------------------- Page: 10 ----------------------
ISO/TS 29761:2015(E)
e) intervention effects;

f) the acute effects of the fire effluent on the individual occupants to the extent that there is

quantitative knowledge on which to base the evaluation.

Long-term effects of exposure to the fire effluent should also be considered, to the extent that there is

quantitative knowledge on which to base the evaluation.

Changes in occupant location during an incident depend on pre-travel activity processes (including

recognition and response) and movement processes. Each of these processes occurs over a period of time:

recognition time, response time, and movement or travel time. These times can be estimated for each

individual, for groups of people in the same location, or a distribution of times can be estimated for the

building population. The calculation of these times is an essential task in evaluating an engineered design.

In evaluating a design option, one would:

— take a building, as designed, including its evacuation plan and fire safety management plan;

— determine the various types of potential occupants to consider (e.g. staff vs. visitors, disabled vs.

able-bodied, etc.);

— determine the relevant design fire scenarios given the identified occupant population;

— for each design fire scenario, evaluate the predicted outcome for each type of occupant;

— compare the available and required escape times for relevant parts of the building (i.e. estimate the

harm done to people by the range of fires that can occur in the building if it is designed as proposed,

and compare that harm to levels of acceptable harm as set by the stakeholders for the project);

— at each step of the calculations, provide for estimation of uncertainty, as that will be important in

the final evaluation.
In order to do this, one would:

1) determine design occupant behavioural scenarios, including initial input, as well as response data

(if necessary);
2) choose an appropriate evacuation calculation method;
3) model the fire and apply the evacuation calculation method;

4) compare the results to the guidance on estimating time available for escape, given in ISO 13571.

There may be several fire safety objectives to be evaluated for a particular design. When life safety is

the objective being considered, occupant behavioural scenarios are constructed. They may be relevant

for other fire safety objectives.

It would be impossible to analyse all scenarios even with the aid of the most sophisticated computing

resources. This infinite set of possibilities needs to be reduced to a smaller, manageable set of groupings

or clusters of scenarios that are amenable to analysis and that collectively represent the range of

combinations of occupant numbers and other characteristics that could be present.

Once occupant behavioural scenarios are selected and evaluated, the design of the built environment

is modified until analysis demonstrates that the estimated fire risk associated with the design is

acceptably low and meets the performance criteria associated with the specified fire safety objective(s).

The characterisation of a design occupant behavioural scenario for analysis purposes involves a

description of such things as the number of occupants, their locations throughout the built environment,

and their ability or inability to recognize and respond to fire cues, and their ability or inability to move

through the available escape routes. The impacts of smoke and fire on people are part of potentially

relevant consequences of a design occupant behavioural scenario and are part of the characterisation

of that scenario when those consequences are relevant to the life safety objective. The characterisation

or quantification of occupant recognition and response and movement belong to the “design occupant

© ISO 2015 – All rights reserved 5
---------------------- Page: 11 ----------------------
ISO/TS 29761:2015(E)
...

SPÉCIFICATION ISO/TS
TECHNIQUE 29761
Première édition
2015-12-15
Ingénierie de la sécurité incendie —
Sélection de scénarios de
comportements des occupants de
dimensionnement
Fire safety engineering — Selection of design occupant behavioural
scenarios
Numéro de référence
ISO/TS 29761:2015(F)
ISO 2015
---------------------- Page: 1 ----------------------
ISO/TS 29761:2015(F)
DOCUMENT PROTÉGÉ PAR COPYRIGHT
© ISO 2015, Publié en Suisse

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni utilisée

sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie, l’affichage sur

l’internet ou sur un Intranet, sans autorisation écrite préalable. Les demandes d’autorisation peuvent être adressées à l’ISO à

l’adresse ci-après ou au comité membre de l’ISO dans le pays du demandeur.
ISO copyright office
Ch. de Blandonnet 8 • CP 401
CH-1214 Vernier, Geneva, Switzerland
Tel. +41 22 749 01 11
Fax +41 22 749 09 47
copyright@iso.org
www.iso.org
ii © ISO 2015 – Tous droits réservés
---------------------- Page: 2 ----------------------
ISO/TS 29761:2015(F)
Sommaire Page

