ISO 27327-1
(Main)Fans — Air curtain units — Part 1: Laboratory methods of testing for aerodynamic performance rating
- Abstract
ISO 27327-1:2009 establishes uniform methods for laboratory testing of air curtain units to determine aerodynamic performance in terms of airflow rate, outlet air velocity uniformity, power consumption and air velocity projection, for rating or guarantee purposes. ISO 27327-1:2009 is not applicable to the specification of test procedures to be used for design, production or field testing.
- Status
- Not Published
- Technical Committee
- ISO/TC 117 - Fans
- Drafting Committee
- ISO/TC 117/WG 9 - Air curtain units
- Current Stage
- 6000 - International Standard under publication - 60 Publication
- Start Date
- 21-Oct-2026
Buy Documents
ISO/FDIS 27327-1 - Fans — Air curtain units — Part 1: Laboratory methods of testing for aerodynamic performance rating
REDLINE ISO/FDIS 27327-1 - Fans — Air curtain units — Part 1: Laboratory methods of testing for aerodynamic performance rating
ISO 27327-1, published by ISO, sets laboratory methods for testing air curtain units. It specifies how to rate aerodynamic performance in terms of airflow rate, outlet air velocity uniformity, power consumption and air velocity projection for rating or guarantee purposes. ISO 27327-1 is for laboratory testing, not for design, production or field testing.
What does ISO 27327-1 specify?
ISO 27327-1 specifies how to test an air curtain unit (ACU) in the laboratory and how to report the results for performance rating. The document is organized into a short front matter, Clause 1 scope, Clause 2 normative references, Clause 3 terms, Clauses 4 to 6 for the three test methods, Clause 7 with illustrations, and four annexes.
| Annex | What it covers |
|---|---|
| Annex A | Air curtain discharge area |
| Annex B | Air curtain depth and width |
| Annex C | Air curtain active and inactive depth and width |
| Annex D | Uncertainty in velocity determination using Pitot-static tube and manometer due to manometer slope |
Clauses 4 to 6 cover the three performance checks: airflow rate, outlet air velocity uniformity, and velocity projection. Clause 7 shows the test layouts and example calculations that support those clauses.
What are the key requirements of ISO 27327-1?
Clause 4 - ACU airflow rate test
ISO 27327-1 requires the ACU to be mounted with its inlet sealed to the test chamber, with the primary discharge nozzle or adjustable vanes set to 0° ± 3°. The unit must run for at least 15 minutes before the first determination so that conditions stabilize.
The test uses a wattmeter with certified accuracy of ±1% of the observed reading, and the airflow-rate test is based on ISO 5801 methods except where ISO 27327-1 adds its own steps. The test records the manufacturer, model, impeller diameter, inlet and outlet areas, number of fans and motors, motor data, accessories attached, and which accessories are energized. In practice, this gives a traceable record of the exact unit and setup being rated.
At least three determinations are taken over a chamber gauge stagnation pressure range from +25 Pa to -25 Pa, or the best obtainable equivalent range if -25 Pa cannot be reached. The results are fitted to a second-order pressure-versus-airflow curve, and the free-air delivery point is taken where static pressure is zero. The standard also requires the corresponding average outlet air velocity and input power to be reported at that operating point.
Clause 5 - ACU outlet air velocity uniformity test
ISO 27327-1 measures how evenly the air curtain spreads across its width. The test uses air curtain core velocity measurements taken with a Pitot-static tube and manometer, a hot-wire anemometer, or another device with ±5.0% accuracy.
The ACU is positioned so the inlet and discharge nozzle are unobstructed, the air curtain width is perpendicular to the floor, and the primary nozzle is set to 15° ± 1°. Units without an adjustable nozzle are mounted so that nothing interferes with the airstream for 3 000 mm. For practical use, this means the test tries to remove installation effects and isolate the unit’s own performance.
The test is based on a minimum of five equally spaced test lines on Plane 1, located one air curtain depth from the normal discharge plane. The line spacing must not exceed 100 mm, and the maximum core velocity along each line is recorded. The calculation uses the average core velocity and its standard deviation to produce outlet air velocity uniformity as a percentage.
Clause 6 - ACU velocity projection test
ISO 27327-1 also measures how far the air curtain keeps its velocity downstream. The test uses at least three planes parallel to the normal discharge plane, with at least five equally spaced test lines across each plane and the same type of core-velocity measurement used in Clause 5.
The sponsor of the test chooses either a target distance method or a minimum average core velocity method. With the target distance method, the planes are placed at 1 000 mm intervals, with defined intermediate positions for shorter targets. With the minimum average core velocity method, the test continues until the calculated average core velocity falls to or below the specified minimum. This gives a performance picture that is useful when the buying or rating question is how far the air curtain remains effective.
Clause 7 and the reporting requirements
ISO 27327-1 requires consistent units in the test report and records the key unit details used in each test. Reports include the manufacturer, trade name, model number, impeller diameter, inlet and outlet areas, number of fans and motors, and motor nameplate data. Clause 7 also shows the test layouts, the air discharge angle setup, the distance calculations, the test-line spacing, and the example performance chart used for reporting airflow-rate results.
What terms does ISO 27327-1 define?
- Air curtain unit (ACU) - An air-moving device that produces an air curtain.
- Air curtain - A directionally controlled airstream with a minimum width-to-depth ratio of 5:1.
- ACU airflow rate - The airflow leaving the ACU discharge nozzle at standard air conditions, measured in accordance with ISO 5801.
- Air curtain discharge area - The true cross-sectional area of the air curtain on the normal discharge plane.
- Air curtain normal discharge plane - The plane perpendicular to the airflow normal at the trailing edge of the active discharge nozzle.
