Empty enclosures for low-voltage switchgear and controlgear assemblies - General requirements

Applies to empty enclosures, prior to the incorporation of switchgear and controlgear components by the user, as supplied by the enclosure manufacturer. This standard specifies definitions, classifications, characteristics and test requirements of enclosures to be used as part of switchgear and controlgear assemblies in accordance with the EN 60439 series, the rated voltage of which does not exceed 1 000 V a.c. at frequencies not exceeding 1 000 Hz, or 1 500 V d.c. and suitable for general use for either indoor or outdoor applications. This standard does not apply to enclosures, which are covered by other specific products standards (e.g. EN 60670). Compliance with the safety requirements of the applicable product standard is the responsibility of the final assembly manufacturer.

Leergehäuse für Niederspannungs-Schaltgerätekombinationen - Allgemeine Anforderungen

Enveloppes vides destinées aux ensembles d'appareillage à basse tension - Règles générales

S'applique aux enveloppes vides, avant incorporation de l'appareillage par l'utilisateur, dans l'état où elles sont fournies par le constructeur. Cette norme spécifie les définitions, les classifications, les caractéristiques et les exigences d'essais des enveloppes à utiliser en tant que partie d'ensembles d'appareillage selon la série EN 60439, dont la tension assignée ne dépasse pas 1 000 V en courant alternatif à des fréquences ne dépassant pas 1 000 Hz, ou 1 500 V en courant continu pour usage général extérieur ou intérieur. Cette norme ne s'applique pas aux enveloppes qui sont couvertes par d'autres normes de produits spécifiques (par exemple la EN 60670). La conformité avec les prescriptions de sécurité de la norme de produit applicable est de la responsabilité du constructeur final de l'ensemble.

Empty enclosures for low-voltage switchgear and controlgear assemblies - General requirements

General Information

Status
Withdrawn
Publication Date
31-May-2004
Withdrawal Date
04-Mar-2012
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
05-Mar-2012
Due Date
28-Mar-2012
Completion Date
05-Mar-2012

Relations

Buy Standard

Standard
EN 62208:2004
English language
25 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 62208:2004
01-junij-2004
1DGRPHãþD
SIST EN 50289-1-1:2002
SIST EN 50298:2000
Empty enclosures for low-voltage switchgear and controlgear assemblies -
General requirements
Empty enclosures for low-voltage switchgear and controlgear assemblies - General
requirements
Leergehäuse für Niederspannungs-Schaltgerätekombinationen - Allgemeine
Anforderungen
Enveloppes vides destinées aux ensembles d'appareillage à basse tension - Règles
générales
Ta slovenski standard je istoveten z: EN 62208:2003
ICS:
29.130.20 Nizkonapetostne stikalne in Low voltage switchgear and
krmilne naprave controlgear
SIST EN 62208:2004 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 62208:2004

---------------------- Page: 2 ----------------------

SIST EN 62208:2004
EUROPEAN STANDARD EN 62208
NORME EUROPÉENNE
EUROPÄISCHE NORM December 2003

ICS 29.130.20 Supersedes EN 50298:1998


English version


Empty enclosures for low-voltage switchgear and controlgear assemblies –
General requirements
(IEC 62208:2002)


Enveloppes vides destinées aux ensembles Leergehäuse für Niederspannungs-
d'appareillage à basse tension – Schaltgerätekombinationen –
Règles générales Allgemeine Anforderungen
(CEI 62208:2002) (IEC 62208:2002)



This European Standard was approved by CENELEC on 2003-12-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Lithuania, Luxembourg, Malta,
Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2003 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. EN 62208:2003 E

---------------------- Page: 3 ----------------------

SIST EN 62208:2004
EN 62208:2003 - 2 -
Foreword
The text of the International Standard IEC 62208:2002, prepared by SC 17D, Low-voltage switchgear
and controlgear assemblies, of IEC TC 17, Switchgear and controlgear, was submitted to the Unique
Acceptance Procedure and was approved by CENELEC as EN 62208 on 2003-12-01 without any
modification.
This European Standard supersedes EN 50298:1998.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2004-12-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2006-12-01
Annexes designated "normative" are part of the body of the standard.
In this standard, Annex ZA is normative.
Annex ZA has been added by CENELEC.
__________
Endorsement notice
The text of the International Standard IEC 62208:2002 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards indicated:
IEC 60417 NOTE Harmonized in EN 60417 series (not modified).
IEC 61000-5-7 NOTE Harmonized as EN 61000-5-7:2001 (not modified).
__________

