SIST EN IEC 61897:2021
(Main)Overhead lines - Requirements and tests for Aeolian vibration dampers (IEC 61897:2020)
Overhead lines - Requirements and tests for Aeolian vibration dampers (IEC 61897:2020)
IEC 61897:2020 is available as IEC 61897:2020 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.
IEC 61897:2020 applies to aeolian vibration dampers intended for single conductors or earth wires or conductor bundles where dampers are directly attached to each subconductor. The purchaser may adopt part(s) of this document when specifying requirements for cables different from those mentioned above (e.g. optical ground wires (OPGW), all dielectric self-supporting optical cables (ADSS)). In some cases, test procedures and test values are left to agreement between the purchaser and the supplier and are stated in the procurement contract. Annex A lists the minimum technical details to be agreed between purchaser and supplier. Throughout this document, the word “conductor” is used when the test applies to dampers for conductors or earth wires. This second edition cancels and replaces the first edition published in 1998. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) Consider, in addition to Stockbridge type aeolian vibration dampers, also spiral aeolian vibration dampers and elastomeric aeolian vibration dampers.
b) Consider the application of dampers on high temperature conductors, specifying additional high temperature tests in clamp slip tests.
c) Simplify the procedure of the damper effectiveness evaluation.
d) Introduce test at low temperature on fastener components such as break away bolts and conical spring washers.
e) Include figures showing the test arrangements for the main mechanical tests.
Key words: Overhead Lines, Aeolian Vibration Dampers
Freileitungen - Anforderungen und Prüfungen für Schwingungsdämpfer (IEC 61897:2020)
Lignes aériennes - Exigences et essais applicables aux amortisseurs de vibrations éoliennes (IEC 61897:2020)
IEC 61897:2020 est disponible sous forme de IEC 61897:2020 RLV qui contient la Norme internationale et sa version Redline, illustrant les modifications du contenu technique depuis l'édition précédente.
IEC 61897:2020 s'applique aux amortisseurs de vibrations éoliennes pour conducteurs uniques ou câbles de garde, ou aux faisceaux de conducteurs lorsque les amortisseurs sont directement reliés à chaque sous-conducteur. L'acheteur peut adopter un ou plusieurs fragments du présent document lors de la spécification d'exigences concernant des câbles différents de ceux mentionnés ci-dessus, par exemple les câbles de garde optiques (OPGW, Optical Ground Wire) ou les câbles optiques autoporteurs entièrement diélectriques (ADSS, All Dielectric Self-Supporting). Dans certains cas, les procédures et valeurs d'essai sont convenues entre l'acheteur et le fournisseur et sont indiquées dans le contrat d'approvisionnement. L'annexe A contient les informations techniques minimales à convenir entre l'acheteur et le fournisseur. Dans le cadre du présent document, le mot "conducteur" est utilisé lorsque l'essai s'applique aux amortisseurs pour conducteurs ou câbles de garde.
Nadzemni vodi - Zahteve in preskusi za dušilnike vetrnih vibracij (IEC 61897:2020)
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-januar-2021
Nadomešča:
SIST EN 61897:1999
Nadzemni vodi - Zahteve in preskusi za dušilnike vetrnih vibracij (IEC 61897:2020)
Overhead lines - Requirements and tests for Aeolian vibration dampers (IEC
61897:2020)
Freileitungen - Anforderungen und Prüfungen für Schwingungsdämpfer (IEC
61897:2020)
Lignes aériennes - Exigences et essais applicables aux amortisseurs de vibrations
éoliennes (IEC 61897:2020)
Ta slovenski standard je istoveten z: EN IEC 61897:2020
ICS:
29.240.20 Daljnovodi Power transmission and
distribution lines
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD EN IEC 61897
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2020
ICS 29.240.20 Supersedes EN 61897:1998 and all of its amendments
and corrigenda (if any)
English Version
Overhead lines - Requirements and tests for Aeolian vibration
dampers
(IEC 61897:2020)
Lignes aériennes - Exigences et essais applicables aux Freileitungen - Anforderungen und Prüfungen für
amortisseurs de vibrations éoliennes Schwingungsdämpfer
(IEC 61897:2020) (IEC 61897:2020)
This European Standard was approved by CENELEC on 2020-04-07. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2020 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 61897:2020 E
European foreword
The text of document 11/266/FDIS, future edition 2 of IEC 61897, prepared by IEC/TC 11 "Overhead
lines" was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2021-01-07
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2023-04-07
document have to be withdrawn
This document supersedes EN 61897:1998 and all of its amendments and corrigenda (if any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
Endorsement notice
The text of the International Standard IEC 61897:2020 was approved by CENELEC as a European
Standard without any modification.