- ACU outlet air velocity uniformity - An indicator of how consistent the air velocities are across the air curtain width, expressed as a percentage.
- ACU velocity projection - A set of average core velocities measured along the air curtain width at specified distances from the normal discharge plane.
- ACU target distance - The distance, specified by the sponsor, used to stop a velocity projection test.
Who uses ISO 27327-1?
ISO 27327-1 is used by manufacturers of air curtain units, test laboratories, and technical teams that need laboratory-rated performance data. It is also useful for quality managers, certification or verification bodies, and buyers who need comparable airflow, uniformity, power, and projection results before accepting a unit. The standard is especially relevant where air curtains are selected for openings that need controlled airflow performance.
What changed in ISO 27327-1 from the previous edition?
ISO 27327-1 is the second edition and it cancels and replaces ISO 27327-1:2009. The foreword states these main changes:
- clarified the difference between the dimensions of the air curtain and the air discharge nozzle
- expanded the definitions of air curtain and discharge nozzle width and depth to cover non-rectangular constructions
- added definitions for discharge nozzles that are not perpendicular to the opening or parallel to the floor by using a normal discharge plane
- added a minimum air curtain core velocity method to the air curtain velocity projection test, so a target-distance test can end when a specified core-velocity limit is reached
Which standards are used with ISO 27327-1?
- ISO 5801 - ISO 27327-1 uses ISO 5801 for standardized airway testing, shared measurement practice, and the calculation framework used in the airflow-rate and related test clauses. Where ISO 27327-1 needs different treatment, it states the exception explicitly.
What does the ISO 27327-1 document contain?
ISO 27327-1 contains the three laboratory test methods, the supporting definitions, and the calculation steps needed to rate ACU performance. It includes figures for the air curtain depth, normal discharge plane, airflow-rate setup, outlet air velocity uniformity setup, velocity projection setup, and a typical airflow-rate performance chart. The document also includes a sample calculation layout for uniformity and projection results, plus informative annex figures showing discharge area, depth and width, and active and inactive sections. Annex D provides the uncertainty treatment for velocity determination with a Pitot-static tube and manometer when manometer slope affects the reading.
Relations
- Effective Date
- 19-Aug-2023
Buy Documents
ISO/FDIS 27327-1 - Fans — Air curtain units — Part 1: Laboratory methods of testing for aerodynamic performance rating
REDLINE ISO/FDIS 27327-1 - Fans — Air curtain units — Part 1: Laboratory methods of testing for aerodynamic performance rating
Get Certified
Connect with accredited certification bodies for this standard
Institut za varilstvo d.o.o. (Welding Institute)
Slovenia's leading welding institute since 1952. ISO 3834, EN 1090, pressure equipment certification, NDT personnel, welder qualification. Only IIW Au
Sponsored listings
Frequently Asked Questions
ISO 27327-1 is a draft published by the International Organization for Standardization (ISO). Its full title is "Fans — Air curtain units — Part 1: Laboratory methods of testing for aerodynamic performance rating". This standard covers: ISO 27327-1:2009 establishes uniform methods for laboratory testing of air curtain units to determine aerodynamic performance in terms of airflow rate, outlet air velocity uniformity, power consumption and air velocity projection, for rating or guarantee purposes. ISO 27327-1:2009 is not applicable to the specification of test procedures to be used for design, production or field testing.
ISO 27327-1:2009 establishes uniform methods for laboratory testing of air curtain units to determine aerodynamic performance in terms of airflow rate, outlet air velocity uniformity, power consumption and air velocity projection, for rating or guarantee purposes. ISO 27327-1:2009 is not applicable to the specification of test procedures to be used for design, production or field testing.
ISO 27327-1 is classified under the following ICS (International Classification for Standards) categories: 23.120 - Ventilators. Fans. Air-conditioners. The ICS classification helps identify the subject area and facilitates finding related standards.
ISO 27327-1 has the following relationships with other standards: It is inter standard links to ISO 27327-1:2009. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
ISO 27327-1 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 1 Scope
- 2 Normative references
- 3 Terms, definitions and symbols
- 3.1 Terms and definitions
- 3.1.1 absolute pressure
- 3.1.2 air curtain unit
- 3.1.3 ACU airflow rate
- 3.1.4 ACU average outlet air velocity
- 3.1.5 ACU discharge nozzle
- 3.1.6 ACU discharge nozzle depth
- 3.1.7 ACU discharge nozzle width
- 3.1.8 ACU inlet area
- 3.1.9 ACU normal
- 3.1.10 ACU outlet air velocity uniformity
- 3.1.11 ACU input power
- 3.1.12 ACU pressure
- 3.1.13 ACU static pressure
- 3.1.14 ACU target distance
- 3.1.15 ACU velocity projection
- 3.1.16 air curtain
- 3.1.17 air curtain average core velocity
- 3.1.18 air curtain core velocity
- 3.1.19 air curtain discharge angle
- 3.1.20 air curtain discharge area
- 3.1.21 air curtain depth
- 3.1.22 air curtain normal discharge plane
- 3.1.23 air curtain width
- 3.1.24 air density
- 3.1.25 airflow rate
- 3.1.26 atmospheric pressure
- 3.1.27 barometric pressure
- 3.1.28 determination
- 3.1.29 dry-bulb temperature
- 3.1.30 dynamic pressure at a point
- 3.1.31 free-air delivery
- 3.1.32 gauge pressure
- 3.1.33 gauge stagnation pressure at a point
- 3.1.34 inlet stagnation volume flow rate
- 3.1.35 point of operation
- 3.1.36 pressure loss
- 3.1.37 standard air
- 3.1.38 static pressure
- 3.1.39 test
- 3.1.40 velocity pressure
- 3.1.41 wet-bulb temperature
- 3.2 Symbols
- 4 ACU airflow rate test
- 4.1 Apparatus and instruments
- 4.2 Preparation of ACU airflow rate test
- 4.3 Test procedure
- 4.4 Calculation
- 4.5 Test report
- 5 ACU outlet air velocity uniformity test
- 5.1 Apparatus and instruments
- 5.2 ACU outlet air velocity uniformity test
- 5.3 Test procedure
- 5.4 Calculation
- 5.5 Test report
- 6 ACU velocity projection test
- 6.1 Apparatus and instruments
- 6.2 Equipment and organization
- 6.3 Test procedure
- 6.4 Calculation
- 6.5 Test report
- 7 Illustration of tests
- 7.1 ACU airflow rate test
- 1 ACU
- 2 ACU discharge nozzle angle arrangement [as given in Figure 4 b)]
- 4 ACU inlet sealed to testing chamber
- 1 ACU
- 2 ACU discharge nozzle
- 7.2 Determination of air discharge angle, θ
- 1 ACU
- 2 ACU discharge nozzle
- 5 ACU inlet
- 7.3 Determination of Distance, A
- 1 ACU
- 2 ACU discharge nozzle
- 7.4 Calculation of test line space, C
- 7.5 Calculation of air curtain average core velocity, ν
1 Scope
This document establishes uniform methods for laboratory testing of air curtain units to determine aerodynamic performance in terms of airflow rate, outlet air velocity uniformity, power consumption and air velocity projection, for rating or guarantee purposes.
