SIST-TS CLC/TS 50131-2-4:2005
(Main)Alarm systems - Intrusion systems -- Part 2-4: Requirements for combined passive infrared and microwave detectors
Alarm systems - Intrusion systems -- Part 2-4: Requirements for combined passive infrared and microwave detectors
Interim TS before EN status (draft expected August 2006) * D117/092: Standstill maintained
Alarmanlagen - Einbruchmeldeanlagen -- Teil 2-4: Anforderungen an Passiv-Infrarotdualmelder und Mikrowellenmelder
Systèmes d'alarme - Systèmes d'alarme intrusion -- Partie 2-4: Exigences pour détecteurs combinés infrarouges passifs et à micro-ondes
Alarmni sistemi – Sistemi za javljanje vloma – 2-4. del: Zahteve za kombinirane pasivne infrardeče in mikrovalovne javljalnike
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST-TS CLC/TS 50131-2-4:2005
01-februar-2005
$ODUPQLVLVWHPL±6LVWHPL]DMDYOMDQMHYORPD±GHO=DKWHYH]DNRPELQLUDQH
SDVLYQHLQIUDUGHþHLQPLNURYDORYQHMDYOMDOQLNH
Alarm systems - Intrusion systems -- Part 2-4: Requirements for combined passive
infrared and microwave detectors
Alarmanlagen - Einbruchmeldeanlagen -- Teil 2-4: Anforderungen an Passiv-
Infrarotdualmelder und Mikrowellenmelder
Systèmes d'alarme - Systèmes d'alarme intrusion -- Partie 2-4: Exigences pour
détecteurs combinés infrarouges passifs et à micro-ondes
Ta slovenski standard je istoveten z: CLC/TS 50131-2-4:2004
ICS:
13.310 Varstvo pred kriminalom Protection against crime
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
SIST-TS CLC/TS 50131-2-4:2005 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST-TS CLC/TS 50131-2-4:2005
---------------------- Page: 2 ----------------------
SIST-TS CLC/TS 50131-2-4:2005
TECHNICAL SPECIFICATION CLC/TS 50131-2-4
SPECIFICATION TECHNIQUE
TECHNISCHE SPEZIFIKATION August 2004
ICS 13.310
English version
Alarm systems - Intrusion systems
Part 2-4: Requirements for combined passive infrared and microwave
detectors
Systèmes d'alarme - Alarmanlagen -
Systèmes d'alarme intrusion Einbruchmeldeanlagen
Partie 2-4: Exigences pour détecteurs Teil 2-4: Anforderungen an Passiv-
combinés infrarouges passifs Infrarotdualmelder und Mikrowellenmelder
et à micro-ondes
This Technical Specification was approved by CENELEC on 2004-05-04.
CENELEC members are required to announce the existence of this TS in the same way as for an EN and to
make the TS available promptly at national level in an appropriate form. It is permissible to keep conflicting
national standards in force.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden,
Switzerland and United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2004 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. CLC/TS 50131-2-4:2004 E
---------------------- Page: 3 ----------------------
SIST-TS CLC/TS 50131-2-4:2005
CLC/TS 50131-2-4:2004 - 2 -
Foreword
This Technical Specification was prepared by the Technical Committee CENELEC TC 79, Alarm systems.
The text of the draft was submitted to the vote at the meeting of TC 79 in Madrid and was approved by
CENELEC as CLC/TS 50131-2-4 on 2004-05-04. Standstill is maintained.
The following date was fixed:
- latest date by which the existence of the TS (doa) 2004-11-04
has to be announced at national level
NOTE Latest date by which the TS has to be voted as EN: 2 years maximum after dav of TS.