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1 Where an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60050-466 1990 International Electrotechnical Vocabulary. - -
Chapter 466: Overhead lines
IEC 60888 1987 Zinc-coated steel wires for stranded - -
conductors
IEC 61284 1997 Overhead lines - Requirements and tests EN 61284 1997
for fittings
IEC 61854 - Overhead lines - Requirements and tests - -
for spacers
IEC 62567 2013 Overhead lines - Methods for testing self- EN 62567 2013
damping characteristics of conductors
ISO 1461 2009 Hot dip galvanized coatings on fabricated EN ISO 1461 2009
iron and steel articles - Specifications and
test methods
ISO 2859-1 1999 Sampling procedures for inspection by - -
attributes - Part 1: Sampling schemes
indexed by acceptance quality limit (AQL)
for lot-by-lot inspection
+ A1 2011 - -
ISO 2859-2 1985 Sampling procedures for inspection by - -
attributes - Part 2: Sampling plans
indexed by limiting quality (LQ) for
isolated lot inspection
ISO 3951-1 2013 Sampling procedures for inspection by - -
variables - Part 1: Specification for single
sampling plans indexed by acceptance
quality limit (AQL) for lot-by-lot inspection
for a single quality characteristic and a
single AQL
ISO 3951-2 2013 Sampling procedures for inspection by - -
variables - Part 2: General specification
for single sampling plans indexed by
acceptance quality limit (AQL) for lot-by-
lot inspection of independent quality
characteristics
ISO 9001 2015 Quality management systems - EN ISO 9001 2015
Requirements
IEC 61897 ®
Edition 2.0 2020-03
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Overhead lines – Requirements and tests for aeolian vibration dampers
Lignes aériennes – Exigences et essais applicables aux amortisseurs
de vibrations éoliennes
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.240.20 ISBN 978-2-8322-7800-0
– 2 – IEC 61897:2020 © IEC 2020
CONTENTS
FOREWORD . 4
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 7
4 General requirements . 7
4.1 Design . 7
4.2 Materials . 8
4.3 Mass, dimensions and tolerances . 8
4.4 Protection against corrosion . 8
4.5 Manufacturing appearance and finish . 8
4.6 Marking . 8
4.7 Installation instructions . 8
5 Quality assurance . 8
6 Classification of tests. 9
6.1 Type tests . 9
6.1.1 General . 9
6.1.2 Application . 9
6.2 Sample tests . 9
6.2.1 General . 9
6.2.2 Application . 9
6.2.3 Sampling, acceptance criteria . 9
6.3 Routine tests. 10
6.3.1 General . 10
6.3.2 Application and acceptance criteria . 10
6.4 Table of tests to be applied . 10
7 Test methods . 11
7.1 Visual examination . 11
7.2 Verification of dimensions, materials and mass . 11
7.3 Corrosion protection tests . 11
7.3.1 Hot dip galvanized components (other than messenger cable wires) . 11
7.3.2 Ferrous components protected from corrosion by methods other than
hot dip galvanizing . 12
7.3.3 Hot dip galvanized messenger cable wires . 12
7.4 Non-destructive tests . 12
7.5 Clamp slip test . 12
7.6 Breakaway bolt test . 13
7.7 Clamp bolt tightening test . 14
7.8 Attachment of weights to messenger cable test . 14
7.9 Attachment of clamp to messenger cable test . 15
7.10 Corona and radio interference voltage (RIV) tests . 15
7.11 Damper performance tests . 15
7.11.1 Performance test variants . 15
7.11.2 Damper characteristic test . 16
7.11.3 Damper effectiveness evaluation . 18
7.12 Damper fatigue test . 21
7.12.1 Test methods . 21
IEC 61897:2020 © IEC 2020 – 3 –
7.12.2 Swept frequency method . 21
7.12.3 Resonant frequency method . 21
7.12.4 Acceptance criteria . 22
7.12.5 Fatigue test method – for spiral aeolian vibration dampers (SVD) . 22
Annex A (normative) Minimum technical details to be agreed between purchaser and
supplier . 23
Annex B (informative) Examples of graphs relevant to damper characteristic test . 24
Annex C (normative) Wind power input curve . 25
Annex D (informative) Description of HT conductors as given in
CIGRE TB 695‑2017 [6] . 27
Bibliography . 28
Figure 1 – Test arrangement for longitudinal slip tests . 13
Figure 2 – Test arrangement for attachment of weights to messenger cable test . 15
Figure 3 – Test arrangement for attachment of clamp to messenger cable test . 15
Figure 4 – Test arrangement for damper characteristic test . 18
Figure 5 – Example of test rig for laboratory test of damper effectiveness . 18
Figure B.1 – Examples of graphs relevant to damper characteristic test (damper with
two resonant frequencies) . 24
Figure C.1 – Wind power input curve . 25
Table 1 – Tests on dampers . 10
Table 2 – Load criteria (for standard and high temperature conductors) . 13
Table 3 – Acceptance criteria . 17
– 4 – IEC 61897:2020 © IEC 2020
INTERNATIONAL ELECTROTECHNICAL COMMISSION
_____________
OVERHEAD LINES –
REQUIREMENTS AND TESTS FOR AEOLIAN VIBRATION DAMPERS
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61897 has been prepared by Technical Committee 11: Overhead
lines.