This document does not specify test procedures to be used for design, production or field testing.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 5801, Fans — Performance testing using standardized airways
3 Terms, definitions and symbols
For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:
- ISO Online browsing platform: available at https:// www .iso .org/ obp
- IEC Electropedia: available at https:// www .electropedia .org/
3.1 Terms and definitions
3.1.1 absolute pressure
p value of a pressure when the datum pressure is absolute zero Note 1 to entry: This is always positive.
3.1.2 air curtain unit
ACU air-moving device which produces an air curtain.
ISO/FDIS 27327-1:2026(en)
3.1.3 ACU airflow rate
q airflow volume which leaves the ACU discharge nozzle (3.1.5), at standard air conditions, as measured in accordance with ISO 5801 Note 1 to entry: This is given by Formula (1):
q = q (1) Vsg1 where q is the volume flow rate at stagnation conditions Vsg1 Note 2 to entry: This rate is expressed in cubic metres per second
3.1.4 ACU average outlet air velocity
ν a ACU airflow rate (3.1.3) produced by the ACU divided by the air curtain discharge area (3.1.20) on the air curtain normal discharge plane (3.1.22) at free-air delivery Note 1 to entry: See 4.4.3 for calculation of the value.
Note 2 to entry: Velocity is expressed in metres per second.
3.1.5 ACU discharge nozzle
component or an assembly in the ACU which directs and controls the airstream Note 1 to entry: May include decorative (inactive) sections.
Note 2 to entry: May include adjustable vanes.
Note 3 to entry: Leading edge shall be the first point or edge where the airstream leaves the ACU discharge nozzle. Note 4 to entry: Trailing edge shall be the last point or edge where the airstream leaves the ACU discharge nozzle. Note 5 to entry: If only one ACU discharge nozzle is present, it is the primary ACU discharge nozzle. Note 6 to entry: ACU discharge nozzles are considered “multiple” when they do not share a common airflow discharge plane and are spaced more than two times the ACU discharge nozzle depth apart. The primary ACU discharge nozzle on a system with multiple ACU discharge nozzles is that which is closest to the plane of the protected opening.
3.1.6 ACU discharge nozzle depth
h n inside short dimension of the ACU discharge nozzle (3.1.5) perpendicular to the airflow plane Note 1 to entry: If a decorative (inactive) section exists between two active sections, it shall be considered active and included in the dimension.
Note 2 to entry: If the ACU discharge nozzle is not rectangular, it shall be the largest measurement of the short dimension.
Note 3 to entry: Depth is expressed in millimetres.
Note 4 to entry: Refer to Figures B.1 and C.1 for examples.
3.1.7 ACU discharge nozzle width
b n inside long dimension of the ACU discharge nozzle (3.1.5) parallel to the airflow plane Note 1 to entry: If decorative (inactive) section exists between two active sections, it shall be considered active and included in the dimension.
ISO/FDIS 27327-1:2026(en) Note 2 to entry: If the ACU discharge nozzle is not rectangular, it shall be the largest measurement of the long side. Note 3 to entry: Width is expressed in millimetres.
Note 4 to entry: Refer to Figures B.1 and C.1 for examples.
3.1.8 ACU inlet area
total inside net area of all surfaces where entering airflow first meets the ACU cabinet
3.1.9 ACU normal
vector declared by the sponsor that identifies the ACU cabinet orientation when the air curtain discharge angle is 0° and parallel to the plane of the opening it is protecting
3.1.10 ACU outlet air velocity uniformity
u ACU indicator of the consistency of air velocities across the air curtain width Note 1 to entry: The outlet air velocity uniformity is expressed as a percentage. Note 2 to entry: See 5.4.4 for calculation of the value. See Figure 7.
3.1.11 ACU input power
power rating P e electrical power supplied at the terminals of the ACU Note 1 to entry: Includes electric motor(s) and drive(s).
Note 2 to entry: Input power is expressed in watts.
3.1.12 ACU pressure
p ACU difference between the stagnation pressure at the ACU outlet and the stagnation pressure at the ACU inlet Note 1 to entry: This is determined using Formula (2):
p = p − p (2) ACU sg2 sg1 Note 2 to entry: When the Mach number is less than 0,15, it is possible to use the relationship given in Formula (3):
p = p − p (3) ACU t2 t1 Note 3 to entry: ACU pressure is expressed in pascals.
