ISO/DIS 6182-13
(Main)Fire protection -- Automatic sprinkler systems
Fire protection -- Automatic sprinkler systems
Protection contre l'incendie -- Systèmes d'extinction automatiques de type sprinkler
General Information
Standards Content (sample)
DRAFT INTERNATIONAL STANDARD ISO/DIS 6182-13
ISO/TC 21/SC 5 Secretariat: ANSI
Voting begins on: Voting terminates on:
2004-07-29 2004-12-29
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION • МЕЖДУНАРОДНАЯ ОРГАНИЗАЦИЯ ПО СТАНДАРТИЗАЦИИ • ORGANISATION INTERNATIONALE DE NORMALISATION
Fire protection — Automatic sprinklers —Part 13:
Requirements and test methods for extended coverage
sprinklers
Protection contre l'incendie — Systèmes d'extinction automatiques du type sprinkler —
Partie 13: Prescriptions et méthodes d'essai des sprinklers couvrant une surface plus étendue que la normale
ICS 13.220.20In accordance with the provisions of Council Resolution 15/1993 this document is circulated in
the English language only.Conformément aux dispositions de la Résolution du Conseil 15/1993, ce document est distribué
en version anglaise seulement.To expedite distribution, this document is circulated as received from the committee secretariat.
ISO Central Secretariat work of editing and text composition will be undertaken at publication
stage.Pour accélérer la distribution, le présent document est distribué tel qu'il est parvenu du
secrétariat du comité. Le travail de rédaction et de composition de texte sera effectué au
Secrétariat central de l'ISO au stade de publication.THIS DOCUMENT IS A DRAFT CIRCULATED FOR COMMENT AND APPROVAL. IT IS THEREFORE SUBJECT TO CHANGE AND MAY NOT BE
REFERRED TO AS AN INTERNATIONAL STANDARD UNTIL PUBLISHED AS SUCH.IN ADDITION TO THEIR EVALUATION AS BEING ACCEPTABLE FOR INDUSTRIAL, TECHNOLOGICAL, COMMERCIAL AND USER PURPOSES, DRAFT
INTERNATIONAL STANDARDS MAY ON OCCASION HAVE TO BE CONSIDERED IN THE LIGHT OF THEIR POTENTIAL TO BECOME STANDARDS TO
WHICH REFERENCE MAY BE MADE IN NATIONAL REGULATIONS.© International Organization for Standardization, 2004
---------------------- Page: 1 ----------------------
ISO/DIS 6182-13
PDF disclaimer
This PDF file may contain embedded typefaces. In accordance with Adobe's licensing policy, this file may be printed or viewed but shall
not be edited unless the typefaces which are embedded are licensed to and installed on the computer performing the editing. In
downloading this file, parties accept therein the responsibility of not infringing Adobe's licensing policy. The ISO Central Secretariat
accepts no liability in this area.Adobe is a trademark of Adobe Systems Incorporated.
Details of the software products used to create this PDF file can be found in the General Info relative to the file; the PDF-creation
parameters were optimized for printing. Every care has been taken to ensure that the file is suitable for use by ISO member bodies. In the
unlikely event that a problem relating to it is found, please inform the Central Secretariat at the address given below.
Copyright noticeThis ISO document is a Draft International Standard and is copyright-protected by ISO. Except as permitted
under the applicable laws of the user's country, neither this ISO draft nor any extract from it may be
reproduced, stored in a retrieval system or transmitted in any form or by any means, electronic, photocopying,
recording or otherwise, without prior written permission being secured.Requests for permission to reproduce should be addressed to either ISO at the address below or ISO's
member body in the country of the requester.ISO copyright office
Case postale 56 CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Reproduction may be subject to royalty payments or a licensing agreement.
Violators may be prosecuted.
ii ISO 2004 – All rights reserved
---------------------- Page: 2 ----------------------
ISO/DIS 6182-13
Contents Page
Foreword .........................................................................................................................................................iv
Introduction.....................................................................................................................................................vi
1 Scope...................................................................................................................................................1
© ISO 2003 — All rights reserved iiiDRAFT 2004
---------------------- Page: 3 ----------------------
ISO/DIS 6182-13
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies
(ISO member bodies). The work of preparing International Standards is normally carried out through ISO
technical committees. Each member body interested in a subject for which a technical committee has been
established has the right to be represented on that committee. International organizations, governmental and
non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the
International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2.
