ISO 15779:2026
(Main)Condensed aerosol fire extinguishing systems — Requirements and test methods for components and system design, installation and maintenance — General requirements
- Abstract
This document specifies the requirements and test methods for components of condensed aerosol firefighting systems. It gives recommendations for the design, installation, testing, maintenance and safety of these systems, as well as their application in buildings, plants or other structures. The characteristics of the extinguishants in the condensed aerosol firefighting systems are also specified, as well as the types of fire for which they are a suitable extinguishing medium. This document covers total flooding systems primarily related to buildings, plants and other specific applications, utilizing electrically non-conducting condensed aerosol fire extinguishants for which there are sufficient data currently available to enable validation of performance characteristics by an appropriate independent authority. Local applications of condensed aerosol extinguishing systems are not covered by this document. Any local applications require a pre-engineered and pre-designed system which has been tested and approved for a specific application by a relevant authority.
- Status
- Published
- Publication Date
- 24-Aug-2026
- Technical Committee
- ISO/TC 21/SC 8 - Gaseous media and firefighting systems using gas
- Drafting Committee
- ISO/TC 21/SC 8/WG 10 - Condensed aerosol fire extinguishing systems
- Current Stage
- 6060 - International Standard published - 60 Publication
- Start Date
- 25-Aug-2026
- Due Date
- 28-Jul-2026
- Completion Date
- 28-Jul-2026
ISO 15779:2026 is an International Standard from ISO for condensed aerosol fire extinguishing systems. It specifies requirements and test methods for components, system design, installation, maintenance and safety for total flooding systems using electrically non-conducting condensed aerosol fire extinguishants. It is written for the people who design, approve, install, test and maintain these systems in buildings, plants and other enclosed hazards.
What does ISO 15779:2026 specify?
ISO 15779:2026 sets the scope, terminology, safety limits, extinguishant concentration rules, system design rules, commissioning checks, and ongoing inspection and maintenance requirements for condensed aerosol fire extinguishing systems. It applies to total flooding systems for enclosed spaces and excludes local applications.
The document is organized into nine clauses and four annexes.
| Annex | What it covers |
|---|---|
| Annex A | Documentation requirements, including working documents for design and approval |
| Annex B | Toxicity and visibility testing guidance |
| Annex C | Test methods for condensed aerosol generators |
| Annex D | Extinguishing density and coverage test procedure |
What are the key requirements of ISO 15779:2026?
ISO 15779:2026 focuses on competent design, safe use, verified extinguishing performance, and documented acceptance and maintenance. In practice, the standard makes sure the system is chosen for the right hazard, installed with the right clearances and controls, and kept serviceable over time.
Use limits and safety boundaries
Clause 4 limits use to hazards where condensed aerosol is suitable, mainly surface Class A fires and Class B fires in enclosed spaces. It also says the system should not be used on certain reactive, oxidizing or pyrophoric fuels unless relevant testing has been accepted by the relevant authority.
Clause 4 also requires bonding and earthing to reduce electrostatic discharge risk, and it warns that explosive atmospheres need specific listing and approval. For users, this means the agent and the protected hazard must be checked together before the system is selected.
Design, documentation and approval
Clause 7 requires specifications to be prepared under the supervision of someone experienced in aerosol extinguishing system design, with approval where appropriate from the relevant authority. The required working documents are listed in Annex A and include location drawings, hazard descriptions, calculations, venting information and detection, actuation and control details.
This matters because the standard treats the design package as part of the system. The installer and owner need a clear, approved basis for the installed arrangement, not just a product list.
Extinguishing performance and system sizing
Clause 6 sets out design application density requirements, fire-class-based sizing, generator performance requirements and marking. ISO 15779:2026 uses extinguishing density, safety factor and design application density as the basis for system design, and it relies on test methods in Annex D to determine those values for specific fuels and hazards.
Clause 7 also requires the hold time to be long enough for effective emergency action, and it states a minimum hold time of 10 min unless otherwise specified by the standard of reference. In practice, this means the enclosure must retain the extinguishing condition long enough for shutdown, evacuation and response.