3.1.13 ACU static pressure
p sACU conventional quantity defined as the ACU pressure minus the ACU dynamic pressure corrected by the Mach factor Note 1 to entry: This is determined using Formula (4):
p = −p (4) sACU sg1 Note 2 to entry: Static pressure is expressed in pascals.
ISO/FDIS 27327-1:2026(en)
3.1.14 ACU target distance
t distance perpendicular to the air curtain normal discharge plane (3.1.22) specified by the sponsor of the test to terminate an ACU velocity projection (3.1.15) test Note 1 to entry: See 6.3.3.1 for definition of distances.
Note 2 to entry: Target distance is expressed in metres.
3.1.15 ACU velocity projection
set of average air curtain core velocities (3.1.17) measured along the air curtain width at specified distances from the air curtain normal discharge plane (3.1.22) Note 1 to entry: See 6.3.3.1 for definition of distances.
Note 2 to entry: Velocity is expressed in metres per second.
3.1.16 air curtain
directionally controlled airstream with a minimum width to depth ratio of 5:1 Note 1 to entry: When applied across the entire height and width of an opening, can reduce the infiltration or transfer of air from one side of the opening to the other and/or inhibit the passage of moisture, insects, dust and debris.
3.1.17 air curtain average core velocity
ν ca average of air curtain core velocities (3.1.18) measured along the air curtain width at specified distances from the air curtain normal discharge plane (3.1.22) Note 1 to entry: See 6.3.3.1 for definition of distances.
Note 2 to entry: See 6.4.3 for determination.
Note 3 to entry: Velocity is expressed in metres per second.
3.1.18 air curtain core velocity
ν
maximum air velocity of the air curtain at point x as measured across both the air curtain depth and width at specified distances from the air curtain normal discharge plane (3.1.22) Note 1 to entry: See 5.3.4 and 6.4.2 for determinations.
Note 2 to entry: See 6.3.3.1 for definition of distances.
Note 3 to entry: Velocity is expressed in metres per second.
3.1.19 air curtain discharge angle
θ angle between the ACU normal (3.1.9) or plane of the protected opening and the direction in which the air curtain leaves the ACU discharge nozzle (3.1.5)
3.1.20 air curtain discharge area
A ac true cross-sectional area of the air curtain on the air curtain normal discharge plane (3.1.22) Note 1 to entry: Rectangular area is obtained by using the air curtain width and depth.
ISO/FDIS 27327-1:2026(en) Note 2 to entry: This is determined using Formula (5).
()bh ac ac A (5) ac
11 0 Note 3 to entry: Discharge area is expressed in metre square.
Note 4 to entry: See Figure A.1 for examples.
3.1.21 air curtain depth
h ac short dimension of the air curtain measured on the air curtain normal discharge plane (3.1.22) Note 1 to entry: If the ACU discharge nozzle’s entire depth is actively directing the airstream and is coplanar with the air curtain normal discharge plane, it shall be equal to the ACU discharge nozzle depth. Note 2 to entry: If the ACU discharge nozzle depth has decorative (inactive) sections and is coplanar with the air curtain normal discharge plane, it shall be equal to the largest measurement of the short dimension of the active section declared and located by the sponsor.
Note 3 to entry: If the ACU discharge nozzle’s entire depth is actively directing the airstream and is not coplanar with the air curtain normal discharge plane, it shall be the largest short measurement from trailing edge of the ACU discharge nozzle to the intersection of a line projected 5° from the leading edge of the ACU discharge nozzle and the air curtain normal discharge plane.
Note 4 to entry: If the ACU discharge nozzle depth has decorative (inactive) sections and is not coplanar with the air curtain normal discharge plane it shall be the largest short measurement from trailing edge of the ACU discharge nozzle to the intersection of a line projected 5° from the leading edge of the active ACU discharge nozzle declared by the sponsor and the air curtain normal discharge plane.
Note 5 to entry: Depth is expressed in millimetres.
Note 6 to entry: Refer to Figures 1, B.1, and C.1 for examples. Key 1 air curtain normal discharge plane 2 airflow normal 3 leading edge of the active nozzle 4 trailing edge of the active nozzle Figure 1 — Air curtain depth
3.1.22 air curtain normal discharge plane
plane perpendicular to the airflow normal (0° discharge angle) created by the cross section of the air curtain Note 1 to entry: It is located at the trailing edge of the active ACU discharge nozzle. Note 2 to entry: See Figure 2 for examples.
ISO/FDIS 27327-1:2026(en) Key 1 air curtain normal discharge plane 2 airflow normal Figure 2 — Air curtain normal discharge plane
3.1.23 air curtain width
b ac long dimension of the air curtain measured on the air curtain normal discharge plane (3.1.22) Note 1 to entry: If the ACU discharge nozzle’s entire width is actively directing the airstream and is coplanar with the air curtain normal discharge plane, it shall be equal to the ACU discharge nozzle width. Note 2 to entry: If the ACU discharge nozzle width has decorative (inactive) sections and is coplanar with the air curtain normal discharge plane, it shall be equal to the largest measurement of the long dimension of the active section declared and located by the sponsor.
Note 3 to entry: If the ACU discharge nozzle’s entire width is actively directing the airstream and is not coplanar with the air curtain normal discharge plane, it shall be the largest long measurement from trailing edge of the ACU discharge nozzle to the intersection of a line projected 5° from the leading edge of the ACU discharge nozzle and the air curtain normal discharge plane.