This second edition cancels and replaces the first edition published in 1998. This edition
constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) Consider, in addition to Stockbridge type aeolian vibration dampers, also spiral aeolian
vibration dampers and elastomeric aeolian vibration dampers.
b) Consider the application of dampers on high temperature conductors, specifying additional
high temperature tests in clamp slip tests.
c) Simplify the procedure of the damper effectiveness evaluation.
d) Introduce test at low temperature on fastener components such as break away bolts and
conical spring washers.
e) Include figures showing the test arrangements for the main mechanical tests.
IEC 61897:2020 © IEC 2020 – 5 –
The text of this standard is based on the following documents:
FDIS Report on voting
11/266/FDIS 11/273/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This document has been drafted in accordance with the ISO/IEC Directives, Part 2.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to
the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended
– 6 – IEC 61897:2020 © IEC 2020
OVERHEAD LINES –
REQUIREMENTS AND TESTS FOR AEOLIAN VIBRATION DAMPERS
1 Scope
This document applies to aeolian vibration dampers intended for single conductors or earth
wires or conductor bundles where dampers are directly attached to each subconductor.
The purchaser may adopt part(s) of this document when specifying requirements for cables
different from those mentioned above (e.g. optical ground wires (OPGW), all dielectric self-
supporting optical cables (ADSS)).
In some cases, test procedures and test values are left to agreement between the purchaser
and the supplier and are stated in the procurement contract.
Annex A lists the minimum technical details to be agreed between purchaser and supplier.
Throughout this document, the word “conductor” is used when the test applies to dampers for
conductors or earth wires.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their
content constitutes requirements of this document. For dated references, only the edition
cited applies. For undated references, the latest edition of the referenced document (including
any amendments) applies.
IEC 60050(466):1990, International Electrotechnical Vocabulary (IEV) – Chapter 466:
Overhead lines
IEC 60888:1987, Zinc-coated steel wires for stranded conductors
IEC 61284:1997, Overhead lines – Requirements and tests for fittings
IEC 61854, Overhead lines – Requirements and tests for spacers
IEC 62567:2013, Overhead lines – Methods for testing self-damping characteristics of
conductors
ISO 1461:2009, Hot dip galvanized coatings on fabricated iron and steel articles –
Specifications and test methods
ISO 2859-1:1999/AMD1:2011, Sampling procedures for inspection by attributes – Part 1:
Sampling schemes indexed by acceptable quality limit (AQL) for lot-by-lot inspection
ISO 2859-2:1985, Sampling procedures for inspection by attributes – Part 2: Sampling plans
indexed by limiting quality level (LQ) for isolated lot inspection
ISO 3951-1:2013, Sampling procedures for inspection by variables – Part 1: Specification for
single sampling plans indexed by acceptance quality limit (AQL) for lot-by-lot inspection for a
single quality characteristic and a single AQL
IEC 61897:2020 © IEC 2020 – 7 –
ISO 3951-2:2013, Sampling procedures for inspection by variables – Part 2: General
specification for single sampling plans indexed by acceptance quality limit (AQL) for lot-by-lot
inspection of independent quality characteristics
ISO 9001:2015, Quality management systems – Requirements
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60050-466 apply, as
well as the following.