Avant-propos ................................................................................................................................................................................................................................v

Introduction ................................................................................................................................................................................................................................vi

1 Domaine d’application ................................................................................................................................................................................... 1

2 Références normatives ................................................................................................................................................................................... 1

3 Termes et définitions ....................................................................................................................................................................................... 1

4 Applications de l’ingénierie de la sécurité incendie ....................................................................................................... 4

4.1 Rôle des scénarios de comportements des occupants dans le dimensionnement de

la sécurité incendie ............................................................................................................................................................................. 4

4.2 Rôle des scénarios de comportements des occupants de dimensionnement dans le

dimensionnement de la sécurité incendie ...................................................................................................................... 5

5 Recentrage des étapes de l’ISO 16733-1 pour un objectif de sécurité pour les personnes ....6

5.1 Aperçu de la procédure.................................................................................................................................................................... 6

5.2 Étape 1 — Identification des enjeux spécifiques en matière de sécurité ............................................. 7

5.3 Étape 2 — Localisation du feu ................................................................................................................................................... 7

5.4 Étape 3 — Type de feu ...................................................................................................................................................................... 7

5.5 Étape 4 — Dangers aggravants potentiels conduisant à d’autres scénarios d’incendie ......... 8

5.6 Étape 5 — Systèmes et dispositifs ayant une influence sur le feu .............................................................. 8

5.7 Étape 6 — Actions des occupants ayant une influence sur le feu ............................................................... 9

5.8 Étapes 7 à 9 — Sélection des scénarios ..........................................................................................................................10

6 Scénarios de comportements des occupants de dimensionnement............................................................10

6.1 Caractéristiques des scénarios de comportements des occupants ........................................................10

6.2 Identification des scénarios de comportements des occupants ...............................................................11

6.2.1 Généralités .........................................................................................................................................................................11

6.2.2 Étape A — Nombre et répartition des occupants .............................................................................12

6.2.3 Étape B — Caractéristiques de la population d’occupants ......................................................12

6.2.4 Étape C — Activités des occupants ...............................................................................................................13

6.2.5 Étape D— Présence et formation du personnel ................................................................................13

6.3 Sélection des scénarios de comportements des occupants de dimensionnement ...................13

6.3.1 Généralités .........................................................................................................................................................................13

6.3.2 Étape E — Matrice des caractéristiques des occupants .................. ............................................14

6.3.3 Considérations lors de la sélection des scénarios ............................................................................14

6.3.4 Sélection finale et documentation .................................................................................................................15

6.3.5 Analyse de sensibilité des paramètres influant sur les objectifs de sécurité

des personnes ........................................................................................................................................... .......................15

7 Comportement des occupants de dimensionnement ..................................................................................................17

7.1 Généralités ...............................................................................................................................................................................................17

7.2 Caractéristiques de base ..............................................................................................................................................................20

7.2.1 Généralités .........................................................................................................................................................................20

7.2.2 Temps de pré-mouvement ....................................................................................................................................21

7.2.3 Choix de sortie ................................................................................................................................................................21

7.2.4 Temps de déplacement ............................................................................................................................................22

7.2.5 Intervention des services d’incendie et autres services de secours .................. ...............22

7.2.6 Intervention d’autres personnes ....................................................................................................................22

7.2.7 Fin de l’évacuation .......................................................................................................................................................22

7.3 Paramètres fournis par le scénario de comportements des occupants

de dimensionnement ......................................................................................................................................................................23

7.4 Paramètres à définir ........................................................................................................................................................................23

7.4.1 Temps de pré-mouvement ....................................................................................................................................23

7.4.2 Choix de sortie ................................................................................................................................................................24

7.4.3 Vitesse de déplacement ..........................................................................................................................................24

7.4.4 Paramètres devant être définis lorsque des modèles de calculs simplistes

sont utilisés........................................................................................................................................................................24