Note 4 to entry: If the ACU discharge nozzle width has decorative (inactive) sections and is not coplanar with the air curtain normal discharge plane it shall be the largest long measurement from trailing edge of the ACU discharge nozzle to the intersection of a line projected 5° from the leading edge of the active ACU discharge nozzle declared by the sponsor and the air curtain normal discharge plane.
Note 5 to entry: Width is expressed in millimetres.
Note 6 to entry: Refer to Figures B.1 and C.1 for examples.
3.1.24 air density
ρ a mass per unit volume of air Note 1 to entry: Air density is expressed in kilograms per cubic metre.
3.1.25 airflow rate
flow of air or an air current, specifically one that passes through a dimensionally defined plane
3.1.26 atmospheric pressure
p a absolute pressure of the free atmosphere at the mean altitude of the ACU Note 1 to entry: Pressure is expressed in pascals.
ISO/FDIS 27327-1:2026(en)
3.1.27 barometric pressure
p b absolute pressure exerted by the atmosphere at a location of measurement Note 1 to entry: Pressure is expressed in pascals.
3.1.28 determination
complete set of measurements for a particular point of operation for the parameter being determined
3.1.29 dry-bulb temperature
T d air temperature measured by a dry temperature sensor in the test enclosure, near the ACU inlet or airway inlet Note 1 to entry: Temperature is expressed in degrees Celsius.
3.1.30 dynamic pressure at a point
p d pressure calculated from the velocity and the density, ρ , of the air at a point a Note 1 to entry: The point is determined using Formula (6):
p (6) da
Note 2 to entry: Pressure is expressed in pascals.
3.1.31 free-air delivery
point of operation where the ACU operates against zero static pressure
3.1.32 gauge pressure
p e value of the pressure when the datum pressure is the atmospheric pressure at the point of measurement Note 1 to entry: Gauge pressure can be negative or positive.
Note 2 to entry: Gauge pressure is determined using Formula (7):
pp p (7) ea Note 3 to entry: Pressure is expressed in pascals.
3.1.33 gauge stagnation pressure at a point
p esg difference between the absolute stagnation pressure, p , and the atmospheric pressure, p sg a Note 1 to entry: This pressure is calculated using Formula (8):
p = p − p (8) esg sg a Note 2 to entry: Pressure is expressed in pascals.
ISO/FDIS 27327-1:2026(en)
3.1.34 inlet stagnation volume flow rate
q Vsg1 mass flow rate divided by the inlet stagnation density Note 1 to entry: This is determined using Formula (9):
q m q (9) Vsg1
sg1 Note 2 to entry: Volume flow rate is expressed in cubic metres per second.
3.1.35 point of operation
relative position on the air curtain performance curve corresponding to a particular airflow rate, pressure, power and efficiency
3.1.36 pressure loss
decrease in pressure caused by friction and turbulence
3.1.37 standard air
air with a standard density of 1,2 kg/m at a standard barometric pressure of 101,325 kPa
3.1.38 static pressure
pressure that exists by degree of compression only Note 1 to entry: If expressed as gauge pressure, it may be positive or negative.
3.1.39 test
series of determinations of various characteristics at a single point of operation of an ACU
3.1.40 velocity pressure
pressure that exists by virtue of rate of motion only
3.1.41 wet-bulb temperature
T w air temperature measured by a temperature sensor covered by a water-moistened wick and exposed to air in motion Note 1 to entry: When properly measured, it is a close approximation to the temperature of adiabatic saturation. Note 2 to entry: Temperature is expressed in degrees Celsius.
3.2 Symbols
Symbol Term Unit
A Air Curtain cross-sectional area m ac b Air curtain width mm ac b ACU discharge nozzle width mm n C The calculated test line spacing mm d
...
Contents
- 1 Scope
- 2 Normative references
- 3 Terms, definitions and symbols
- 3.1 Terms and definitions
- 3.1.2 Air Curtain Unit
- 3.1.2 air curtain unit
- 3.2 Symbols
- 4 ACU airflow rate test
- 4.1 Apparatus and instruments
- 1 Mainsmains
- 2 Motormotor control (e.g. VSD)
- 3 Motormotor
- 4.2 Preparation of ACU airflow rate test
- 4.3 Test procedure
- 4.4 Calculation
- 4.5 Test report
- 5 ACU outlet air velocity uniformity test
- 5.1 Apparatus and instruments
- 5.2 ACU outlet air velocity uniformity test
- 5.3 Test procedure
- 5.4 Calculation
- 5.5 Test report
- 6 ACU velocity projection test
- 6.1 Apparatus and instruments
- 6.2 Equipment and organization
- 6.3 Test procedure
- 6.4 Calculation
- 6.5 Test report
- 7 Illustration of tests
- 7.1 ACU airflow rate test
- 1 ACU
- 2 ACU discharge nozzle angle arrangement [as given in Figure 4Figure 4 b)]
- 4 ACU inlet sealed to testing chamber
- 1 ACU
- 2 ACU discharge nozzle
- 7.2 Determination of air discharge angle, θ
- 1 ACU
- 2 ACU discharge nozzle
- 5 ACU inlet
- 7.3 Determination of Distance, A
- 1 ACU
- 2 ACU discharge nozzle
- 7.4 Calculation of test line space, Cd
- 7.5 Calculation of air curtain average core velocity, ν
- 7.6 Calculation of standard if deviation, s
- 1 ACU
- 2 ACU discharge nozzle
- Annex A
- Annex B
- Annex C
- 1 ACU discharge nozzle active section
- 2 ACU discharge nozzle inactive section
- 3 ACU discharge nozzle vane
- Annex D
- Bibliography
1 Scope
This document establishes uniform methods for laboratory testing of air curtain units to determine aerodynamic performance in terms of airflow rate, outlet air velocity uniformity, power consumption and air velocity projection, for rating or guarantee purposes.