ISO and IEC maintain terminological databases for use in standardization at the following
addresses:
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp
3.1
stockbridge-type aeolian vibration damper
device comprising a steel cable with a weight at each end and one bolted clamp or a helical rod
attachment, attachable to a conductor, for the purpose of damping aeolian vibration
3.2
spiral aeolian vibration damper
SVD
device made of helical plastic which wraps around the conductor for purposes of damping
aeolian vibration (these are commonly used on earth wires, OPGW and ADSS cables)
3.3
elastomeric aeolian vibration damper
device comprising suspended weights connected to elastomeric articulations and one bolted
clamp or a helical rod attachment, attachable to a conductor for the purpose of damping
aeolian vibration
3.4
high temperature conductors
HTC
conductors which are designed to have a maximum continuous operating temperature
over 95 °C
3.5
maximum continuous operating temperature
conductor temperature specified by the manufacturer and measured at the outer wire layers
4 General requirements
4.1 Design
The damper shall be designed so as to
– damp aeolian vibration;
– withstand mechanical loads imposed during installation, maintenance and specified
service conditions;
– avoid damage to the conductor under specified service conditions;
– be capable of being removed and re-installed without damage to the conductor;
– 8 – IEC 61897:2020 © IEC 2020
– be free from unacceptable levels of corona and radio interference under all service
conditions, when installed on phase conductors;
– be suitable for safe and easy installation. The clamp design shall retain all parts when
opened for attachment to conductor. Furthermore, the clamp design shall be such that the
damper, during installation, can be suspended on the conductor before tightening the
clamp;
– ensure that individual components will not become loose in service;
– maintain its function over the entire service temperature range;
– avoid audible noise;
– prevent water collection.
Other desirable characteristics which are not essential to the basic functions of the damper
but which may be advantageous include:
– verification of proper installation from the ground;
– easy installation and removal from energized lines.
In the case of vibration dampers for conductors or earth wires containing integral fibre optic
elements (or an externally applied optical cable wrapped around the earth wire) the possible
effects of the damper on these fibre optic elements should be accounted for.
4.2 Materials
The materials shall conform to the requirements of IEC 61284.
4.3 Mass, dimensions and tolerances
Damper mass and significant dimensions, including appropriate tolerances, shall be shown on
contract drawings.
4.4 Protection against corrosion
In addition to the applicable requirements of IEC 61284, the messenger cable (including cut
ends when exposed) shall be protected against corrosion, e.g. in accordance with IEC 60888
for hot dip galvanized steel wire.
4.5 Manufacturing appearance and finish
The dampers shall be free of defects and irregularities; they shall have all outside surfaces
smooth and all edges and corners well-rounded.
4.6 Marking
The fitting marking requirements of IEC 61284 shall be applied to all clamp assemblies
including those using breakaway bolts. On spiral dampers, the markings should be on the
plastic rod.
4.7 Installation instructions
The supplier shall provide a clear and complete description of the recommended installation
procedure including in-span positions.
5 Quality assurance
A quality assurance programme taking into account the requirements of this document can be
used by agreement between the purchaser and the supplier to verify the quality of the
vibration dampers during the manufacturing process.
IEC 61897:2020 © IEC 2020 – 9 –
Detailed information on the use of quality assurance is given in a system as per ISO 9001 or
similar.
It is recommended that test equipment used to verify compliance to this document is routinely
maintained and calibrated in accordance with a relevant quality standard.
6 Classification of tests
6.1 Type tests
6.1.1 General
Type tests are intended to establish design characteristics. They are normally made once and
repeated only when the design or the material of the damper components is changed. The
results of type tests are recorded as evidence of compliance with design requirements.
6.1.2 Application
Dampers shall be subjected to type tests as per Table 1.
Unless otherwise specified, each type test shall be performed on three test samples which are
identical in all essential respects with dampers to be supplied under contract to the purchaser.
All units shall pass the tests.
The dampers used for tests during which no damage occurs to the units or their components
may be used in subsequent tests.
6.2 Sample tests
6.2.1 General
Sample tests are required to verify that the dampers meet the performance specifications of
the type test samples. In addition, they are intended to verify the quality of material and
workmanship.
6.2.2 Application
Dampers shall be subjected to sample tests as per Table 1.