© ISO 2015 – Tous droits réservés iii
---------------------- Page: 3 ----------------------
ISO/TS 29761:2015(F)

7.5 Estimations du temps d’évacuation et des conditions pour les occupants .....................................25

7.5.1 Généralités .........................................................................................................................................................................25

7.5.2 Méthodes de calcul simplifiées pour le temps d’évacuation ...................................................25

7.5.3 Méthodes de calcul avancées pour le temps d’évacuation .......................................................25

7.5.4 Essais.......................................................................................................................................................................................26

Bibliographie ...........................................................................................................................................................................................................................27

iv © ISO 2015 – Tous droits réservés
---------------------- Page: 4 ----------------------
ISO/TS 29761:2015(F)
Avant-propos

L’ISO (Organisation internationale de normalisation) est une fédération mondiale d’organismes

nationaux de normalisation (comités membres de l’ISO). L’élaboration des Normes internationales est

en général confiée aux comités techniques de l’ISO. Chaque comité membre intéressé par une étude

a le droit de faire partie du comité technique créé à cet effet. Les organisations internationales,

gouvernementales et non gouvernementales, en liaison avec l’ISO participent également aux travaux.

L’ISO collabore étroitement avec la Commission électrotechnique internationale (IEC) en ce qui

concerne la normalisation électrotechnique.

Les procédures utilisées pour élaborer le présent document et celles destinées à sa mise à jour sont

décrites dans les Directives ISO/IEC, Partie 1. Il convient, en particulier de prendre note des différents

critères d’approbation requis pour les différents types de documents ISO. Le présent document a été

rédigé conformément aux règles de rédaction données dans les Directives ISO/IEC, Partie 2 (voir www.

iso.org/directives).

L’attention est appelée sur le fait que certains des éléments du présent document peuvent faire l’objet de

droits de propriété intellectuelle ou de droits analogues. L’ISO ne saurait être tenue pour responsable

de ne pas avoir identifié de tels droits de propriété et averti de leur existence. Les détails concernant

les références aux droits de propriété intellectuelle ou autres droits analogues identifiés lors de

l’élaboration du document sont indiqués dans l’Introduction et/ou dans la liste des déclarations de

brevets reçues par l’ISO (voir www.iso.org/brevets).

Les appellations commerciales éventuellement mentionnées dans le présent document sont données

pour information, par souci de commodité, à l’intention des utilisateurs et ne sauraient constituer un

engagement.

Pour une explication de la signification des termes et expressions spécifiques de l’ISO liés à

l’évaluation de la conformité, ou pour toute information au sujet de l’adhésion de l’ISO aux principes

de l’OMC concernant les obstacles techniques au commerce (OTC), voir le lien suivant: Avant-propos —

Informations supplémentaires.

Le comité chargé de l’élaboration du présent document est l’ISO/TC 92, Sécurité au feu, Sous-comité

SC 4, Ingénierie de la sécurité incendie.
© ISO 2015 – Tous droits réservés v
---------------------- Page: 5 ----------------------
ISO/TS 29761:2015(F)
Introduction

Dans une évaluation d’ingénierie de la sécurité incendie, la capacité des occupants à évacuer en

toute sécurité ou à trouver un lieu de refuge désigné est évaluée pour chaque scénario d’incendie de

dimensionnement, en tenant compte des occupants supposés être présents dans l’environnement bâti.

L’objet de la présente Spécification technique est de présenter une méthodologie générale pour

sélectionner des scénarios d’incendie de dimensionnement dont l’objectif de sécurité spécifique est la

sécurité des occupants, puis développer les scénarios de comportements des occupants pour lesquels

ces scénarios d’incendie de dimensionnement seront évalués. L’ISO 16733-1 fournit des préconisations

générales concernant la sélection des scénarios d’incendie de dimensionnement.