This document does not specify test procedures to be used for design, production or field testing.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 5801, Fans — Performance testing using standardized airways
3 Terms, definitions and symbols
For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:
- — ISO Online browsing platform: available at https://www.iso.org/obphttps://www.iso.org/obp
- — IEC Electropedia: available at https://www.electropedia.org/https://www.electropedia.org/
3.1 Terms and definitions
3.1.1 3.1.1 absolute pressure p value of a pressure when the datum pressure is absolute zero NOTE Note 1 to entry: This is always positive.
3.1.2 Air Curtain Unit
3.1.2 air curtain unit
ACU air-moving device which produces an air curtain.
ISO/FDIS 27327-1:2026(en) 3.1.23.1.3 3.1.3 ACU airflow rate q airflow volume which leaves the ACU discharge nozzle [3.1.5],(3.1.5), at standard air conditions, as measured in accordance with ISO 5801 Note 1 to entry: This is given by Formula (1): Error! Reference source not found.:
q = q (1) Vsg1 where qVsg1 is the volume flow rate at stagnation conditions Note 2 to entry: This rate is expressed in cubic metres per second 3.1.33.1.4 3.1.4 ACU average outlet air velocity ν a ACU airflow rate [3.1.3](3.1.3) produced by the ACU divided by the air curtain discharge area [3.1.20](3.1.20) on the air curtain normal discharge plane [3.1.22](3.1.22) at free-air delivery NOTE 1 Note 1 to entry: See 4.4.34.4.3 for calculation of the value. NOTE Note 2 to entry: Velocity is expressed in metres per second. 3.1.43.1.5 3.1.5 ACU discharge nozzle component or an assembly in the ACU which directs and controls the airstream Note 1 to entry: May include decorative (inactive) sections.
Note 2 to entry: May include adjustable vanes.
Note 3 to entry: Leading edge shall be the first point or edge where the airstream leaves the ACU discharge nozzle. Note 4 to entry: Trailing edge shall be the last point or edge where the airstream leaves the ACU discharge nozzle. Note 5 to entry: If only one ACU discharge nozzle is present, it is the primary ACU discharge nozzle. Note 6 to entry: ACU discharge nozzles are considered “multiple” when they do not share a common airflow discharge plane and are spaced more than two times the ACU discharge nozzle depth apart. The primary ACU discharge nozzle on a system with multiple ACU discharge nozzles is that which is closest to the plane of the protected opening. 3.1.53.1.6 3.1.6 ACU discharge nozzle depth h n inside short dimension of the ACU discharge nozzle (3.1.5)(3.1.5) perpendicular to the airflow plane ICS 23.120 Price based on 29 pages
ISO/DISFDIS 27327-1:20252026(en) Note 1 to entry: If a decorative (inactive) section exists between two active sections, it shall be considered active and included in the dimension.
Note 2 to entry: If the ACU discharge nozzle is not rectangular, it shall be the largest measurement of the short dimension,.
Note 3 to entry: Depth is expressed in millimetres.
Note 4 to entry: Refer to Figures B.1Figure B.1 and C.1Figure C.1 for examples. 3.1.63.1.7 3.1.7 ACU discharge nozzle width bn inside long dimension of the ACU discharge nozzle [3.1.5](3.1.5) parallel to the airflow plane Note 1 to entry: If decorative (inactive) section exists between two active sections, it shall be considered active and included in the dimension.
Note 2 to entry: If the ACU discharge nozzle is not rectangular, it shall be the largest measurement of the long side. Note 3 to entry: Width is expressed in millimetres.
Note 4 to entry: Refer to Figures B.1Figure B.1 and C.1Figure C.1 for examples. 3.1.73.1.8 3.1.8 ACU inlet area total inside net area of all surfaces where entering airflow first meets the ACU cabinet 3.1.83.1.9 3.1.9 ACU normal vector declared by the sponsor that identifies the ACU cabinet orientation when the air curtain discharge angle is 0° and parallel to the plane of the opening it is protecting 3.1.93.1.10 3.1.10 ACU outlet air velocity uniformity u ACU indicator of the consistency of air velocities across the air curtain width Note 1 to entry: The outlet air velocity uniformity is expressed as a percentage. Note 2 to entry: See 5.4.45.4.4 for calculation of the value. See Figure 7.Figure 7 . 3.1.103.1.11 3.1.11 ACU input power power rating P e electrical power supplied at the terminals of the ACU Note 1 to entry: Includes electric motor(s) and drive(s).
Note 2 to entry: Input power is expressed in watts.
3.1.113.1.12 3.1.12 ACU pressure MUST BE USED p ACU difference between the stagnation pressure at the ACU outlet and the stagnation pressure at the ACU inlet FOR FINAL Note 1 to entry: This is determined using Formula (2): Error! Reference source not found.:
ISO/FDIS 27327-1:2026(en) pACU = psg2 − psg1 (2) Note 2 to entry: When the Mach number is less than 0,15, it is possible to use the relationship given in Formula (3):
Error! Reference source not found.:
pACU = pt2 − pt1 (3) Note 3 to entry: ACU pressure is expressed in pascals.
3.1.123.1.13 3.1.13 ACU static pressure p sACU conventional quantity defined as the ACU pressure minus the ACU dynamic pressure corrected by the Mach factor Note 1 to entry: This is determined using Formula (4): Error! Reference source not found.:
p = −p (4) sACU sg1 Note 2 to entry: Static pressure is expressed in pascals.