The samples to be tested shall be selected at random from the lot offered for acceptance. The
purchaser has the right to make the selection.
The dampers used for tests during which no damage occurs to the units or their components
may be used in subsequent tests.
6.2.3 Sampling, acceptance criteria
The sampling plan procedures according to ISO 2859-1 and ISO 2859-2 (inspection by
attributes) and ISO 3951 (inspection by variables) and the detailed procedures (inspection
level, AQL, single, double or multiple sampling, etc.) shall be agreed between the purchaser
and the supplier for each different attribute or variable.
NOTE Sampling inspection by variables is an acceptance sampling procedure to be used in place of inspection by
attributes when it is appropriate to measure on some continuous scale the characteristic(s) under consideration. In
the case of failure load tests and similar expensive tests, better distinction between acceptable quality and
objective quality is available with acceptance sampling by variables than by attributes for the same sample size.
– 10 – IEC 61897:2020 © IEC 2020
The purpose of the sampling process may also be important in the choice between a variables or attributes plan.
For example, a purchaser may choose to use an attributes acceptance sampling plan to assure that parts in a
shipment lot are within a required dimensional tolerance; the manufacturer may make measurements under a
variables sampling plan of the same dimensions because he is concerned with gradual trends or changes which
may affect his ability to provide shipment lots which meet the AQL.
6.3 Routine tests
6.3.1 General
Routine tests are intended to prove conformance of vibration dampers to specific
requirements and are made on every damper. The tests shall not damage the dampers.
6.3.2 Application and acceptance criteria
Whole lots of dampers may be subjected to routine tests. Any damper which does not conform
to the requirements shall be discarded.
6.4 Table of tests to be applied
The following Table 1 indicates the tests which shall be performed. These are marked with
an "X" in the table.
However, the purchaser may specify additional tests which are included in the table and
marked with an "O".
Units or components damaged during the test shall be excluded from the delivery to the
customer.
Table 1 – Tests on dampers
Subclause Test Type Sample Routine
test test test
7.1 Visual examination X X O
7.2 Verification of dimensions, materials and mass X X
7.3 Corrosion protection tests X X
7.4 Non-destructive tests O O O
7.5 Clamp slip test X O
7.6 Breakaway bolt test X X
7.7 Clamp bolt tightening test X X
7.8 Attachment of weights to messenger cable X X
7.9 Attachment of clamp to messenger cable test X X
1)
7.10 Corona and radio interference voltage (RIV) tests X
7.11 Damper performance tests
7.11.2 – Damper characteristic test X O
7.11.3 – Damper effectiveness evaluation X
7.12 Damper fatigue test X
1)
Not applicable for earth wire dampers.
• The supplier should state in the tender quality plan, or other tender documentation, which testing is
already complete (i.e. which type tests) and which tests (sample or routine) are included in the tender,
subject to the approval or change required by the purchaser.
• If conical washers are used on bolted clamps, embrittlement tests shall be performed in accordance with
clause 7.5.2.2 of IEC 61854:2019.
IEC 61897:2020 © IEC 2020 – 11 –
7 Test methods
7.1 Visual examination
Type tests shall include visual examination to ascertain conformity of the dampers in all
essential respects, with the manufacturing or contract drawings. Deviations from the drawings
shall be subject to the approval of the purchaser and shall be appropriately documented as an
agreed concession.
Sample tests and, if required, routine tests shall include visual examination to ensure
conformity of manufacturing process, shape, coating and surface finish of the damper with the
contract drawings. Particular attention shall be given to markings required and to the finish of
surfaces which come into contact with the conductor. The sample test procedure and
acceptance criteria shall be agreed between the purchaser and the supplier.
For dampers subjected to corona type test, the sample test shall include a comparison of
shape and surface finish with one of the corona type test samples when specified by the
purchaser.
7.2 Verification of dimensions, materials and mass
Type and sample tests shall include verification of dimensions to ensure that dampers are
within the dimensional tolerances stated on contract drawings. The purchaser may choose to
witness the measurement of selected dimensions or may inspect the supplier's documentation
when this is available.
Type and sample tests shall also include verification of materials to ensure that they are in
accordance with contract drawings and documents. This verification shall normally be carried
out by the purchaser inspecting the supplier's documentation relating to material
specifications, certificates of conformity or other quality documentation.
The total mass of the damper complete with all its components shall comply with the mass
shown on the contract drawing (within given tolerances).