Generator selection, placement and operating conditions
Clause 7 requires the designer to consider enclosure venting, leakage, generator size and quantity, mounting location, protected height limits and multiple-generator arrangements. Where more than one generator is needed, the standard prefers generators from the same family and type, and asks for a rationale if that is not possible.
The document also ties operation to the manufacturer’s declared temperature, humidity and vibration ranges. That matters because the system must work under the actual conditions of the protected space, not just in ideal test conditions.
Commissioning and acceptance
Clause 8 requires enclosure checks, review of design calculations, review of mechanical and electrical components, preliminary functional tests and a system functional operational test. It also covers remote monitoring, control panel power supply checks, and completion documentation.
For the user, this is the point where the installed system is confirmed against the approved design before it is put into service.
Inspection, maintenance and training
Clause 9 requires regular inspection, maintenance and training for people who inspect, test, maintain or operate the system. It also requires record keeping, visual checks of aerosol generator assemblies and checks on enclosure integrity and pressure relief devices.
This is important because aerosol systems can be disabled by tampering, leakage, expiry or damaged components even when they were originally installed correctly.
What terms does ISO 15779:2026 define?
- condensed aerosol - An extinguishing medium of very fine solid particles suspended in gas and generated by combustion of a solid aerosol-forming compound.
- aerosol generator - A non-pressurized container that produces the condensed aerosol extinguishing agent when activated.
- design application density - The extinguishing density multiplied by the safety factor, used as the design value.
- extinguishing density - The minimum mass of discharged agent per unit enclosure volume needed to extinguish a fire under defined test conditions.
- hold time - The period during which the agent must keep at least the extinguishing density throughout the protected volume.
- system discharge time - The time from the first generator activation until the last generator finishes discharging for the protected volume.
- total flooding system - A firefighting system arranged to discharge extinguishant into an enclosed space to reach the required design application density.
- system isolate switch - A manual switch that prevents electrical actuation of the generators and gives an alarm of system isolation.
Who uses ISO 15779:2026?
ISO 15779:2026 is used by fire protection engineers, system designers, installers, commissioning technicians, maintenance contractors, manufacturers and approval authorities. It is also relevant to building owners and users who are responsible for operation and for keeping performance consistent with the manufacturer’s instructions.
Typical applications include electrical and electronic equipment rooms, telecommunications facilities and flammable or combustible liquid hazards in enclosed spaces. It is also used by test and certification organizations that evaluate generator performance, marking and environmental resistance.
What changed in ISO 15779:2026 from the previous edition?
ISO 15779:2026 is the second edition and replaces ISO 15779:2011. The changes stated in the document are:
- a requirement was added for Class B fires concerning the time to reach minimum design density from the start of discharge
- Clause C.12, the impact test, was removed
- the wood crib test preburn time in D.6.1.3.2 was changed from 6 min to 2 min
- figures were updated for clarity
- the bibliography no longer cites ISO 14520-1 and now adds the ATEX Directive reference
Which standards are used with ISO 15779:2026?
- ISO 3941 - Provides the fire classification used throughout the document for Class A and Class B fire references.
- EN 60068-2-6 - Provides the vibration test method used in Annex C for generator vibration resistance.
- EN 60068-2-30 - Provides the damp heat cyclic test method used in Annex C for humidity-related environmental testing.
What does the ISO 15779:2026 document contain?
ISO 15779:2026 contains the full set of clauses needed to specify, test and maintain condensed aerosol fire extinguishing systems, from use limits through to training. Clause 4 covers use and limitations, including activation devices, temperature limits and compatibility with other extinguishants.
Clause 5 covers safety topics such as toxicity, reduced visibility, turbulence, thermal hazards, electrical hazards and earthing, including Table 1 for electrical clearances. Clause 6 sets the concentration framework and generator marking requirements.
Clause 7 gives the design and approval framework, including enclosure venting, total flooding quantity, leakage, generator sizing, hold time, discharge, detection and alarms. Clause 8 covers commissioning and acceptance tests, while Clause 9 covers inspection, maintenance, testing and training.
