Fire detection and fire alarm systems - Part 7: Smoke detectors - Point detectors using scattered light, transmitted light or ionisation

This European Standard specifies the requirements, test methods and performance criteria for point smoke detectors that operate using scattered light, transmitted light or ionization, for use in fire detection and fie alarm systems for buildings (see EN 54-1: 1996).
For other types of smoke detector, or for smoke detectors working on different principles, this standard should only be used for guidance.  Smoke detectors with special characteristics and developed for specific risks are not covered by this standard.

Brandmeldeanlagen - Teil 7: Rauchmelder - Punktförmige Melder nach dem Streulicht-, Durchlicht- oder Ionisationsprinzip

Diese Europäische Norm legt Anforderungen, Prüfverfahren und Leistungsmerkmale für punktförmige Rauchmelder fest, die nach dem Streulicht-, Durchlicht- oder Ionisationsprinzip arbeiten und die in Brandmeldeanlagen für Gebäude eingesetzt werden (siehe EN 54 1:1996). Diese Europäische Norm umfasst punktförmige Rauchmelder mit mehr als einem Rauchsensor, die nach diesem Prinzip arbeiten, zusätzliche Anforderungen und Prüfverfahren für derartige Melder sind im Anhang N aufgeführt.
Für andere Typen von Rauchmeldern oder für Rauchmelder, die nach anderen Prinzipien arbeiten, sollte die vorliegende Norm nur als Leitfaden angewendet werden. Rauchmelder mit speziellen Merkmalen, entwickelt für besondere Risiken, sind nicht Gegenstand dieser Norm.
ANMERKUNG   Einige Meldertypen enthalten radioaktive Werkstoffe. Die nationalen Anforderungen für den Schutz gegen ionisierende Strahlung sind in den Ländern unterschiedlich und werden deshalb in der vorliegenden Norm nicht festgelegt.

Systèmes de détection et d'alarme incendie - Partie 7: Détecteurs de fumée - Détecteurs ponctuels fonctionnant suivant le principe de la diffusion de la lumière, de la transmission de la lumière ou de l'ionisation

La présente norme européenne spécifie les exigences, les méthodes d'essais et les critères de performance des détecteurs ponctuels fonctionnant suivant le principe de la diffusion de la lumière, de la transmission de la lumière ou de l'ionisation, utilisés dans les systèmes de détection et d'alarme incendie installés dans les bâtiments (voir EN 54-1:1996). La présente norme européenne comprend les détecteurs ponctuels de fumée qui ont plus d’un capteur de fumée fonctionnant suivant ces principes ; les exigences complémentaires et les méthodes d’essai de ces détecteurs sont fournies dans l’Annexe N.
Pour d'autres types de détecteurs de fumée ou pour ceux fonctionnant sur des principes différents, il convient d’utiliser cette partie de la norme comme un guide. Les détecteurs de fumée possédant des caractéristiques particulières, conçus pour des risques spéciaux, ne sont pas couverts par la présente norme.
NOTE   Certains types de détecteurs contiennent des matières radioactives. Les exigences nationales de radioprotection variant d'un pays à l'autre, celles-ci ne sont pas spécifiées dans la présente norme.

Sistemi za odkrivanje in javljanje požara ter alarmiranje - 7. del: Dimni javljalniki - Točkovni javljalniki na principu sipanja svetlobe, prepuščene svetlobe ali ionizacije

General Information

Status
Not Published
Public Enquiry End Date
30-May-2011
Technical Committee
Current Stage
98 - Abandoned project (Adopted Project)
Start Date
07-Oct-2013
Due Date
12-Oct-2013
Completion Date
07-Oct-2013

Relations

Buy Standard

Draft
prEN 54-7:2011
English language
80 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
oSIST prEN 54-7:2011
01-maj-2011
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO'LPQLMDYOMDOQLNL
7RþNRYQLMDYOMDOQLNLQDSULQFLSXVLSDQMDVYHWOREHSUHSXãþHQHVYHWOREHDOL
LRQL]DFLMH
Fire detection and fire alarm systems - Part 7: Smoke detectors - Point detectors using
scattered light, transmitted light or ionisation
Brandmeldeanlagen - Teil 7: Rauchmelder - Punktförmige Melder nach dem Streulicht-,
Durchlicht- oder Ionisationsprinzip
Systèmes de détection et d'alarme incendie - Partie 7: Détecteurs de fumée - Détecteurs
ponctuels fonctionnant suivant le principe de la diffusion de la lumière, de la transmission
de la lumière ou de l'ionisation
Ta slovenski standard je istoveten z: prEN 54-7 rev
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
oSIST prEN 54-7:2011 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 54-7:2011