3.1.133.1.14 3.1.14 ACU target distance
t distance perpendicular to the air curtain normal discharge plane [3.1.22](3.1.22) specified by the sponsor of the test to terminate an ACU velocity projection [3.1.15](3.1.15) test Note 1 to entry: See 6.3.2.56.3.3.1 for definition of distances. Note 2 to entry: Target distance is expressed in metres.
3.1.143.1.15 3.1.15 ACU velocity projection set of average air curtain core velocities [3.1.17](3.1.17) measured along the air curtain width at specified distances from the air curtain normal discharge plane [3.1.22](3.1.22) Note 1 to entry: See 6.3.2.56.3.3.1 for definition of distances. Note 2 to entry: Velocity is expressed in metres per second.
3.1.153.1.16 3.1.16 air curtain directionally controlled airstream with a minimum width to depth ratio of 5:1 Note 1 to entry: When applied across the entire height and width of an opening, can reduce the infiltration or transfer of air from one side of the opening to the other and/or inhibit the passage of moisture, insects, dust and debris.
ICS 23.120 Price based on 29 pages
ISO/DISFDIS 27327-1:20252026(en) 3.1.163.1.17 3.1.17 air curtain average core velocity νca average of air curtain core velocities [3.1.18](3.1.18) measured along the air curtain width at specified distances from the air curtain normal discharge plane [3.1.22](3.1.22) Note 1 to entry: See 6.3.2.56.3.3.1 for definition of distances. Note 2 to entry: See 6.4.36.4.3 for determination.
Note 3 to entry: Velocity is expressed in metres per second.
3.1.173.1.18 3.1.18 air curtain core velocity ν
maximum air velocity of the air curtain at point x as measured across both the air curtain depth and width at specified distances from the air curtain normal discharge plane [3.1.22](3.1.22) Note 1 to entry: See 5.3.45.3.4 and 6.3.46.4.2 for determinations. Note 2 to entry: See 6.3.2.56.3.3.1 for definition of distances. Note 3 to entry: Velocity is expressed in metres per second.
3.1.183.1.19 3.1.19 air curtain discharge angle θ angle between the ACU normal [3.1.9](3.1.9) or plane of the protected opening and the direction in which the air curtain leaves the ACU discharge nozzle [3.1.5](3.1.5) 3.1.193.1.20 3.1.20 air curtain discharge area Aac true cross-sectional area of the air curtain on the air curtain normal discharge plane [3.1.22](3.1.22) Note 1 to entry: Rectangular area is obtained by using the air curtain width and depth. Note 2 to entry: This is determined using Formula (5). (5).
()bh ac ac A = (5) ac
110 (𝑏 × ℎ ) 𝑎𝑐 𝑎𝑐 𝐴 = 𝑎𝑐
1 × 10 (5) Note 3 to entry: Discharge area is expressed in metre squaredsquare. Note 4 to entry: See Figure A.1Figure A.1 for examples.
3.1.203.1.21 3.1.21 air curtain depth hac MUST BE USED short dimension of the air curtain measured on the air curtain normal discharge plane [3.1.22](3.1.22) Note 1 to entry: If the ACU discharge nozzle’s entire depth is actively directing the airstream and is coplanar with the air FOR FINAL curtain normal discharge plane, it shall be equal to the ACU discharge nozzle depth.
ISO/FDIS 27327-1:2026(en) Note 2 to entry: If the ACU discharge nozzle depth has decorative (inactive) sections and is coplanar with the air curtain normal discharge plane, it shall be equal to the largest measurement of the short dimension of the active section declared and located by the sponsor.
Note 3 to entry: If the ACU discharge nozzle’s entire depth is actively directing the airstream and is not coplanar with the air curtain normal discharge plane, it shall be the largest short measurement from trailing edge of the ACU discharge nozzle to the intersection of a line projected 5° from the leading edge of the ACU discharge nozzle and the air curtain normal discharge plane.
Note 4 to entry: If the ACU discharge nozzle depth has decorative (inactive) sections and is not coplanar with the air curtain normal discharge plane it shall be the largest short measurement from trailing edge of the ACU discharge nozzle to the intersection of a line projected 5° from the leading edge of the active ACU discharge nozzle declared by the sponsor and the air curtain normal discharge plane.
Note 5 to entry: Depth is expressed in millimetres.
Note 6 to entry: Refer to Figures 1, B.1,Figure 1 , Figure B.1 , and C.1Figure C.1 for examples.
Key 1 air curtain normal discharge plane 2 airflow normal 3 leading edge of the active nozzle 4 trailing edge of the active nozzle ICS 23.120 Price based on 29 pages
ISO/DISFDIS 27327-1:20252026(en) Figure 1 — Air Curtain Depthcurtain depth 3.1.213.1.22 3.1.22 air curtain normal discharge plane plane perpendicular to the airflow normal (0° discharge angle) created by the cross section of the air curtain Note 1 to entry 1: : It is located at the trailing edge of the active ACU discharge nozzle. Note 2 to entry 2: : See Figure 2Figure 2 for examples.
Key 1 air curtain normal discharge plane 2 airflow normal Figure 2 — Air Curtain Normal Discharge Planecurtain normal discharge plane 3.1.223.1.23 3.1.23 air curtain width bac long dimension of the air curtain measured on the air curtain normal discharge plane [3.1.22](3.1.22) Note 1 to entry: If the ACU discharge nozzle’s entire width is actively directing the airstream and is coplanar with the air curtain normal discharge plane, it shall be equal to the ACU discharge nozzle width. Note 2 to entry: If the ACU discharge nozzle width has decorative (inactive) sections and is coplanar with the air curtain normal discharge plane, it shall be equal to the largest measurement of the long dimension of the active section declared and located by the sponsor.