Annex B gives guidance on toxicity and visibility assessment, including a flowchart, a visibility table and a visual-range formula. Annex C provides the generator test methods, and Annex D gives detailed fire test arrangements, instrumentation layouts, and procedures for distribution verification, extinguishing density and hold time determination.
Relations
- Effective Date
- 29-Oct-2022
Get Certified
Connect with accredited certification bodies for this standard
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Kmetijski inštitut Slovenije
Agricultural Institute of Slovenia. Soil testing, plant health, agricultural product analysis.
Sponsored listings
Frequently Asked Questions
ISO 15779:2026 is a standard published by the International Organization for Standardization (ISO). Its full title is "Condensed aerosol fire extinguishing systems — Requirements and test methods for components and system design, installation and maintenance — General requirements". This standard covers: This document specifies the requirements and test methods for components of condensed aerosol firefighting systems. It gives recommendations for the design, installation, testing, maintenance and safety of these systems, as well as their application in buildings, plants or other structures. The characteristics of the extinguishants in the condensed aerosol firefighting systems are also specified, as well as the types of fire for which they are a suitable extinguishing medium. This document covers total flooding systems primarily related to buildings, plants and other specific applications, utilizing electrically non-conducting condensed aerosol fire extinguishants for which there are sufficient data currently available to enable validation of performance characteristics by an appropriate independent authority. Local applications of condensed aerosol extinguishing systems are not covered by this document. Any local applications require a pre-engineered and pre-designed system which has been tested and approved for a specific application by a relevant authority.
This document specifies the requirements and test methods for components of condensed aerosol firefighting systems. It gives recommendations for the design, installation, testing, maintenance and safety of these systems, as well as their application in buildings, plants or other structures. The characteristics of the extinguishants in the condensed aerosol firefighting systems are also specified, as well as the types of fire for which they are a suitable extinguishing medium. This document covers total flooding systems primarily related to buildings, plants and other specific applications, utilizing electrically non-conducting condensed aerosol fire extinguishants for which there are sufficient data currently available to enable validation of performance characteristics by an appropriate independent authority. Local applications of condensed aerosol extinguishing systems are not covered by this document. Any local applications require a pre-engineered and pre-designed system which has been tested and approved for a specific application by a relevant authority.
ISO 15779:2026 is classified under the following ICS (International Classification for Standards) categories: 13.220.10 - Fire-fighting. The ICS classification helps identify the subject area and facilitates finding related standards.
ISO 15779:2026 has the following relationships with other standards: It is inter standard links to ISO 15779:2011. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
ISO 15779:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- Introduction
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 aerosol generator
- 3.2 aerosol generator assembly
- 3.3 approved
- 3.4 authority
- 3.5 automatic
- 3.6 competent person
- 3.7 condensed aerosol
- 3.8 coolant
- 3.9 design application density
- 3.10 discharge time
- 3.11 effective mass
- 3.12 electrical activation device
- 3.13 electrical clearance
- 3.14 emergency hold device
- 3.15 extinguishing density
- 3.16 family of condensed aerosol generators
- 3.17 hold time
- 3.18 hot work
- 3.19 ignition device
- 3.20 inspection
- 3.21 listed
- 3.22 listing organization
- 3.23 location drawing
- 3.24 maintenance
- 3.25 manual
- 3.26 manufacturer
- 3.27 mass median aerodynamic diameter
- 3.28 monitoring
- 3.29 normally occupied area
- 3.30 normally unoccupied area
- 3.31 particulate concentration
- 3.32 release
- 3.33 safety factor
- 3.34 solid aerosol-forming compound
- 3.35 system discharge time
- 3.36 system isolate switch
- 3.37 thermal activation device
- 3.38 thermal clearance
- 3.39 total flooding system
- 3.40 unoccupiable area
- 3.41 user
- 4 Use and limitations
- 4.1 General
- 4.2 Aerosol agent description
- 4.3 Application
- 4.4 Activation device
- 4.5 Limitation of use
- 4.6 Electrostatic discharge
- 4.7 Potentially explosive atmosphere
- 4.8 Temperature limitations
- 4.9 Compatibility with other extinguishants
- 4.10 Environment
- 5 Safety
- 5.1 General
- 5.2 Toxicity
- 5.3 Reduced visibility
- 5.4 Turbulence
- 5.5 Thermal hazards
- 5.6 Safety precautions
- 5.7 Electrical hazards
- 5.8 Electrical earthing
- 5.9 Electrostatic discharge
- 6 Extinguishant concentrations
- 6.1 General
- 6.2 Design application density requirements
- 6.3 Aerosol generator performance requirements
- 6.4 Marking
- 7 Specifications, plans and approvals
- 7.1 Specifications
- 7.2 Enclosure
- 7.3 Total flooding quantity
- 7.4 Design application density adjustment
- 7.5 Unit size and quantity of aerosol generators
- 7.6 Operating conditions
- 7.7 Duration of protection
- 7.8 System discharge
Introduction
The firefighting systems covered in this document are designed to provide a supply of condensed aerosol extinguishing medium for the extinction of fire.