---------------------- Page: 4 ----------------------
SIST-TS CLC/TS 50131-2-4:2005
- 3 - CLC/TS 50131-2-4:2004
Contents
Page
1 Scope.4
2 Normative references.4
3 Definitions and abbreviations .5
4 Functional requirements.7
4.1 Indication signals or messages .7
4.2 Detection .8
4.3 Operational requirements.9
4.4 Immunity of the individual technologies to incorrect operation.10
4.5 Tamper security.10
4.6 Electrical requirements.11
4.7 Environmental classification and conditions.12
5 Marking, identification and documentation.12
5.1 Marking and/or identification .12
5.2 Documentation .12
6 Testing.13
6.1 General test conditions.13
6.2 Basic detection test .14
6.3 Walk testing.15
6.4 Verification of detection performance.16
6.5 Switch-on delay, time interval between signals and indication of detection .18
6.6 Fault condition signals or messages: self tests.19
6.7 Immunity of individual technologies to incorrect operation.19
6.8 Tamper security.20
6.9 Electrical tests .22
6.10 Environmental classification and conditions.23
6.11 Marking, identification and documentation.24
Annex A (normative) Format of standard test magnets.26
Annex B (normative) General testing matrix.27
Annex C (normative) Walk test diagrams.29
Annex D (normative) Procedure for calculation of the average temperature difference
between the standard target and the background .32
Annex E (informative) Basic detection target for the basic test of detection capability .34
Annex F (informative) Calibration heat source and microwave reflector.35
Annex G (normative) Calibration of the standard walk test targets .36
Annex H (informative) Equipment for walk test velocity control.38
Annex J (informative) Immunity to visible and near infrared radiation:
notes on calibration of the light source .39
Annex K (informative) Immunity to microwave signal attenuation by fluorescent lights .40
Annex L (normative) List of small tools suitable for testing immunity of casing to attack.41
Annex M (informative) Test for resistance to re-orientation of adjustable mountings .42
Figure A.1 - Format of standard test magnets.26
Figure C.1 - Detection across the boundary, & effect of control adjustments .29
Figure C.2 - Detection within the boundary, & effect of control adjustments.29
Figure C.3 - High velocity and intermittent movement.30
Figure C.4 - Close-in detection.30
Figure C.5 - Significant range reduction .31
Figure G.1 – Calibration of microwave SWT .37
Figure K.1 – Immunity to fluorescent lamp interference.40
Table 1 - Indication signals or messages .7
Table 2 - General walk test velocity and attitude requirements.8
Table 3 - Tamper security requirements.11
Table 4 - Electrical requirements.11
Table 5 - Range of materials for masking tests.22
Table 6 - Environmental tests, operational .24
Table 7 - Environmental tests, endurance.24
---------------------- Page: 5 ----------------------
SIST-TS CLC/TS 50131-2-4:2005
CLC/TS 50131-2-4:2004 - 4 -
Introduction
This Technical Specification is a specification for combined passive infrared and microwave detectors (to
be referred to here as the combined detector) used as part of intrusion detection systems installed in
buildings. It includes four security grades and the first three environmental classes.
The purpose of the combined detector is to detect the broad spectrum infrared radiation emitted by an
intruder and, at the same time, to emit microwave radiation over the area being protected, and analyse
signals that are returned. An intrusion signal or message is only generated when both technologies
register a positive indication of the presence of an intruder, thus reducing incorrect operation. The
combined detector shall provide the necessary range of signals or messages to be used by the rest of the
intrusion detection system.
The number and scope of these signals or messages will be more comprehensive for systems that are
specified at the higher grades.
If a combined detector can be operated in each technology individually, it shall also meet the grade
dependent requirements of the standards having relevance to those technologies.
This specification is only concerned with the requirements and tests for the detector. Other types of
detector are covered by other documents identified as CLC/TS 50131-2-x.
The requirement in EN 50131-1 that detectors in grade 3 and 4 systems shall include a means to detect a
significant reduction in range may be met either by detectors having the appropriate function (4.2.3) or by
suitable system design.
1 Scope
This Technical Specification provides for security grades 1 to 4 (see EN 50131-1), specific or non-specific
wired or wire-free combined passive infrared and microwave detectors, and is covered by environmental
classes I to III (see EN 50130-5).
A function designated in the specification as not required for a particular grade may be provided by the
manufacturer. If provided, it will be tested, and shall meet all relevant requirements of any higher grade. If
it passes, the manufacturer may claim it as an extra feature, which does not alter the overall grading of the
detector.