The main task of technical committees is to prepare International Standards. Draft International Standards
adopted by the technical committees are circulated to the member bodies for voting. Publication as an
International Standard requires approval by at least 75 % of the member bodies casting a vote.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. ISO shall not be held responsible for identifying any or all such patent rights.
ISO 6182-13 was prepared by Technical Committee ISO/TC 21, Equipment for fire protection and fire fighting,
Subcommittee SC 5, Sprinkler and water spray extinguishing systems.This second/third/... edition cancels and replaces the first/second/... edition (), [clause(s) / subclause(s) /
table(s) / figure(s) / annex(es)] of which [has / have] been technically revised.
ISO 6182 consists of the following parts, under the general title Fire protection — Automatic sprinklers:
— Part 1: Requirements and test methods for sprinklers— Part 2: Requirements and test methods for wet alarm valves, retard chambers and water motor
alarms— Part 3: Requirements and test methods for dry pipe valves
— Part 4: Requirements and test methods for quick-opening devices
— Part 5: Requirements and test methods for deluge valves
— Part 6: Requirements and test methods for check valves
— Part 7: Requirements and test methods for early suppression fast response (ESFR) sprinklers
— Part 8: Requirements and test methods for pre-action dry alarm valves— Part 9: Requirements and test methods for water mist nozzles
— Part 10: Requirements and test methods for domestic sprinklers
— Part 11: Requirements and test methods for pipe hangers
— Part 12: Requirements and test methods for couplings for grooved end components for
steel pipe systems— Part 13: Requirements and test methods for extended coverage sprinklers
iv © ISO 2003 — All rights reserved
DRAFT 2004
---------------------- Page: 4 ----------------------
ISO/DIS 6182-13
All pressure data in this ISO Standard are given as gauge pressure in bar (1 bar = 0,1 MPa).
© ISO 2003 — All rights reserved vDRAFT 2004
---------------------- Page: 5 ----------------------
DRAFT INTERNATIONAL STANDARD ISO/DIS 6182-13
Fire protection — Automatic sprinklers —
Part 13:
Requirements and test methods for extended coverage
sprinklers
1 Scope
1.1 This part of ISO 6182 specifies performance requirements, test methods and marking requirements for
extended coverage spray sprinklers.1.2 These sprinklers are intended to provide control of fires in occupancies or portions of occupancies where
quantity and/or combustibility of contents is low such as in hotel rooms. Requirements and test methods for
extended coverage sprinklers for other occupancy hazards are in preparation.2 References
The following standards contain provisions which, though referenced in this text, constitute provisions of this
part of ISO 6182. At the time of publication, the editions indicated were valid. All standards are subject to
revision, and parties to agreements based on this part of ISO 6182 are encouraged to investigate the
possibility of applying the most recent editions of the standards indicated below. Members of IEC and ISO
maintain registers of currently valid International Standards.ISO 7-1:1982, Pipe threads where pressure-tight joints are made on the threads, Part 1: Designation,
Dimension and TolerancesISO 49:1983, Malleable cast iron fittings threaded to ISO 7-1
ISO 65:1981, Carbon steel tubes suitable for screwing in accordance with ISO 7-1
3 Definitions
3.1 General
3.1.1 Assembly load: The force exerted on the sprinkler body at 0 bar hydraulic pressure at the inlet.
3.1.2 Conductivity factor: A measure of the conductance between the sprinkler's heat responsive
0,5element and the fitting expressed in units of (m/s) .