Several different methods for supplying condensed aerosol extinguishant to, and applying it at, the required point of discharge for fire extinction have been developed in recent years, and there is a need for dissemination of information on established systems and methods. This document has been prepared to meet this need.
The requirements of this document are made in the light of the best technical data known to the working group at the time of writing but, since a wide field is covered, it has been impracticable to consider every possible factor or circumstance that can potentially affect implementation of the recommendations. It has been assumed in the preparation of this document that the execution of its provisions is entrusted to people appropriately qualified and experienced in the specification, design, installation, testing, approval, inspection, operation and maintenance of systems and equipment, for whose guidance it has been prepared, and who can be expected to exercise a duty of care to avoid unnecessary release of extinguishant. It is important that the fire protection of a building or plant be considered as a whole. Condensed aerosol extinguishing systems form only a part, albeit an important part, of the available facilities. Their adoption does not remove the need to consider supplementary measures, such as the provision of portable fire extinguishers or other mobile appliances for first aid or emergency use, or to deal with special hazards. For many years, condensed aerosol extinguishants have been a recognized effective medium for the extinction of flammable liquid fires and fires in the presence of electrical and ordinary Class A hazards. However, it is important to note in the planning of comprehensive schemes that there can be hazards for which these mediums are not suitable, and in certain circumstances or situations there can be dangers in their use requiring special precautions.
Advice on these matters can be obtained from the appropriate manufacturer of either the extinguishant or the extinguishing system, or both. Information can also be sought from the appropriate fire authority, the health and safety authorities and insurers. In addition, reference should be made as necessary to other national standards and statutory regulations of the particular country.
International Standard ISO 15779:2026(en) Condensed aerosol fire extinguishing systems — Requirements and test methods for components and system design, installation and maintenance — General requirements
1 Scope
This document specifies the requirements and test methods for components of condensed aerosol firefighting systems. It gives recommendations for the design, installation, testing, maintenance and safety of these systems, as well as their application in buildings, plants or other structures. The characteristics of the extinguishants in the condensed aerosol firefighting systems are also specified, as well as the types of fire for which they are a suitable extinguishing medium. This document covers total flooding systems primarily related to buildings, plants and other specific applications, utilizing electrically non-conducting condensed aerosol fire extinguishants for which there are sufficient data currently available to enable validation of performance characteristics by an appropriate independent authority. Local applications of condensed aerosol extinguishing systems are not covered by this document. Any local applications require a pre-engineered and pre-designed system which has been tested and approved for a specific application by a relevant authority.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 3941, Classification of fires EN 60068-2-6, Environmental testing — Part 2-6: Tests — Test Fc: Vibration (sinusoidal) EN 60068-2-30, Environmental testing — Part 2-30: Tests — Test Db and guidance: Damp heat, cyclic (12 h + 12 h cycle)
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:
- ISO Online browsing platform: available at https:// www .iso .org/ obp
- IEC Electropedia: available at https:// www .electropedia .org/
3.1 aerosol generator
non-pressurized container that, when activated, generates a condensed aerosol (3.7) extinguishing agent
3.2 aerosol generator assembly
aerosol generator (3.1) with its mounting bracket
ISO 15779:2026(en)
3.3 approved
acceptable to a relevant authority (3.4) Note 1 to entry: In determining the acceptability of installations or procedures, equipment or materials, the authority can base acceptance on conformance to the appropriate standards.