The specification does not apply to system interconnections.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 50130-4:1995 Alarm systems - Part 4: Electromagnetic compatibility - Product family standard:
Immunity requirements for components of fire, intruder and social alarm
systems
EN 50130-5:1998 Alarm systems - Part 5: Environmental test methods
EN 50131-1:1997 Alarm Systems - Intrusion systems - Part 1: General requirements
EN 50131-6:1997 Alarm systems - Intrusion systems - Part 6: Power supplies
EN 60529:1991 Degree of protection provided by enclosures (IP code)
---------------------- Page: 6 ----------------------
SIST-TS CLC/TS 50131-2-4:2005
- 5 - CLC/TS 50131-2-4:2004
3 Definitions and abbreviations
For the purpose of this specification. the following definitions and abbreviations apply in addition to those
given in EN 50131-1:
3.1
alert/set mode
state of operation in which a detector will generate an intrusion signal in response to stimulation by a
human being or a standard target
3.2
basic detection target
heat source and/or microwave reflector designed to verify the operation of a detector
3.3
ceiling mount detector
detector capable of sensing human movement from a mounting position on the ceiling
3.4
combined passive infrared and microwave detector
detector of the broad-spectrum infrared emitted by a human being, with an active microwave emitter and
detector installed in the same casing
3.5
curtain detector
detector capable of sensing human movement through a continuous layer of detection zones
3.6
incorrect operation
physical condition that causes an inappropriate signal from a detector
3.7
local memory
storage medium situated on board the detector, and having the capability to record signals or messages
generated by the detector
3.8
long range detector
detector capable of sensing human movement in an extended field of view with horizontal angular
coverage less than 10°
3.9
masking
interference with the detector input capability by the introduction of a physical barrier such as metal,
plastic, paper or sprayed paints or lacquers in close proximity to the detector
3.10
microwave detector
detector having an active microwave emitter and detector installed in the same casing
3.11
passive infrared detector
detector of the broad-spectrum infrared radiation emitted by a human being
3.12
simulated walk test target
non-human or synthetic heat source or microwave reflector designed to simulate the standard walk test
target
---------------------- Page: 7 ----------------------
SIST-TS CLC/TS 50131-2-4:2005
CLC/TS 50131-2-4:2004 - 6 -
3.13
standard walk test target
human being of standard weight and height clothed in close fitting clothing appropriate to the simulation of
an intruder
3.14
standby/unset mode
state of operation in which a detector is not required to generate an intrusion signal or message in
response to stimulation by a human being or a standard target
NOTE For environmental reasons, the microwave emitter may be switched off.
3.15
test mode
state of operation in which a detector will activate an intrusion indicator in response to stimulation by a
human being or a standard walk test target
3.16
volumetric detector
detector capable of sensing human movement in a volume such as a room with a field of view with
horizontal angular coverage greater than 45°
3.17
walk test
operational test during which a detector is stimulated by the standard walk test target in a controlled
environment
3.18
walk test attitude, crawling
crawling attitude shall consist of the standard walk test target moving with hands and knees in contact with
the floor
3.19
walk test attitude, upright
upright attitude shall consist of the standard walk test target standing and walking with arms held at the
sides of the body. The standard walk test target begins and ends a traverse with feet together
3.20
wire free detector
detector connected to the control & indicating equipment by non-physical means such as radio frequency
signals
3.21 Abbreviations
HDPE high density polyethylene
PIR passive infrared
EMC electromagnetic compatibility
SWT standard walk test target
BDT basic detection target
FOV field of view
---------------------- Page: 8 ----------------------
SIST-TS CLC/TS 50131-2-4:2005
- 7 - CLC/TS 50131-2-4:2004
4 Functional requirements
4.1 Indication signals or messages
All detectors shall have an alert/set mode. Grades 3 and 4 shall have an unset mode. If a detector has
only one mode of operation, then it shall always be in the alert/set mode. Tamper detection shall be active
in all modes.
Each possible mode of operation is determined by the status of the intrusion detection system with which
the detector communicates. The detector signals or messages in these modes of operation shall function
in accordance with Table 1. All signals or messages apply to all modes of operation unless stated
otherwise. Where a memory display is provided on board the detector, it shall not function in the alert/set
mode.
Table 1 - Indication signals or messages
Event Grades Intrusion signal or Tamper signal or Fault signal or
message message message
Intrusion 1 – 4 Required * Not permitted Not permitted
1 – 4 Not permitted Not permitted Not permitted
No stimulus
Masking 1 – 2 Not required Not required Not required
3 – 4 Required ** Not required Required **
Tamper 1 – 4 Not required Required Not required
1 – 2 Not required Not required Not required
Low supply voltage (external)
3 – 4 Not required Not required Required
Total loss of external power 1 Not required Not required Not required
supply
2 – 4 Required Not required Not required
***
Local self test pass 1 – 4 Not permitted Not permitted Not permitted
1 – 2 Not permitted Not permitted Not required
Local self test fail
3 – 4
Not permitted Not permitted Required
Remote self test pass 1 – 2 Not permitted Not permitted Not permitted
3 – 4 Required Not permitted Not permitted
1 – 2
Not permitted Not permitted Not required
Remote self test fail
3 – 4 Not permitted Not permitted Required
* Not required in unset/standby mode: required in test mode.