---------------------- Page: 2 ----------------------
oSIST prEN 54-7:2011


EUROPEAN STANDARD
DRAFT
prEN 54-7 rev
NORME EUROPÉENNE

EUROPÄISCHE NORM

March 2011
ICS 13.220.20 Will supersede EN 54-7:2000
English Version
Fire detection and fire alarm systems - Part 7: Smoke detectors
- Point detectors using scattered light, transmitted light or
ionisation
Systèmes de détection et d'alarme incendie - Partie 7: Brandmeldeanlagen - Teil 7: Rauchmelder - Punktförmige
Détecteurs de fumée - Détecteurs ponctuels fonctionnant Melder nach dem Streulicht-, Durchlicht- oder
suivant le principe de la diffusion de la lumière, de la Ionisationsprinzip
transmission de la lumière ou de l'ionisation
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 72.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland,
Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2011 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 54-7 rev:2011: E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 54-7:2011
prEN 54-7:2011 (E)
Contents Page
Foreword .6
1 Scope .8
2 Normative references .8
3 Terms and definitions .9
4 Requirements . 10
4.1 Compliance . 10
4.2 Operational reliability . 10
4.2.1 Individual alarm indication . 10
4.2.2 Connection of ancillary devices . 10
4.2.3 Monitoring of detachable detectors . 10
4.2.4 Manufacturer's adjustments . 10
4.2.5 On-site adjustment of response behaviour . 10
4.2.6 Protection against the ingress of foreign bodies . 11
4.2.7 Response to slowly developing fires. 11
4.2.8 Marking . 11
4.2.9 Data . 12
4.2.10 Additional requirements for software controlled detectors . 12
4.3 Nominal activation conditions/sensitivity . 14
4.3.1 Repeatability . 14
4.3.2 Directional Dependence . 14
4.3.3 Reproducibility . 14
4.4 Tolerance to supply voltage . 14
4.4.1 Variation in supply parameters . 14
4.5 Response delay (response time). 14
4.5.1 Air movement . 14
4.5.2 Dazzling . 14
4.6 Durability of reliability, temperature resistance: . 14
4.6.1 Dry heat (operational) . 14
4.6.2 Cold (operational) . 14
4.7 Durability of reliability, humidity resistance: . 15
4.7.1 Damp heat, steady state (operational) . 15
4.7.2 Damp heat, steady state (endurance) . 15
4.8 Durability of reliability, corrosion resistance: . 15
4.8.1 Sulphur dioxide (SO ) corrosion (endurance) . 15
2
4.9 Durability of reliability, vibration resistance: . 15
4.9.1 Shock (operational) . 15
4.9.2 Impact (operational). 15
4.9.3 Vibration, sinusoidal, (operational). 15
4.9.4 Vibration, sinusoidal (endurance) . 15
4.10 Durability of operational reliability, electrical stability: . 15
4.10.1 Electromagnetic Compatibility (EMC), Immunity tests (operational) . 15
4.11 Performance parameters under fire conditions: . 16
4.11.1 Fire sensitivity . 16
5 Tests . 17
5.1 General . 17
5.1.1 Atmospheric conditions for tests . 17
5.1.2 Operating conditions for tests . 17
5.1.3 Mounting arrangements . 17
5.1.4 Tolerances . 17
2

---------------------- Page: 4 ----------------------
oSIST prEN 54-7:2011
prEN 54-7:2011 (E)
5.1.5 Measurement of response value . 17
5.1.6 Provision for tests . 18
5.1.7 Test schedule . 19
5.2 Operational reliability: . 20
5.2.1 Individual alarm indication . 20
5.2.2 Connection of ancillary devices . 20
5.2.3 Monitoring of detachable detectors . 20
5.2.4 Manufacturer's adjustments . 20
5.2.5 On-site adjustment of response behaviour . 20
5.2.6 Protection against the ingress of foreign bodies . 20
5.2.7 Response to slowly developing fires . 20
5.2.8 Marking . 21
5.2.9 Data . 21
5.2.10 Additional requirements for software controlled detectors . 21
5.3 Nominal activation conditions/sensitivity . 21
5.3.1 Repeatability . 21
5.3.2 Directional dependence . 21
5.3.3 Reproducibility . 22
5.4 Tolerance to supply voltage . 22
5.4.1 Variation in supply parameters . 22
5.5 Response delay (response time) . 23
5.5.1 Air movement . 23
5.5.2 Dazzling . 24
5.6 Durability of reliability, temperature resistance: . 24
5.6.1 Dry heat (operational) . 24
5.6.2 Cold (operational) . 25
5.7 Durability of reliability, humidity resistance:. 26
5.7.1 Damp heat, steady state (operational) . 26
5.7.2 Damp heat, steady state (endurance) . 27
5.8 Durability of reliability, corrosion resistance: . 27
5.8.1 Sulphur dioxide (SO ) corrosion (endurance) . 27
2
5.9 Durability of reliability, vibration resistance: . 28
5.9.1 Shock (operational) . 28
5.9.2 Impact (operational) . 29
5.9.3 Vibration, sinusoidal, (operational) . 30
5.9.4 Vibration, sinusoidal (endurance) . 31
5.10 Durability of operational reliability, electrical stability: . 32
5.10.1 Electromagnetic Compatibility (EMC), Immunity tests (operational) . 32
5.11 Performance parameters under fire conditions: . 33
5.11.1 Fire sensitivity . 33
6 Evaluation of conformity . 35
6.1 General . 35
6.2 Initial type testing . 35
6.2.1 General . 35
6.2.2 Test samples . 36
6.2.3 Test reports . 36
6.3 Factory production control. 36
6.3.1 General . 36
6.3.2 General requirements . 37
6.3.3 Product specific requirements . 38
6.3.4 Initial inspection of factory and FPC . 39
6.3.5 Surveillance of FPC . 40
6.4 Procedure for modifications. 40
6.5 One-off products, pre-production products, prototypes and products produced in very
low quantities . 40
Annex A (normative) Smoke tunnel for response value measurements . 42
Annex B (normative) Test aerosol for response value measurements . 43
3