3.4 authority
organization, office or individual responsible for approving equipment, installations or procedures
3.5 automatic
performing a function without the necessity of intentional human intervention
3.6 competent person
person who is suitably trained, qualified by knowledge and practical experience, and with the necessary instructions to enable the required system design, installation and maintenance
3.7 condensed aerosol
aerosol extinguishing agent extinguishant extinguishing medium consisting of finely divided solid particles, generally in the order of magnitude of microns in diameter suspended in gas which is generated and distributed by a combustion process of a solid aerosol-forming compound
3.8 coolant
heat-absorbing medium or process
3.9 design application density
extinguishing density multiplied by the safety factor, required for system design purposes Note 1 to entry: Extinguishing density is the actual concentration of aerosol in the test room.
Note 2 to entry: The extinguishing density and the design application density are expressed in g/m .
3.10 discharge time
time from the generator activation until the end of its discharge Note 1 to entry: Measured in s.
Note 2 to entry: The end of discharge is determined by the drop of the temperature (primary), sound (secondary) and visual indication if possible.
3.11 effective mass
mass of discharged extinguishant required to achieve the design application density within the protected volume within the specified system discharge time
3.12 electrical activation device
device which automatically operates via an electrical input and is arranged to initiate the aerosol-forming compound (3.34).
ISO 15779:2026(en)
3.13 electrical clearance
unobstructed air distance between the aerosol generator (3.1) components and unenclosed or uninsulated live electrical components not at ground potential
3.14 emergency hold device
device that prevents the electrical actuation (3.12) of aerosol generators (3.1)
3.15 extinguishing density
effective minimum mass of discharged extinguishant per unit of enclosure volume required to extinguish fire involving a specific fuel under defined experimental conditions, using a specific aerosol generator (3.1) type and size, excluding any safety factor
Note 1 to entry: Measured in g/m .
3.16 family of condensed aerosol generators
range of aerosol generators (3.1) designed with the same solid compound, the same kind of cooling device, discharge outlet, ignition device, layout and internal/external architecture, with variation in the mass of the solid compound
3.17 hold time
period of time during which an extinguishant is required to maintain at least the extinguishing density to ensure even distribution throughout the protected volume
3.18 hot work
grinding, welding, thermal cutting, oxygen cutting, thermal heating, oxygen heating and other related heatproducing or spark-producing operations
3.19 ignition device
device that is able to ignite the solid aerosol-forming compound (3.34)
3.20 inspection
visual examination to give reasonable assurance that the extinguishing system is fully operable and has not been activated or tampered with, and that there is no obvious physical damage or condition to prevent operation
3.21 listed
systems or components that are included in a list published by a listing organization
3.22 listing organization
internationally recognized fire protection system or components test and certification organization
3.23 location drawing
layout diagram of protected volume clearly indicating the as-installed location of all aerosol generator assemblies (3.2), controls, system isolate switch (3.36), emergency hold device (3.14), and associated components of the firefighting system
ISO 15779:2026(en)
3.24 maintenance
thorough check to give maximum assurance that the extinguishing system will operate as intended Note 1 to entry: Maintenance includes a thorough examination and any necessary repair or replacement of system components.