3.1.3 Design load: The force exerted on the release element at the service load of the sprinkler.
3.1.4 Extended coverage sprinkler: A sprinkler having a specified area of coverage which is larger than
that of a conventional, spray, flat spray or sidewall sprinkler.0,5
3.1.5 Response time index: A measure of sprinkler sensitivity expressed as RTI = tu , where t is the
time constant of the heat responsive element in units of seconds, and u is the gas velocity expressed in
meters per second. RTI can be used in combination with the conductivity factor (C) to predict the response of
© ISO 2003 — All rights reserved 1DRAFT 2004
---------------------- Page: 6 ----------------------
ISO/DIS 6182-13
a sprinkler in fire environments defined in terms of gas temperature and velocity versus time. RTI has units of
0,5(m-s) .
3.1.6 Service load: The combined force exerted on the sprinkler body by the assembly load of the
sprinkler and equivalent force of a 12 bar (1,2 MPa) hydraulic pressure at the inlet.
3.1.7 Sprinkler: A thermosensitive device designed to react at a predetermined temperature by
automatically releasing a stream of water and distributing it in a specified pattern and quantity over a
designated area.3.1.8 Standard orientation: In the case of symmetrical heat responsive elements, standard orientation is
with the air flow perpendicular to both the axis of the waterway and the plane of the frame arms. In the case
of non-symmetrical heat responsive elements, standard orientation is with the air flow perpendicular to both
the waterway axis and the plane of the frame arms which produces the shortest response time.
3.1.9 Worst case (response) orientation: The orientation which produces the longest response time with
the axis of the sprinkler inlet perpendicular to the air flow.3.2 Type of sprinklers according to type of heat responsive element.
3.2.1 Fusible element sprinkler: A sprinkler that opens under the influence of heat by the melting of a
component.3.2.2 Glass bulb sprinkler: A sprinkler that opens under the influence of heat by the bursting of the glass
bulb through pressure resulting from expansion of the fluid enclosed therein.3.3 Types of extended coverage sprinklers
3.3.1 Pendent extended coverage sprinkler: An extended coverage sprinkler that is arranged in such a
way that the water stream is directed initially downwards against the distribution plate. This sprinkler has a
square area of coverage not exceeding 36 m with sprinkler spacings in 0,5 m increments. The maximum
spacing between sprinklers is 6,0 m.3.3.2 Sidewall extended coverage sprinkler: An extended coverage sprinkler giving a one-sided
(half-paraboloid) water distribution over a definite protection area. The axis of the sprinkler waterway may be
either horizontal or vertical. This sprinkler has an area of coverage not exceeding 36 m , with sprinkler
spacings in 0,5 m increments, with no dimension exceeding 7 m.3.3.3 Upright extended coverage sprinkler: An extended coverage sprinkler that is arranged in such a
way that the water stream is directed initially upwards against the distribution plate. This sprinkler has a
square area of coverage not exceeding 36 m with sprinkler spacings in 0,5 m increments. The maximum
spacing between sprinklers is 6,0 m.3.4 Special types of extended coverage sprinklers
3.4.1 Concealed extended coverage sprinkler: An extended coverage sprinkler fitted with a ceiling
cover plate with the sprinkler body and heat responsive element located above the plane of the ceiling.
3.4.2 Dry extended coverage sprinkler: A unit comprising an extended coverage sprinkler mounted at
the outlet of a special riser extension with a seal at the inlet end, which prevents water from entering the riser
until it is released by operation of the sprinkler.3.4.3 Flush extended coverage sprinkler: An extended coverage sprinkler of which all or part of the
body, including the shank thread, is mounted above the lower plane of the ceiling, but part of, or all of, the
heat responsive element is below the lower plane of the ceiling.2 © ISO 2003 — All rights reserved
DRAFT 2004
---------------------- Page: 7 ----------------------
ISO/DIS 6182-13
3.4.4 Recessed extended coverage sprinkler: An extended coverage sprinkler of which all or part of the
body, other than the shank thread, is mounted within a recessed housing.3.4.5 Coated extended coverage sprinkler: An extended coverage sprinkler which has a factory applied
coating for corrosion protection.4 Product consistency
It shall be the responsibility of the manufacturer to implement a quality control programme to ensure that
production continuously meets the requirements of this part of IS0 6182 in the same manner as the originally
tested samples.Every manufactured sprinkler shall pass a leak resistance test equivalent to a hydrostatic pressure of at least
30 bar (3,0 MPa) for at least 2 seconds.5 Product assembly
5.1 All extended coverage sprinklers shall be designed and manufactured in such a way that they cannot be
readily adjusted, dismantled or reassembled.5.2 An extended coverage sprinkler shall be constructed to effect closure of its water seat for extended
periods of time without leakage and to open as intended and release all parts from 0,34 bar (0,034 MPa) up to
the rated working pressure. The closure of the water seat shall not be achieved by the use of a dynamic o-
ring or similar seal (an o-ring or similar seal that moves during operation or is in contact with a component that
moves during operation.6 Requirements
6.1 General
Sprinklers shall comply with the requirements given in table 1.