Comme chaque scénario d’incendie de dimensionnement peut nécessiter plusieurs scénarios différents

de comportements des occupants, le nombre de possibilités de scénarios de comportements des

occupants de dimensionnement dans un environnement bâti quelconque (bâtiment, ouvrage ou

véhicule de transport) peut être très grand et, il n’est pas possible de tous les quantifier. Ce grand

nombre de possibilités doit être réduit à un ensemble raisonnable de scénarios de comportements

des occupants, dont l’analyse est plus aisément maîtrisable. Dans une évaluation déterministe,

comme implicitement envisagée dans la présente Spécification technique, un nombre raisonnable de

scénarios de comportements des occupants de dimensionnement est sélectionné. Pour une évaluation

quantitative complète du risque, voir l’ISO 16732-1.

La caractérisation d’un scénario de comportements des occupants comprend la description de la

répartition initiale des occupants et le nombre ainsi que les autres caractéristiques de la population,

y compris leurs capacités de réaction et de réponse. Les scénarios de comportements des occupants

seront déterminés spécifiquement pour chaque scénario d’incendie de dimensionnement, lequel

comprend lui-même l’interaction avec les dispositifs de protection contre l’incendie proposés pour

l’environnement bâti. Les conséquences possibles de chaque scénario d’incendie pour chaque scénario

de comportements des occupants doivent être prises en considération.

Suite à la sélection des scénarios de comportements des occupants de dimensionnement, il est

nécessaire de décrire les caractéristiques présumées du comportement des occupants sur lesquelles se

fondera la quantification du scénario. Ces caractéristiques supposées du comportement des occupants

sont appelées «comportement des occupants de dimensionnement». Les comportements des occupants

de dimensionnement sont habituellement caractérisés en termes de temps de pré-mouvement (temps

de réponse et de réaction) et de vitesses de déplacement des occupants. Il est nécessaire que le

comportement des occupants de dimensionnement soit adapté à l’objectif de sécurité des personnes de

l’analyse d’ingénierie de la sécurité incendie et qu’il aboutisse à une solution de dimensionnement qui

est conservative.
vi © ISO 2015 – Tous droits réservés
---------------------- Page: 6 ----------------------
SPÉCIFICATION TECHNIQUE ISO/TS 29761:2015(F)
Ingénierie de la sécurité incendie — Sélection de scénarios
de comportements des occupants de dimensionnement
1 Domaine d’application

La présente Spécification technique décrit une méthodologie de sélection de scénarios de comportements

des occupants de dimensionnement, qui sont sévères mais plausibles, pour être utilisés dans des

analyses déterministes d’ingénierie de la sécurité incendie d’un environnement bâti quelconque, dont

les bâtiments, les ouvrages ou les véhicules de transport.

Les scénarios de comportements des occupants sont liés aux scénarios d’incendie de dimensionnement.

Des préconisations concernant la sélection de scénarios d’incendie et de feux de dimensionnement sont

fournies dans l’ISO 16733-1. Les étapes de l’ISO 16733-1 sont respectées dans la présente Spécification

technique, avec la sécurité des occupants comme unique objectif de sécurité incendie considéré.

L’ISO/TR 16738 fournit des informations sur les méthodes utilisées lors de la conception pour la

quantification des différents aspects du comportement humain en cas d’évacuation. Une partie de

ce processus comprend la sélection de scénarios de comportements des occupants. La présente

Spécification technique contient des préconisations concernant cet aspect de l’évaluation d’une

stratégie d’évacuation.

La présente Spécification technique traite des comportements qui surviennent après l’allumage d’un

feu, mais n’aborde pas les comportements qui influencent cet allumage.
2 Références normatives

Les documents ci-après, dans leur intégralité ou non, sont des références normatives indispensables à

l’application du présent document. Pour les références datées, seule l’édition citée s’applique. Pour les

références non datées, la dernière édition du document de référence s’applique (y compris les éventuels

amendements).

ISO 13571:2012, Composants dangereux du feu — Lignes directrices pour l’estimation du temps disponible

avant que les conditions de tenabilité ne soient compromises.
ISO 13943, Sécurité au feu — Vocabulaire.