3.25 manual
requiring intentional intervention to accomplish a function
3.26 manufacturer
entity that manufactures a product or has a product designed or manufactured, and markets that product under its name or trademark
3.27 mass median aerodynamic diameter
MMAD particle size and distribution of any aerosol statistically, based on the weight and size of the particle, along with the geometric standard deviation
3.28 monitoring
supervision of the operating integrity of an electrical, mechanical, pneumatic or hydraulic control feature of a system
3.29 normally occupied area
area that is occupied by persons, under normal circumstances
3.30 normally unoccupied area
area not normally occupied by people, but which may be entered occasionally for brief periods
3.31 particulate concentration
concentration of the solid fraction of the aerosol in the protected space after system discharge at the design application density
Note 1 to entry: Measured in g/m .
Note 2 to entry: This information is necessary to assess the potential health effects of accidental exposure to the agent and the potential degree of visibility obscuration.
3.32 release
physical discharge or emission of extinguishant as a consequence of the aerosol generator’s actuation
3.33 safety factor
multiplier of the extinguishing density to determine the aerosol design application density
3.34 solid aerosol-forming compound
mixture of oxidant, combustible component and technical admixtures producing fire-extinguishing aerosol upon ignition
ISO 15779:2026(en)
3.35 system discharge time
time from the first generator activation until the end of the last generator discharge time to achieve the design application density within the protected volume Note 1 to entry: This time measurement is relevant to an extinguishing system of interconnected aerosol generators (3.1) intended to protect the same hazard.
3.36 system isolate switch
key-operated or dual mode switch manual device that prevents the electrical actuation (3.12) of aerosol generators by electrically isolating them from the released circuit Note 1 to entry: The actuation of this device provides an indication of system isolation and shall result in an audible and visual alarm of system impairment at the control panel.
Note 2 to entry: The intention is to prevent the discharge of agent into the hazard area when the system isolation switch device is activated.
3.37 thermal activation device
device which automatically operates at a rated temperature and is arranged for the activation of the solid aerosol-forming compound (3.34)
3.38 thermal clearance
minimum air distance between both a condensed aerosol (3.1) generator surface and its discharge ports and either personnel, any structure or components sensitive to the temperature developed by the generator during and following discharge
3.39 total flooding system
firefighting system arranged to discharge extinguishant into an enclosed space to achieve the appropriate design application density
3.40 unoccupiable area
area which cannot be occupied due to dimensional or other physical constrains EXAMPLE Shallow voids or cabinets.
3.41 user
entity for whom the system is designed, and who is responsible for operation and for ensuring the consistency of performance as described by the manufacturer and for following the legal regulation
4 Use and limitations
4.1 General
The design, installation, testing and maintenance of aerosol fire-extinguishing systems shall be performed by persons competent in this fire extinguishing system technology.
4.2 Aerosol agent description
4.2.1 Condensed aerosol
Condensed aerosol is an extinguishant consisting of finely divided solid particles, typically based on alkali metal salts, and gases mainly comprised of nitrogen, carbon dioxide, carbon monoxide and water vapour.
ISO 15779:2026(en) Condensed aerosol is self-generated by a combustion process of a solid aerosol-forming compound contained in a non-pressurized can, an aerosol generator. Aerosol generators also contain one or more actuation device(s) designed to ignite the aerosol-forming compound and can have various cooling arrangements to cool the aerosol prior to its release into a protected volume. The aerosol generating combustion process provides sufficient energy for a rapid discharge rate and efficient distribution of the aerosol. No stored propelling gas is required for the aerosol delivery. An aerosol generator has one or more discharge outlets and is normally placed inside the protected risk area. No piping is required.
4.2.2 Physical characteristics
Aerosols are electrically non-conductive media, which are suspended in the air in the protected volume. Being a suspension of fine solid particles in a gaseous medium, the aerosol is not a clean agent. Following the actuation of an aerosol generator, there is a period of time during which the aerosol remains suspended within the enclosure; if the enclosure is not ventilated, the aerosol suspension will eventually settle down, forming a dust-like residue.
4.2.3 Extinguishing mechanism
Condensed aerosols extinguish fires chemically, interfering with the flame chain reaction by chemically bonding to the reactive free radicals and physically, by cooling the seat of the fire. Both actions take place mainly on the surface of the aerosol particles, and as such, the finer the particles the more efficient the extinguishment.