Nominal flow constant, K Nominal thread size
0,5
(l/min/bar )
(inches)
(see 6.4.1)
80 ± 4 1/2
115 ± 6 3/4
160 ± 8 3/4
200 ± 10 3/4
Note: In some countries, the use of 1/2 inch threads for sprinklers having
0,5
nominal flow constants up to 160 l/min/bar is acceptable.
Table 1 — Dimensional requirements
6.1.1 All sprinklers shall be constructed so that a sphere of diameter 8 mm can pass through each water
passage in the sprinkler.6.1.2 Nominal thread sizes should be suitable for fittings threaded in accordance with ISO 7-1.
© ISO 2003 — All rights reserved 3DRAFT 2004
---------------------- Page: 8 ----------------------
ISO/DIS 6182-13
6.1.2.1 In some countries, the use of 1/2 inch threads for sprinklers having nominal flow constants up to 160
0,5l/min/bar is acceptable.
6.1.2.2 Special sprinklers may have larger thread sizes.
6.1.2.3 The dimensions of all threaded connections should conform to International Standards where applied.
National Standards may be used if International Standards are not applicable.6.2 Nominal operating temperatures (see 7.6)
The nominal operating temperature of sprinklers shall be as indicated in table 2. The nominal operating
temperatures of all other sprinklers shall be specified in advance by the manufacturer and verified in
accordance with 6.3. They shall be determined as a result of the operating temperature test (see 7.6.1).
Nominal operating temperatures shall be within the ranges specified in table 2.The nominal operating temperature that is to be marked on the sprinkler shall be that determined when the
sprinkler is tested in accordance with 7.6.1, taking into account the specifications of 6.3.
Values in degrees Celsius1 2
GLASS BULB SPRINKLERS
Nominal Liqud Color
Operating code
Temperature
57 Orange
68 Red
79 yellow
93 green
107 green
121 blue
141 blue
163 mauve
182 mauve
204 black
227 black
260 black
343 black
4 © ISO 2003 — All rights reserved
DRAFT 2004
---------------------- Page: 9 ----------------------
ISO/DIS 6182-13
3 4
FUSIBLE ELEMENT SPRINKLERS
Nominal Yoke arm
Operating color code
Temperature
57 to 77 uncolored
80 to 107 white
121 to 149 blue
163 to 191 red
204 to 246 green
260 to 302 orange
320 to 343 orange
Table 2 — Nominal operating temperature
6.3 Operating temperatures (see 7.6.1)
6.3.1 Extended coverage sprinklers, shall open within a temperature range of
X ± (0,035 X + 0,62) C
where X is the nominal operating temperature.
6.4 Water flow and distribution
6.4.1 Flow constant (see 7.10)
The flow constant, K, for sprinklers is given by the formula:
K = Q
0,5
P
where
P is the pressure in bars;
Q is the flow rate in liters per minute;
K-factor for the sprinklers defined in table 1 shall have the values given in table 1 when determined by the
test method of 7.10.© ISO 2003 — All rights reserved 5
DRAFT 2004
---------------------- Page: 10 ----------------------
ISO/DIS 6182-13
6.4.2 Water distribution (see 7.11)
6.4.2.1 To demonstrate the required coverage of the protected area allotted to it, the sprinkler shall pass the
tests specified in 7.11.6.4.2.2 Upright and pendent sprinklers shall be evaluated using one quadrant of the room as shown in figures
5 through 8. Sidewall sprinkler distributions shall be measured utilizing one half of the floor area as shown in
figures 9 through 14. In all cases, a space of 25 mm shall be maintained between all walls and pans.