ISO 16733-1:2015, Ingénierie de la sécurité incendie — Sélection de scénarios d’incendie et de feux de

dimensionnement — Partie 1: Sélection de scénarios d’incendie de dimensionnement.

ISO/TR 16738, Ingénierie de la sécurité incendie — Informations techniques sur les méthodes d’évaluation

du comportement et du mouvement des personnes.
3 Termes et définitions

Pour les besoins du présent document, les termes et définitions donnés dans l’ISO 13943, l’ISO/TR 16738

ainsi que les suivants, s’appliquent.

NOTE Certaines définitions ont été mises à jour pour refléter la compréhension actuelle des termes employés

en ingénierie de la sécurité incendie. Certaines ont été dupliquées dans le présent document pour la commodité

de ses utilisateurs.
© ISO 2015 – Tous droits réservés 1
---------------------- Page: 7 ----------------------
ISO/TS 29761:2015(F)
3.1
ASET
temps disponible pour l’évacuation en sécurité

pour un occupant individuel, l’intervalle de temps calculé entre le moment de l’allumage et le moment

où les conditions sont telles que l’occupant se trouve dans l’incapacité d’exécuter une action efficace

d’évacuation vers un refuge sûr ou une zone de sécurité

Note 1 à l’article: L’instant d’allumage peut être connu, par exemple dans le cas d’un modèle feu ou d’un essai au

feu, ou bien il peut être supposé connu; par exemple, il peut être basé sur une estimation à rebours à partir de

l’instant de détection. Il est nécessaire d’indiquer les conditions permettant de déterminer l’instant d’allumage.

Note 2 à l’article: Cette définition correspond à une incapacitation avec impossibilité de s’échapper. D’autres

critères pour l’ASET sont possibles. Si un critère de rechange est sélectionné, il est nécessaire de l’indiquer.

Note 3 à l’article: Chaque occupant peut avoir une valeur différente d’ASET, selon ses caractéristiques

personnelles.
[SOURCE: ISO 13943:2008, 4.20, modifiée]
3.2
environnement bâti
immeuble ou autre structure

EXEMPLE Les plateformes off-shore, les travaux de génie civil comme les tunnels, les ponts et les mines, et

les moyens de transport, comme les véhicules à moteur et les bateaux.

Note 1 à l’article: L’ISO 67071 contient un certain nombre de termes et de définitions de concepts associés à

l’environnement bâti.
[SOURCE: ISO 13943:2008, 4.26]
3.3
feu de dimensionnement

description quantitative des caractéristiques théoriques d’un incendie dans le cadre du scénario

d’incendie de dimensionnement (3.4)

Note 1 à l’article: Il s’agit en général d’une description idéale de la variation en fonction du temps des variables

importantes de l’incendie telles que le débit calorifique, la vitesse de propagation de flammes, le taux de

dégagement de fumée, les rendements en gaz toxiques et la température.
[SOURCE: ISO 13943:2008, 4.64]
3.4
scénario d’incendie de dimensionnement

scénario d’incendie (3.7) spécifique sur lequel sera réalisée une analyse déterministe d’ingénierie de la

sécurité incendie

Note 1 à l’article: Du fait que le nombre de scénarios d’incendie possibles peut être très grand, il est nécessaire

de sélectionner les scénarios les plus importants (les scénarios d’incendie de dimensionnement) pour l’analyse.

La sélection des scénarios d’incendie de dimensionnement est adaptée aux objectifs de dimensionnement de la

sécurité incendie et tient compte de la probabilité et des effets des scénarios potentiels.

[SOURCE: ISO 13943:2008, 4.65]
3.5
comportement des occupants de dimensionnement

description quantitative des caractéristiques du comportement des occupants dans le scénario de

comportements des occupants de dimensionnement (3.6)

Note 1 à l’article: En général, il s’agit d’une description idéalisée du temps nécessaire à l’évacuation ou à l’accès

à un refuge, incluant les composantes de reconnaissance, de réaction et de déplacement. Les variables réelles

comprennent le délai d’attente, la distance d’évacuation et la vitesse de déplacement.