** An independent masking signal or message may be provided instead.
*** Not required for bus systems.
NOTE For internal power supplies, see EN 50131-6.
---------------------- Page: 9 ----------------------
SIST-TS CLC/TS 50131-2-4:2005
CLC/TS 50131-2-4:2004 - 8 -
4.2 Detection
4.2.1 Detection performance
The combined detector shall generate an intrusion signal or message when the SWT or simulated walk
test target moves within the boundary for a distance of 3 m or across the manufacturer’s claimed
boundary of detection. An intrusion signal or message shall only be generated when both technologies
register a positive indication of the presence of an intruder.
The variety of velocities and attitudes are as specified in Table 2.
Table 2 - General walk test velocity and attitude requirements
Test Grade 1 Grade 2 Grade 3 Grade 4
Required Required Required Required
Detection at the boundary
Velocity (m/s) 1,0 1,0 1,0 1,0
Attitude Upright Upright Upright Upright
Detection within the boundary Required Required Required Required
Velocity (m/s) 0,3 0,3 0,2 0,1
Attitude Upright Upright Upright Upright
Not required Required Required Required
Detection at high velocity
Velocity (m/s) # 2,0 2,5 3,0
Attitude # Upright Upright Upright
Close-in detection performance (dist, m) 2,0 2,0 0,5 0,5
Velocity (m/s) 0,5 0,4 0,3 0,2
Attitude Upright Upright Crawling Crawling
Not required Not required Required Required
Intermittent movement detection
performance *
Velocity (m/s) # # 0,2 (1,0) 0,1 (1,0)
Attitude # # Upright Upright
Effect of control adjustments ** Not Required Required Required
Required
Velocity (m/s) # 0,3 0,2 0,1
Attitude # Upright Upright Crawling
Significant reduction of specified range Not required Not required Not required Not required
*** ***
Velocity (m/s) # # # (1,0) 1,0
Attitude # # # (Upright) Upright
* The intermittent movement shall consist of the SWT moving a distance of 1 m by taking two 0,2 (5) m steps (at 1,0 m/s),
pausing for 5 s then continuing until the SWT has left the area for a further 1 s.
** If means for continuous adjustment of detection sensitivity is provided, the effect of any setting shall be indicated with a
tolerance of less than 25 % of the maximum reading.
*** The means to detect a significant reduction in range may be met either by detectors having the appropriate function (4.2.3) or
by suitable system design.
# To test features that are not required in a particular grade, parameters from a higher grade shall be specified.
---------------------- Page: 10 ----------------------
SIST-TS CLC/TS 50131-2-4:2005
- 9 - CLC/TS 50131-2-4:2004
4.2.2 Indication of detection
An indicator shall be provided at the detector to indicate when detection causes an intrusion signal or
message. This indicator shall only have this function, shall not function in the event of power failure, and
be capable of being enabled/disabled. This operation shall only be performed locally after removal of the
cover or remotely at the control and indicating equipment.
4.2.3 Significant reduction of specified range
If the facility to detect reduction in specified range is provided, then range reduction along the
principal axis of detection of more than 50 % shall generate an alarm or fault signal or message
within a maximum period of 180 s, according to the requirements given in Table 2. The
requirements of 4.3.5 (self test) and 4.5.5 (resistance to masking) can provide range reduction
detection.
If additional equipment is required to detect significant reduction in range, reference shall be
made to the manufacturer’s documentation.
4.3 Operational requirements
4.3.1 Time interval between intrusion signals or messages
Wired detectors shall be able to provide an intrusion signal or message not more than 15 s after the end
of the preceding intrusion signal or message. Wire free detectors shall perform the same function in a
time as follows:
Grade 1: 300 s
Grade 2: 300 s
Grade 3: 30 s
Grade 4: 15 s
NOTE See EN 50131-1 for amendment.
4.3.2 Switch on delay
The detector shall meet all functional requirements within 180 s of the power supply reaching its nominal
voltage.
4.3.3 Fault condition signals
When a detector suffers a fault, a fault signal or message shall be generated in accordance with the
manufacturer's specification, and the provisions of Table 1.
4.3.4 Power supply faults
Detectors of all grades shall signal complete power failure according to the provisions of Table 1.
Additionally, detectors of grades 3 and 4 shall signal when the supply voltage moves below the
manufacturer’s specified range according to the provisions of Table 1.
4.3.5 Self tests
Grade 3 and grade 4 detectors shall monitor the function of the sensor and associated on-board signal
processing circuitry. A self test shall be performed under the control of the detector.