6.4.2.3 Not more than one pan shall have a collection less than 0,6 mm/minute and it shall not have less than
0,2 mm/minute.6.4.2.4 The average collection of all the distribution pans for each test shall be a minimum of 1,6 mm/minute.
6.4.2.5 Sprinklers must meet all criteria when tested to the parameters shown in tables 3 and 4. Pendent or
upright sprinklers shall meet all criteria as shown in table 3. Sidewall sprinklers shall meet all criteria as
shown in table 4.6.4.2.6 Coated sprinklers shall be subjected to additional distribution tests if the coating is observed to deform
or deteriorate during the dynamic heating test of 6.15.Nominal Flow Nominal Room Deflector to Nominal Flow Rate
Constant, K Dimensions Ceiling Distance
0,5
(l/m/[bar] ) [width x length] (mm)
(l/min)
(m x m)
80 5,0 x 5,0 100 101,8
80 5,5 x 5,5 100 123,2
80 6,0 x 6,0 100 146,6
115 5,0 x 5,0 100 101,8
115 5,5 x 5,5 100 123,2
115 6,0 x 6,0 100 146,6
160 5,0 x 5,0 100 111,1
160 5,5 x 5,5 100 123,2
160 6,0 x 6,0 100 146,6
200 5,0 x 5,0 100 138,9
200 5,5 x 5,5 100 138,9
200 6,0 x 6,0 100 146,6
Table 3 — Distribution testing parameters for upright and pendent sprinklers
6 © ISO 2003 — All rights reserved
DRAFT 2004
---------------------- Page: 11 ----------------------
ISO/DIS 6182-13
Nominal Flow Nominal Room Deflector to Nominal Flow Rate
Constant, K Dimensions Ceiling Distance
0,5
(l/m/[bar] ) [width x length] (mm)
(l/min)
(m x m)
80 5,0 x 5,0 100 101,8
80 5,0 x 5,0 300 101,8
80 5,0 x 5,5 100 112,0
80 5,0 x 5,5 300 112,0
80 5,0 x 6,0 100 122,2
80 5,0 x 6,0 300 122,2
115 5,0 x 5,0 100 127,3
115 5,0 x 5,0 300 127,3
115 5,0 x 5,5 100 140,0
115 5,0 x 5,5 300 140,0
115 5,0 x 6,0 100 152,7
115 5,0 x 6,0 300 152,7
115 5,0 x 6,5 100 165,4
115 5,0 x 6,5 300 165,4
115 5,0 x 7,0 100 178,2
115 5,0 x 7,0 300 178,2
160 In Preparation In Preparation In Preparation
200 In Preparation In Preparation In Preparation
Table 4 - Distribution testing parameters for sidewall sprinklers
6.5 Function (see 7.5)
6.5.1 When tested in accordance with 7.5.1 to 7.5.4, the sprinkler shall open and, within 5 s after the release
of the heat responsive element, shall operate satisfactorily by complying with the requirements of 6.4.1. Any
lodgement of released parts shall be cleared within 10 s or the sprinkler shall then comply with the
requirement of 6.4.2. No lodgements are permitted in the 80 sprinklers tested. Lodgement is considered to
have occurred when one or more of the released parts lodge in the deflector frame assembly in such a way as
to cause failure to meet the water distribution requirement of 6.4.2 after 10 s.6.5.2 The deflector and its supporting parts shall not sustain significant damage as a result of the functional
test specified in 7.5.4 and shall meet the requirements of 6.4.2.6.5.3 In most instances, visual examination of the sprinkler will be sufficient to establish conformity with the
requirements of 6.5.1 and 6.5.2.© ISO 2003 — All rights reserved 7
DRAFT 2004
---------------------- Page: 12 ----------------------
ISO/DIS 6182-13
6.6 Strength of sprinkler body (see 7.3)
The sprinkler body shall not show permanent elongation of more than 0,2% between the load-bearing points
of the sprinkler body after being subjected to twice the service load as measured in 7.3.