2 © ISO 2015 – Tous droits réservés
---------------------- Page: 8 ----------------------
ISO/TS 29761:2015(F)

EXEMPLE De jeunes gens en état d’ébriété dans un stade peuvent tarder davantage avant de commencer à

évacuer que des personnes sobres; des personnes âgées dans une maison de retraite peuvent se déplacer plus

lentement que d’autres adultes plus mobiles; les personnes en état d’ébriété peuvent avoir plus de difficultés à

prendre des décisions et, par conséquent, peuvent prendre plus de temps pour se décider à choisir une issue.

3.6
scénario de comportements des occupants de dimensionnement

scénario spécifique de comportements des occupants sur lequel une analyse déterministe d’ingénierie

de la sécurité incendie sera réalisée
3.7
scénario d’incendie

description qualitative du déroulement d’un incendie dans le temps, identifiant les évènements clés qui

caractérisent l’incendie et le différencient des autres incendies potentiels

Note 1 à l’article: Il définit typiquement les processus d’allumage et de croissance du feu, le stade de feu

complètement développé, le stade de déclin du feu, ainsi que l’environnement et les systèmes qui interviennent

dans le déroulement de l’incendie.
[SOURCE: ISO 13943:2008, 4.129]
3.8
scénario de comportements des occupants

description qualitative du comportement et de la réponse des occupants dans le temps, incluant le

nombre d’occupants et les caractéristiques physiques et cognitives qui affectent leur prise de décision

et leurs actions en réponse à des signes d’incendie, en identifiant les principales caractéristiques qui

différencient ces membres des autres occupants

Note 1 à l’article: Il décrit habituellement le nombre et autres caractéristiques et capacités des membres d’un

groupe qui sont susceptibles d’avoir un impact sur leur prise de décision et leurs processus comportementaux

(par exemple, des occupants âgés peuvent être moins susceptibles d’entendre une alarme et peuvent se déplacer

plus lentement que des occupants plus jeunes; le personnel peut reconnaître et réagir à une alarme plus

rapidement et prendre part à des activités de sauvetage avant d’évacuer eux-mêmes).

3.9
temps de pré-mouvement
PTAT

pour un occupant individuel, intervalle entre le moment où une alerte incendie est donnée et le moment

où l’occupant commence à se diriger vers une sortie

Note 1 à l’article: Ce temps a deux composantes: le temps de reconnaissance (3.10) et le temps de réaction (3.11).

Note 2 à l’article: Pour les groupes d’occupants, les deux phases suivantes peuvent être identifiées:

— le temps de pré-mouvement des premiers occupants qui se déplacent;

— la distribution du temps de pré-mouvement entre les premiers et les derniers occupants qui se déplacent.

[SOURCE: ISO/TR 16738:2009, 3.9]
3.10
temps de reconnaissance

intervalle entre le moment où une alerte incendie est donnée et la première réaction à cette alerte

[SOURCE: ISO/TR 16738:2009, 3.10]

Note 1 à l’article: Ce concept est présenté de manière plus approfondie dans l’ISO/TR 16738:2009, Annexe B.

© ISO 2015 – Tous droits réservés 3
---------------------- Page: 9 ----------------------
ISO/TS 29761:2015(F)
3.11
temps de réaction

intervalle entre le moment où a lieu la première réaction à un événement et le moment où le déplacement

vers un endroit sécurisé commence (3.13)
[SOURCE: ISO/TR 16738:2009, 3.11]

Note 1 à l’article: Ce concept est présenté de manière plus approfondie dans l’ISO/TR 16738:2009, Annexe B.