4.3 Application
Aerosol extinguishants have been recognized as an effective media for the extinguishing of surface type Class A fires and Class B fires, as specified in ISO 3941. The hazards against which these systems offer protection, and any limitations on their use, shall be contained in the system manufacturer’s design manual. Total flooding fire-extinguishing systems are used primarily for protection against hazards located in enclosures or hazards with equipment that includes an enclosure to contain the extinguishant. The following are examples of such hazards, but the list is not exhaustive:
a) electrical and electronic equipment; b) telecommunications facilities; c) flammable and combustible liquids.
4.4 Activation device
4.4.1 General
The activation device is arranged to initiate the aerosol-forming compound. If the activation device is a complex device incorporating several components, all components shall be specified by the manufacturer.
4.4.2 Electrical activation device
The electrical activation device shall be capable of operating via an electrical input and arranged to initiate the aerosol-forming compound.
4.4.3 Thermal activation device
The thermal activation device shall be capable of operating at a rated temperature and arranged to initiate the aerosol-forming compound.
ISO 15779:2026(en)
4.4.4 Other methods of activation device
Any methods capable of initiating the aerosol-forming compound, other than 4.4.2 and 4.4.3, shall be specified by the manufacturer.
4.5 Limitation of use
The extinguishants referred to in this document shall not be used on fires involving the following fuels (list not exhaustive) unless relevant testing has been carried out to the satisfaction of the relevant authority:
a) mixtures containing oxidizing materials, such as sodium chlorate or sodium nitrate; b) chemicals capable of undergoing autothermal decomposition, such as some organic peroxides; c) reactive metals (such as sodium, potassium, magnesium, titanium and zirconium), reactive hydrides, or metal amides, some of which can react violently with some aerosol extinguishants; d) oxidizing agents such as nitric oxides and fluorine; e) pyrophoric materials such as white phosphorous or metallo-organic compounds.
4.6 Electrostatic discharge
The aerosol generating system shall be adequately bonded and earthed to minimize electrostatic discharge risk
4.7 Potentially explosive atmosphere
CAUTION — Aerosol extinguishing systems are intended for the types of fire for which they are a suitable extinguishing medium. The end user should consider the potential adverse effects of aerosol extinguishing agent discharge residue on sensitive equipment and other objects. Under certain conditions, the potential for explosive atmospheres can exist. Areas where such potential exists are classified as hazardous. Aerosol generators may be used in hazardous areas subject to the manufacturer obtaining the specific listings for such areas and approvals from the appropriate authorities having jurisdiction.
Where aerosol generators are used in a potentially explosive application, the suitability of the generator to the atmosphere for the determined lifetime shall be assessed. Thus, aerosol generators shall be constructed such that they do not cause fire or explosion when actuated.
4.8 Temperature limitations
All devices shall be designed for the service they will encounter and shall not readily be rendered inoperative or susceptible to accidental operation.
Devices shall function properly from −20 °C to +50 °C or at a temperature lower than −20 °C or higher than +50 °C as specified by the manufacturer and demonstrated by a test report from an accredited testing laboratory and with temperature testing within its scope. The temperature limitations shall be marked on the name-plate, and in the manufacturer’s instruction manual.
For condensed aerosols, special care shall be taken to determine the maximum ambient temperature at which the aerosol generator can be installed, without risk of actuation by temperature itself. Condensed aerosol generators shall not be employed at less than the minimum thermal clearance distances specified in the manufacturer’s instruction manual.
ISO 15779:2026(en)
4.9 Compatibility with other extinguishants
Systems employing the simultaneous discharge of aerosols and other extinguishants to protect the same enclosed space shall not be permitted.
4.10 Environment
When selecting an extinguishing system or agent to protect a hazard area, the effects of the agent on the environment shall be considered.
5 Safety
5.1 General
Any hazard to personnel created by the actuation and discharge of the condensed aerosol extinguishing system shall be considered in the design of the system with reference to the hazards associated with particular aerosol extinguishants. When selecting an aerosol extinguishant, careful consideration should be given to independent occupational health and safety data.
...