7.3 Corrosion protection tests
7.3.1 Hot dip galvanized components (other than messenger cable wires)
Hot dip galvanized components other than messenger cable wires shall be tested in
accordance with the requirements specified in ISO 1461.
The coating thicknesses shall conform to Tables 3 and 4 of ISO 1461:2009, unless otherwise
agreed between purchaser and supplier. However, for the purpose of this document, Tables 3
and 4 in ISO 1461:2009 shall apply to the following categories of items (and not to the
categories specified in ISO 1461).
Table 3: Coating thickness on all samples except
– washers;
– threaded components;
– small parts which are centrifuged (significant surface area <1 000 mm ).
Table 4: Coating thickness on
– washers;
– threaded components;
– small parts which are centrifuged (significant surface area <1 000 mm ).
– 12 – IEC 61897:2020 © IEC 2020
7.3.2 Ferrous components protected from corrosion by methods other than hot dip
galvanizing
Ferrous components protected from corrosion by methods other than hot dip galvanizing shall
be tested in accordance with the requirements of relevant IEC/ISO standards agreed between
purchaser and supplier.
7.3.3 Hot dip galvanized messenger cable wires
Hot dip galvanized messenger cable wires shall be tested in accordance with the
requirements specified in IEC 60888.
7.4 Non-destructive tests
The purchaser shall specify or agree to relevant test methods (ISO or other) and acceptance
criteria. Examples of non-destructive tests are as follows:
– magnetic test;
– eddy current test;
– radiographic test;
– ultrasonic test;
– proof load test;
– dye penetrant test;
– hardness test.
7.5 Clamp slip test
The test shall be performed using the conductor for which the clamp is intended. The
conductor shall be "as new", i.e. free of any deterioration or damage. The minimum free
length of test conductor between its terminating fittings shall be 4 m. The conductor shall be
tensioned to 20 % of its rated tensile strength. Precautions shall be taken to avoid birdcaging
of the conductor.
The clamp shall be installed in accordance with the supplier's instructions on a different
portion of conductor for each test. In the case of breakaway bolts, the installation torque shall
be the nominal breakaway torque minus the specified tolerance (see 7.6).
The use of other conductors, or conductor lengths or tensions may be agreed between
purchaser and supplier.
By means of a suitable device a load coaxial to the conductor shall be applied to the damper
clamp, as indicated in Figure 1. The load shall be gradually increased (not faster than 100 N/s)
until it reaches the load given in Table 2 or the load agreed between purchaser and supplier.
This load shall be kept constant for 60 s. Then the load shall be gradually increased until
slippage of the clamp occurs. The value of slip load shall be recorded.
For the slip test conducted on High Temperature Conductors (HTC) using Stockbridge and
elastomeric dampers only, the parameters are the same as for standard conductors. After
installing the clamp at ambient temperature, the conductor shall be electrically heated up to
the maximum continuous operating temperature as specified by the conductor manufacturer
and kept constant at this temperature for 0,5 h. The conductor tension load shall be kept
constant at 20 % RTS. Then the slip test shall be performed at maximum continuous
operating temperature as described above.
For the type test, an additional thermal process of the conductor shall be performed.
IEC 61897:2020 © IEC 2020 – 13 –
A new clamp shall be fixed at ambient temperature on the conductor which is tensioned to 20 %
of RTS. It is permitted to fix several clamps on the same setup to reduce expenditure of time.
The distance between the clamps shall be at least 300 mm.
Then the conductor shall be electrically heated up to the maximum continuous operating
temperature as specified by the conductor manufacturer and kept constant at this temperature
for 1h.
Afterwards the temperature shall decrease to at least ambient temperature plus 5 °C. These
cycles shall be carried out four times. At the end of the fourth cycle, after decreasing the
temperature to ambient values the slip load test shall be performed. For the complete test run
the tension shall be kept constant at 20 % of rated tensile strength.
Clamp slip shall be considered as having occurred when a slip distance of 1 mm for bolted
clamps and 2,5 mm for helical attachments is measured.
Figure 1 – Test arrangement for longitudinal slip tests
Table 2 – Load criteria (for standard and high temperature conductors)
Specified minimum load/Maximum slip
Damper Conductor diameter Attachment Load Movement
kN mm
Stockbridge or
< 19 mm Bolted 1,25 1,0
Elastomeric
Stockbridge or
≥ 19 mm Bolted 2,5 1,0
Elastomeric
Stockbridge or
All Helical 1,0 2,5
Elastomeric
Spiral damper All Helical 0,1 2,5
Only for standard conductors.