3.12
RSET
temps nécessaire pour l’évacuation en sécurité

durée calculée nécessaire à un occupant pour passer de son emplacement au moment de l’allumage à un

refuge sûr ou une zone de sécurité
[SOURCE: ISO 13943:2008, 4.277]
3.13
endroit sécurisé

lieu éloigné ou isolé des effets d’un feu de sorte que ces effets ne constituent plus une menace

Note 1 à l’article: L’endroit sécurisé peut se trouver à l’intérieur ou à l’extérieur de l’environnement bâti en

fonction de la stratégie d’évacuation.
[SOURCE: ISO/TR 16738:2009, 3.12]
3.14
temps de déplacement

temps nécessaire, une fois le mouvement vers la sortie amorcé, pour qu’un occupant d’une partie

spécifiée d’un environnement bâti atteigne un endroit sécurisé (3.13)
[SOURCE: ISO/TR 16738:2009, 3.14]
4 Applications de l’ingénierie de la sécurité incendie
4.1 Rôle des scénarios de comportements des occupants dans le dimensionnement de
la sécurité incendie

Quand un environnement bâti est conçu, il est prévu (planifié) pour des usages et des usagers. Pour

réaliser l’évaluation d’une conception d’ingénierie, des scénarios d’incendie de dimensionnement

sont développés afin de démontrer que la conception répondra aux objectifs de sécurité incendie. Ce

processus est exposé dans l’ISO 16733-1.

Lorsque la sécurité des personnes est l’un des objectifs de conception, l’évaluation démontre dans

quelle mesure les occupants sont protégés d’un incendie et de ses effets. Il convient que l’évaluation

comprenne: les utilisateurs et/ou occupants de l’environnement bâti, leurs rôles, leurs besoins et leurs

capacités prévues, ainsi que la probabilité que les occupants réagissent et répondent à un incendie et

la manière dont ils le feront. Ces facteurs permettent de déterminer le degré de sécurité des personnes

prévu par le dimensionnement.

De même que l’évaluation de la sécurité incendie requiert des scénarios d’incendie adaptés à la

conception et à l’usage prévu de l’environnement bâti, l’évaluation nécessite également des scénarios

de comportements des occupants qui reflètent la population attendue et ses caractéristiques, comme

décrit dans la présente Spécification technique.
4 © ISO 2015 – Tous droits réservés
---------------------- Page: 10 ----------------------
ISO/TS 29761:2015(F)
4.2 Rôle des scénarios de comportements des occupants de dimensionnement dans le
dimensionnement de la sécurité incendie

L’évaluation de la sécurité des personnes fournie par un dimensionnement d’ingénierie exige une

évaluation de la protection des occupants pendant la durée allant de l’allumage de l’incendie jusqu’au

moment où ils atteignent un endroit sécurisé désigné.

La localisation des occupants dans un environnement bâti à un moment donné et la manière dont la

localisation des occupants évolue avec le temps, dans des conditions normales d’utilisation et dans

des situations d’urgence, dépendent de l’interaction de plusieurs paramètres différents relatifs aux

caractéristiques de l’environnement bâti et des occupants, du système de gestion de la sécurité incendie

proposé pour l’environnement bâti et du scénario d’incendie en développement. Il existe principalement

cinq catégories d’informations requises pour déterminer l’emplacement (et l’état) des occupants au

cours d’un incendie:
a) les caractéristiques de l’environnement bâti;
b) la stratégie/procédure de gestion de la sécurité incendie;
c) les caractéristiques des occupants;
d) la dynamique du feu, y compris le transport de la fumée;
e) les conséquences de l’intervention;

f) les effets graves des effluents du feu sur chaque occupant, dans la mesure où il existe des

connaissances quantitatives sur lesquelles se fonde l’évaluation.

Il convient également de tenir compte des effets à long terme de l’exposition aux effluents du feu, dans

la mesure où il existe des connaissances quantitatives sur lesquelles se fonde l’évaluation.

La modification de la localisation de l’occupant lors d’un incident dépend des processus d’activité de

pré-mouvement (y compris la reconnaissance et la réaction) et des processus de mouvement. Chacun

de ces processus se produit sur une période de temps: le temps de reconnaissance, le temps de réaction

et le temps de mouvement ou de déplacement. Ces temps peuvent être estimés pour
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.