The manufacturer shall specify the average and upper limit of the service load.6.7 Strength of release element (see 7.9)
6.7.1 When tested in accordance with 7.9.1 glass bulb elements shall
a) have an average strength of at least six times the average service; load; and
b) have a design strength lower tolerance limit (LTL) on the strength distribution curve of at least two times
the upper tolerance limit (UTL) of the service load distribution curve based on calculations with a degree
of confidence (y) of 0,99 for 99 percent of samples (P). Calculations will be based on Normal or Gaussian
Distribution except where other distribution can be shown to be more applicable due to manufacturing of
design factors. See Figure 21.6.7.2 Fusible heat-responsive elements in the ordinary temperature range shall be designed to
a) sustain a load of 15 times its design load corresponding to the maximum service load measured in 7.3;
for a period of 100h when tested in accordance with 7.9.2.1; orb) demonstrate the ability to sustain the design load when tested in accordance with 7.9.2.2.
6.8 Leak and hydrostatic strength (see 7.4.1)6.8.1 A sprinkler shall not show any sign of leakage when tested by the method specified in 7.4.1.
6.8.2 A sprinkler shall not rupture, operate or release any parts when tested by the method specified in 7.4.2.
6.9 Heat exposure (see 7.7)6.9.1 Glass bulb sprinklers There shall be no damage to the glass bulb element when the sprinkler is tested
by the method specified in 7.7.1.6.9.2 Uncoated sprinklers Sprinklers shall withstand exposure to increased ambient temperature without
evidence of weakness or failure, when tested by the method specified in 7.7.2.6.9.3 Coated sprinklers In addition to meeting the requirement of 6.10.2 in an uncoated version, coated
sprinklers shall withstand exposure to increased ambient temperatures without evidence of weakness or
failure of the coating, when tested by the method specified in 7.7.3.6.10 Thermal shock (see 7.8)
Glass bulb sprinklers shall not be damaged when tested by the method specified in 7.8. Proper operation
shall not be considered damage.8 © ISO 2003 — All rights reserved
DRAFT 2004
---------------------- Page: 13 ----------------------
ISO/DIS 6182-13
6.11 Corrosion (see 7.12)
6.11.1 Stress corrosion (see 7.12.1) When tested in accordance with 7.12.1, each sprinkler shall show no
cracks, delaminations or failures which could affect its ability to satisfy other requirements.
6.11.2 Sulfur dioxide corrosion (See 7.12.2) Coated and uncoated sprinklers shall be resistant to sulfur
dioxide saturated with water vapor when conditioned in accordance with 7.12.2. Following exposure, the
sprinklers shall be functionally tested at 0,35 bar (0,035 MPa) only in accordance with 6.5.1 and meet the
dynamic heating requirements of 6.15.2.6.11.3 Salt spray corrosion (see 7.12.3) Coated and uncoated sprinklers shall be resistant to salt spray
when conditioned in accordance with 7.12.3. Following exposure, the sprinklers shall be functionally tested at
0,35 bar (0,035 MPa) only in accordance with 6.5.1 and meet the dynamic heating requirements of 6.15.2.
6.11.4 Moist air exposure (see 7.12.4) Sprinklers shall be resistant to moist air exposure when tested in
accordance with 7.12.4. Following exposure, the sprinklers shall be functionally tested at 0,35 bar (0,035
MPa) only in accordance with 6.5.1 and meet the dynamic heating requirements of 6.15.2.
6.12 Coated sprinklers (see 7.13)6.12.1 Evaporation of wax and bitumen (see 7.13.1) Waxes and bitumens used for coating sprinklers shall
not contain volatile matter in sufficient quantities to cause shrinkage, hardening, cracking or flaking of the
applied coating. The loss in mass shall not exceed 5% of that of the original sample when tested by the
method in 7.13.1.6.12.2 Resistance to low temperatures (see 7.13.2) All coatings used for sprinklers shall not crack or flake
when subjected to low temperatures by the method in 7.13.2.6.12.3 Resistance to high temperature Coated sprinklers shall meet the requirements of 6.10.3.