Acceptance criteria
No movement of the clamp relative to the conductor greater than shown in Table 2 shall occur
at or before the end of the specified minimum load for 60 s. Surface flattening of the outer
strands of the conductor is acceptable. If armor rods are used under the clamp, slippage of
the armor rods relative to the conductor is considered as clamp slippage.
7.6 Breakaway bolt test
The breakaway bolt or breakaway cap, if used, shall be tested by applying increasing torque
to the breakaway portion of the bolt or the cap until it breaks away. The test shall be carried
out at ambient temperature.
Precaution shall be taken on a constant continuous circular motion of the torque wrench and a
perpendicular angle between torque wrench and bolt head.
– 14 – IEC 61897:2020 © IEC 2020
The breakaway torque shall be recorded.
• Acceptance criteria:
The breakaway torque shall be within the tolerance specified by the supplier.
If no tolerance is specified, the range shall be nominal installation torque plus/minus 10 %.
For countries where ambient temperature below 0 °C can be expected, it is recommended to
repeat the tests on breakaway bolts and breakaway caps at the temperature corresponding to
the average temperature of the coldest month.
The specimens shall be kept for at least 1 h in an appropriate cooling device prior the test.
During the break away test the temperature should be measured and recorded. The
temperature during the test shall not increase more than 10 °C from initial cooling
temperature.
7.7 Clamp bolt tightening test
The test shall be performed by installing the clamp on a length of the conductor for which the
damper is intended. In case not available, an equivalent conductor or a tube of same diameter
can be used. If the damper is to be used for two or more sizes or types of conductor, then the
clamp shall be tested on each conductor unless the purchaser agrees to test on one
conductor only.
The bolts or nuts shall be tightened to a torque 10 % above the specified installation torque
with a calibrated torque wrench. Clamps with breakaway bolts or breakaway caps shall have
the breakaway portion of the head removed prior to the test and shall be tightened 10 %
above the specified installation torque.
• Acceptance criteria
The threaded connection shall remain serviceable (by hand) for three subsequent installations
and removals and all components of the clamp shall be without any mechanical deformation
or cracks. No plastic deformation shall occur to the conductor inside the clamp.
Lastly, the torque shall be increased to either twice the specified installation value or the
maximum torque value recommended by the bolt supplier, whichever is lower. This increase
shall not result in any breakage of threaded parts or other components of the clamp or any
cracks. The bolt shall be able to be removed from the clamp without any failure.
Plastic deformation is permitted.
7.8 Attachment of weights to messenger cable test
On an assembled damper a tensile load shall be applied between the weights coaxial with the
messenger cable, as indicated in Figure 2. The load shall be gradually increased (100 N/s
maximum) until it reaches 5 kN (specified minimum slip load). This load shall be kept constant
for 60 s.
The load shall then be increased slowly until one weight has been pulled free of the
messenger cable. The maximum load obtained during this process shall be recorded, for
information purposes only.
• Acceptance criteria
No relative movement greater than 1 mm between each weight and the messenger cable shall
occur at or before the end of the application of 5 kN for 60 s.
IEC 61897:2020 © IEC 2020 – 15 –
It may be necessary to remove the load before measuring the distance between the weights,
i.e. when the elastic stretch of the messenger cable results in an apparent movement of the
weights along the messenger cable.
Figure 2 – Test arrangement for attachment of weights to messenger cable test
7.9 Attachment of clamp to messenger cable test
A tensile load shall be applied between the messenger cable and the clamp body, coaxial with
the messenger cable, as indicated in Figure 3. The load shall be gradually increased (100 N/s
maximum) until it reaches 1,5 kN (specified minimum slip load). This load shall be kept
constant for 60 s.
The load shall then be increased slowly until the clamp has been pulled free of the messenger
cable. The maximum load obtained during this process shall be recorded, for information
purposes only.
• Acceptance criteria
No movement of the clamp relative to the messenger cable greater than 1 mm shall occur at
or before the end of the application of 1,5 kN for 60 s.
Figure 3 – Test arrangement for attachment of clamp to messenger cable test
7.10 Corona and radio interference voltage (RIV) tests
The tests shall
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...