Note 3 to entry: If the ACU discharge nozzle’s entire width is actively directing the airstream and is not coplanar with the air curtain normal discharge plane, it shall be the largest long measurement from trailing edge of the ACU discharge MUST BE USED nozzle to the intersection of a line projected 5° from the leading edge of the ACU discharge nozzle and the air curtain normal discharge plane.
FOR FINAL
ISO/FDIS 27327-1:2026(en) Note 4 to entry: If the ACU discharge nozzle width has decorative (inactive) sections and is not coplanar with the air curtain normal discharge plane it shall be the largest long measurement from trailing edge of the ACU discharge nozzle to the intersection of a line projected 5° from the leading edge of the active ACU discharge nozzle declared by the sponsor and the air curtain normal discharge plane.
Note 5 to entry: Width is expressed in millimetres.
Note 6 to entry: Refer to Figures B.1Figure B.1 and C.1Figure C.1 for examples. 3.1.233.1.24 3.1.24 air density ρa mass per unit volume of air Note 1 to entry: Air density is expressed in kilograms per cubic metre. 3.1.243.1.25 3.1.25 airflow rate flow of air or an air current, specifically one that passes through a dimensionally defined plane 3.1.253.1.26 3.1.26 atmospheric pressure p a absolute pressure of the free atmosphere at the mean altitude of the ACU Note 1 to entry: Pressure is expressed in pascals.
3.1.263.1.27 3.1.27 barometric pressure p b absolute pressure exerted by the atmosphere at a location of measurement Note 1 to entry: Pressure is expressed in pascals.
3.1.273.1.28 3.1.28 determination complete set of measurements for a particular point of operation for the parameter being determined 3.1.283.1.29 3.1.29 dry-bulb temperature Td air temperature measured by a dry temperature sensor in the test enclosure, near the ACU inlet or airway inlet Note 1 to entry: Temperature is expressed in degrees Celsius.
ICS 23.120 Price based on 29 pages
ISO/DISFDIS 27327-1:20252026(en) 3.1.293.1.30 3.1.30 dynamic pressure at a point pd pressure calculated from the velocity and the density, ρ , of the air at a point. a Note 1 to entry: The point is determined using Formula (6): (6):
v 𝑣 p = 𝑝 = 𝜌 ( )
da d a 2
(6) NOTENote 2 to entry: Pressure is expressed in pascals.
3.1.303.1.31 3.1.31 free-air delivery point of operation where the ACU operates against zero static pressure 3.1.313.1.32 3.1.32 gauge pressure p e value of the pressure when the datum pressure is the atmospheric pressure at the point of measurement Note 1 to entry: Gauge pressure can be negative or positive.
Note 2 to entry: Gauge pressure is determined using Formula (7): (7):
p =−p p 𝑝 = 𝑝 − 𝑝 e a ea (7) Note 3 to entry: Pressure is expressed in pascals.
3.1.323.1.33 3.1.33 gauge stagnation pressure at a point p esg difference between the absolute stagnation pressure, p , and the atmospheric pressure, p sg a Note 1 to entry: This pressure is calculated using Formula (8): Error! Reference source not found.:
p = p − p (8) esg sg a Note 2 to entry: Pressure is expressed in pascals.
3.1.333.1.34 3.1.34 inlet stagnation volume flow rate q Vsg1 mass flow rate divided by the inlet stagnation density Note 1 to entry: This is determined using Formula (9): (9):
q 𝑞 m m q = 𝑞 = Vsg1 Vsg1 𝜌 sg1
sg1 MUST BE USED (9) Note 2 to entry: Volume flow rate is expressed in cubic metres per second. FOR FINAL
ISO/FDIS 27327-1:2026(en) 3.1.343.1.35 3.1.35 point of operation relative position on the air curtain performance curve corresponding to a particular airflow rate, pressure, power and efficiency 3.1.353.1.36 3.1.36 pressure loss decrease in pressure caused by friction and turbulence 3.1.363.1.37 3.1.37 standard air
air with a standard density of 1,2 kg/m at a standard barometric pressure of 101,325 kPa 3.1.373.1.38 3.1.38 static pressure pressure that exists by degree of compression only Note 1 to entry: If expressed as gauge pressure, it may be positive or negative. 3.1.383.1.39 3.1.39 test series of determinations of various characteristics at a single point of operation of an ACU 3.1.393.1.40 3.1.40 velocity pressure pressure that exists by virtue of rate of motion only 3.1.403.1.41 3.1.41 wet-bulb temperature Tw air temperature measured by a temperature sensor covered by a water-moistened wick and exposed to air in motion Note 1 to entry: When properly measured, it is a close approximation to the temperature of adiabatic saturation. Note 2 to entry: Temperature is expressed in degrees Celsius.
3.2 Symbols
Symbol Term Unit
Aac Air Curtain cross-sectional area m b Air curtain width mm ac b ACU discharge nozzle width mm n C The calculated test line spacing mm d ICS 23.120 Price based on 29 pages
ISO/DISFDIS 27327-1:20252026(en) E ACU energy effectiveness 1 ACU h Air curtain depth mm ac hn ACU discharge nozzle depth mm l ACU target distance m t n Number of data points 1 N ACU speed (rotational) r/min p Absolute pressure Pa p ACU pressure Pa ACU p Atmospheric pressure Pa a p Barometric pressure Pa b pd Dynamic pressure at a point Pa p Gauge pressure Pa e p Gauge stagnation pressure at a point Pa esg psg Absolute stagnation pressure Pa p Stagnation pressure at the ACU inlet Pa sg1 p Stagnation pressure at the ACU outlet Pa sg2 p ACU static pressure Pa sACU Pe ACU input power W
q ACU airflow rate m /s q Mass flow rate kg/s m
q Inlet stagnation volume flow rate m /s Vsg1
ρa Air density kg/m
...