6.13 Water hammer (see 7.15)Sprinklers shall not leak when subjected to pressure surges from 4 bar to 34 bar (0,4 to 3,4 MPa). They shall
show no signs of mechanical damage when tested in accordance with 7.15 and shall operate when
functionally tested to the requirements of 6.14.1.6.14 Dynamic heating (see 7.6.2)
6.14.1 Extended coverage sprinklers shall meet the RTI and C limits for fast response sensitivity sprinklers as
shown in figure 1 when tested in the standard orientation. For concealed, flush, and recessed sprinklers see
1/2 0,56.22. Sprinklers with C values below 0,5 (m/s) should be evaluated using C equal to 0,5 (m/s) . All RTI
values shall be calculated as in 7.6.2.3.6.14.2 Extended coverage sprinklers, when tested in the worst case orientation, shall have RTI values not
0,5exceeding 125 (m-s) or 250 percent of the average RTI in the standard orientation.
6.14.3 After exposure to the corrosion test described in 6.12.2, 6.12.3, and 6.12.4 sprinklers shall be tested in
the standard orientation as described in 7.6.2.1 to determine the post-exposure RTI. Each post-exposure RTI
value shall not exceed the limits shown in figure 1. In addition, the average RTI value shall not exceed 130%
of the pre-exposure average value. All post-exposure RTI values shall be calculated as in 7.6.2.3 using the
pre-exposure conductivity factor (C).© ISO 2003 — All rights reserved 9
DRAFT 2004
---------------------- Page: 14 ----------------------
ISO/DIS 6182-13
6.15 Resistance to heat (see 7.14)
Open sprinklers shall be resistant to high temperatures when tested in accordance with 7.14. After exposure,
the sprinkler shall not show visual deformation or breakage.6.16 Resistance to vibration (see 7.16)
Sprinklers shall be able to withstand the effects of vibration without deterioration when tested in accordance
with 7.16. After the vibration test of 7.16, sprinklers shall show no visible deterioration and shall meet the leak
resistance requirement of 6.8 and the functional test requirement of 6.5.1, at 0,35 Bar (0,035 MPa) only.
Test Gas Gas AppliedCondition Temperature Velocity Vacuum
Number ( C) (m/s) (mm Hg)
1 128 1,0 0,007
2 128 2,6 0,007
3 128 3,5 0,007
4 197 1,0 0,010
5 197 2,6 0,010
6 197 3,5 0,010
7 290 1,0 0,013
8 290 2,6 0,013
9 290 3,5 0,013
Table 5 - Plunge tunnel conditions for concealed, flush, and
recessed extended coverage sprinklers
Test Upright or Pendent Sidewall
Condition Maximum Operating Maximum Operating
Number Time Time
(sec) (sec)
1 34 44
2 19 24
10 © ISO 2003 — All rights reserved
DRAFT 2004
---------------------- Page: 15 ----------------------
ISO/DIS 6182-13
3 16 20
4 16 20
5 10 12
6 7 10
7 --- ---
8 --- ---
9 --- ---
Table 6 - Maximum operating times for fast response concealed, flush,
and recessed extended coverage sprinklers
6.17 Resistance to impact (see 7.17)
Extended coverage sprinklers shall have adequate strength to withstand impacts associated with handling,
transport and installation without deterioration of performance or reliability. These sprinklers shall show no
fracture or deformation, shall meet the leak resistance requirement of 6.8 and the functional test requirement
of 6.5.1, at 0,35 Bar (0,035 MPa) only, after the impact test of 7.17.6.18 Lateral discharge (see 7.18)
Extended coverage sprinklers shall not prevent the operation of adjacent sprinklers when tested in accordance
with 7.18.6.19 30 day leakage resistance (see 7.19)
Sprinklers shall not leak, sustain distortion or other mechanical damage when subjected to 20 bar (2 MPa)
water pressure for 30 days. Following completion of this 30 day test, all samples shall meet the leak
resistance requirements specified in 6.8. Examine all samples to verify that there is no evidence of distortion
or other mechanical damage.6.20 Vacuum resistance (see 7.20)
Sprinklers shall not exhibit distortion, mechanical damage or lea
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.