---------------------- Page: 5 ----------------------
oSIST prEN 54-7:2011
prEN 54-7:2011 (E)
Annex C (normative) Smoke measuring instruments . 44
C.1 Obscuration meter . 44
C.2 Measuring ionization chamber (MIC) . 45
C.2.1 General . 45
C.2.2 Operating method and basic construction . 45
C.2.3 Technical data . 47
Annex D (normative) Apparatus for dazzling test . 49
Annex E (informative) Apparatus for impact test . 50
Annex F (normative) Fire test room . 52
Annex G (normative) Smouldering (pyrolysis) wood fire (TF2) . 54
G.1 Fuel . 54
G.2 Hotplate . 54
G.3 Arrangement . 54
G.4 Heating rate . 55
G.5 End of test condition . 55
G.6 Test validity criteria . 55
Annex H (normative) Glowing smouldering cotton fire (TF3) . 56
H.1 Fuel . 56
H.2 Arrangement . 56
H.3 Ignition . 57
H.4 End of test condition . 57
H.5 Test validity criteria . 57
Annex I (normative) Flaming plastics (polyurethane) fire (TF4) . 58
I.1 Fuel . 58
I.2 Arrangement . 58
I.3 Ignition . 58
I.4 End of test condition . 58
I.5 Test validity criteria . 58
Annex J (normative) Flaming liquid (n-heptane) fire (TF5). 60
J.1 Fuel . 60
J.2 Arrangement . 60
J.3 Ignition . 60
J.4 End of test condition . 60
J.5 Test validity criteria . 60
Annex K (informative) Information concerning the construction of the smoke tunnel . 62
Annex L (informative) Information concerning the requirements for the response to slowly
developing fires . 64
Annex M (informative) Information concerning the construction of the measuring ionization
chamber . 68
Annex N (normative) Additional requirements and test methods for smoke detectors with more
than one smoke sensor . 70
N.1 General . 70
N.2 Measurement of the response value for smoke detectors with more than one smoke
sensor . 70
N.3 Assessment of sensor stability . 70
Annex O . 71
(normative) Test set-up for testing the protection against the effect of moving objects . 71
Annex P (normative) Apparatus open detector static object test . 73
Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU
Construction Products Directive (89/106/EEC) . 75
ZA.1 Scope and relevant characteristics . 75
4

---------------------- Page: 6 ----------------------
oSIST prEN 54-7:2011
prEN 54-7:2011 (E)
ZA.2 Procedures for the attestation of conformity of smoke detector for use in fire detection
and fire alarm systems for buildings . 77
ZA.2.1 System of attestation of conformity . 77
ZA.2.2 EC Certificate of conformity . 78
ZA.3 CE marking and labelling. 79

5

---------------------- Page: 7 ----------------------
oSIST prEN 54-7:2011
prEN 54-7:2011 (E)
Foreword
This document (prEN 54-7:2011) has been prepared by Technical Committee CEN/TC 72 “Fire detection and
fire alarm systems”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 54-7:2000.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive, see informative Annex ZA, which is an integral part of this document.
EN 54, Fire detection and fire alarm systems, consists of the following parts:
 Part 1: Introduction
 Part 2: Control and indicating equipment
 Part 3: Fire alarm devices – Sounders
 Part 4: Power supply equipment
 Part 5: Heat detectors – Point detectors
 Part 7: Smoke detectors – Point detectors using scattered light, transmitted light or ionization
 Part 10: Flame detector – Point detectors
 Part 11: Manual call points
 Part 12: Smoke detectors – Line detector using an optical light beam
 Part 13: Compatibility assessment of system components
 Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance
 Part 15: Point detectors using a combination of detected phenomena
 Part 16: Voice alarm control and indicating equipment
 Part 17: Short circuit isolators
 Part 18: Input/output devices
 Part 20: Aspirating smoke detectors
 Part 21: Alarm transmission and fault warning routine equipment
 Part 22: Line-type heat detectors
6

---------------------- Page: 8 ----------------------
oSIST prEN 54-7:2011
prEN 54-7:2011 (E)
 Part 23: Fire alarm devices – Visual alarms
 Part 24: Components of voice alarm systems – Loudspeakers
 Part 25: Components using radio links and system requirements
 Part 26: Carbon monoxide detectors – Point detectors
 Part 27: Duct smoke detectors
 Part 28: Non-resettable (digital) line type heat detectors
 Part 29: Multi-sensor
...