When a remote self test is initiated a signal or message shall be generated between 1 and 5 s later, and
shall be signalled within 5 s of that initiation. The test duration shall not exceed 10 s. After the test is
completed, the detector shall resume it’s previous state within 5 s. Fault indication requirements appear in
Table 1.
---------------------- Page: 11 ----------------------
SIST-TS CLC/TS 50131-2-4:2005
CLC/TS 50131-2-4:2004 - 10 -
Where normal operation of the detector is inhibited during a local test of function monitoring the inhibition
time shall be limited to a maximum of 15 s in a period of 1 h.
4.4 Immunity of the individual technologies to incorrect operation
The detector shall be considered to have sufficient immunity to incorrect operation if the following
requirements have been met. No intrusion signal or message shall be generated during the tests.
4.4.1 Immunity to air flow
The PIR component of the detector shall not generate an intrusion signal or message when air is blown
over the face of the detector.
4.4.2 Immunity to visible & near infrared radiation
The PIR component of the detector shall not generate an intrusion signal or message when visible and
near infrared radiation from a light source such as a car headlamp is directed on to the front window or
lens through a pane of glass.
4.4.3 Immunity to microwave signal interference by fluorescent lights
The microwave component of the detector shall not generate an intrusion signal or message due to the
operation of a fluorescent light source mounted nearby.
4.5 Tamper security
Tamper security requirements for each grade of detector are shown in Table 3.
4.5.1 Prevention of unauthorized access to the inside of the detector through covers and
existing holes
Access holes shall not allow interference with the operation of the detector by probing with commonly
available tools. Damage must not be caused that would be visible to a person with normal eyesight
viewing from a distance of 1 m with the detector illuminated at a level of 2 000 lux.
A tool shall be required to open the unit. All covers giving access to components which could affect
adversely the operation of the detector shall be fitted with a tamper detection device in accordance with
Table 3. A tamper signal or message shall be generated before access is gained with any tool.
4.5.2 Detection of removal from the mounting surface
A tamper detection device shall be fitted which signals a tamper if the detector is removed from the
mounting surface in accordance with Table 3. Mounting screws shall only be accessible from within the
unit. Operation of the device shall not be preventable by external means. This device shall activate before
access can be gained to it.
4.5.3 Resistance to re-orientation of adjustable mountings
Where the orientation of a detector can be adjusted, resistance to re-orientation of the mounting shall be
provided in accordance with Table 3.
The alignment of the boundary of detection shall not have changed by more than 5° due to a grade
dependent applied torque. Alternatively a tamper detection device shall signal before the alignment of the
boundary of detection has moved by 5°. One test arrangement is described in Annex M.
If a detector provides a means to adjust the orientation of its coverage pattern, the access to this means
shall be protected by a tamper detection device.
---------------------- Page: 12 ----------------------
SIST-TS CLC/TS 50131-2-4:2005
- 11 - CLC/TS 50131-2-4:2004
4.5.4 Immunity to magnetic field interference
It shall not be possible to inhibit any signalling devices with a magnet of grade dependent remanence,
according to Table 3. The form of standard magnets is described in Annex A.
4.5.5 Resistance to masking
Means shall be provided to detect inhibition of the operation of the detector by covering its sensing area
and sensor, in the unset mode. The maximum response time for the masking detection device shall be
180 s. Intrusion and fault signals or messages or a dedicated anti-masking signal or message shall be
generated. The signals or messages shall remain latched until restored. Grade dependency appears in
Table 3.
No anti-masking signal shall be generated by normal human movement at 1m/s at a distance greater than
1 m in the unset condition.
Table 3 - Tamper security requirements
Requirement Grade 1 Grade 2 Grade 3 Grade 4
Resistance to access to the inside Required Required Required Required
of the detector
Removal from the mounting Not required Required * Required Required
surface *
Not required Required Required Required
Resistance to reorientation
2 5 10
Applied torque (Nm)
Magnetic field Not required Required Required Required
0,15 0,3 1,2
Immunity (T)
Anti-masking capability Not required Not required Required Required
* Required for wire free detectors only.
4.6 Electrical requirements
These requirements do not apply to detectors having internal power supplies. For these detectors refer to
EN 50131-6. For a detector having an external power supply, the requirements appear in Table 4.
Table 4 - Electrical requirements
Test Grade 1 Grade 2 Grade 3 Grade 4
Required Required Required Required
Detector power consumption
Input voltage range and slow input Not required Required Required Required
voltage rise
Not required Requ
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.