---------------------- Page: 4 ----------------------

SIST EN 62208:2004
- 3 - EN 62208:2003
Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications
This European Standard incorporates by dated or undated reference, provisions from other
publications. These normative references are cited at the appropriate places in the text and the
publications are listed hereafter. For dated references, subsequent amendments to or revisions of any
of these publications apply to this European Standard only when incorporated in it by amendment or
revision. For undated references the latest edition of the publication referred to applies (including
amendments).
NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
Publication Year Title EN/HD Year
1)
IEC 60068-2-2 1974 Basic environmental testing procedures EN 60068-2-2 1993
Part 2: Tests - Test B: Dry heat
A2 1994 A2 1994

IEC 60068-2-11 1981 Part 2: Tests - Test Ka: Salt mist EN 60068-2-11 1999

IEC 60068-2-30 1980 Part 2: Tests - Test Db and guidance:
Damp heat, cyclic (12 + 12 hour cycle)
+ A1 1985 EN 60068-2-30 1999

IEC 60068-2-75 1997 Part 2-75: Tests - Test Eh: Hammer EN 60068-2-75 1997
tests

IEC 60439 Series Low-voltage switchgear and controlgear EN 60439 Series
assemblies

IEC 60439-1 1999 Low-voltage switchgear and controlgear EN 60439-1 1999
assemblies
Part 1: Type-tested and partially type-
tested assemblies

IEC 60439-5 1996 Part 5: Particular requirements for EN 60439-5 1996
assemblies intended to be installed
outdoors in public places - Cable
distribution cabinets (CDCs) for power
distribution in networks

IEC 60529 1989 Degrees of protection provided by EN 60529 1991
enclosures (IP Code)

IEC 60695-2-10 2000 Fire hazard testing EN 60695-2-10 2001
Part 2-10: Glowing/hot-wire based test
methods - Glow-wire apparatus and
common test procedure


1)
EN 60068-2-2 includes supplement A:1976 to IEC 60068-2-2.

---------------------- Page: 5 ----------------------

SIST EN 62208:2004
EN 62208:2003 - 4 -
Publication Year Title EN/HD Year
IEC 60695-2-11 2000 Part 2-11: Glowing/hot-wire based test EN 60695-2-11 2001
methods - Glow-wire flammability test
method for end-products

IEC/TR3 60890 1987 A method of temperature-rise - -
+ corr. March 1988 assessment by extrapolation for partially
type-tested assemblies (PTTA) of low-
voltage switchgear and controlgear
+ A1 1995 CLC/TR 60890 2002

IEC 62262 2002 Degrees of protection provided by EN 62262 2002
enclosures for electrical equipment
against external mechanical impacts (IK
code)

ISO 178 2001 Plastics - Determination of flexural EN ISO 178 2003
properties

ISO 179 Series Plastics - Determination of Charpy EN ISO 179 Series
impact properties

ISO 2409 1992 Paints and varnishes - Cross-cut test EN ISO 2409 1994

ISO 4628-3 1982 Paints and varnishes - Evaluation of - -
degradation of paint coatings -
Designation of intensity, quantity and
size of common types of defect
Part 3: Designation of degree of rusting

ISO 4892-2 1994 Plastics - Methods of exposure to EN ISO 4892-2 1999
laboratory light sources
Part 2: Xenon arc sources

ISO 11469 2000 Plastics - Generic identification and EN ISO 11469 2000
marking of plastic products

---------------------- Page: 6 ----------------------

SIST EN 62208:2004
NORME CEI
INTERNATIONALE IEC
62208
INTERNATIONAL
Première édition
STANDARD
First edition
2002-11
Enveloppes vides destinées aux ensembles
d'appareillage à basse tension –
Règles générales
Empty enclosures for low-voltage switchgear
and controlgear assemblies –
General requirements
 IEC 2002 Droits de reproduction réservés  Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in any
utilisée sous quelque forme que ce soit et par aucun procédé, form or by any means, electronic or mechanical, including
électronique ou mécanique, y compris la photocopie et les photocopying and microfilm, without permission in writing from
microfilms, sans l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch  Web: www.iec.ch
CODE PRIX
S
Commission Electrotechnique Internationale PRICE CODE
International Electrotechnical Commission
Международная Электротехническая Комиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue

---------------------- Page: 7 ----------------------

SIST EN 62208:2004
62208  IEC:2002 – 3 –
CONTENTS
FOREWORD . 5
1 Scope . 7
2 Normative references. 7
3 Terms and definitions. 9
4 Classification .11
5 EMC requirements .13
6 Information to be given regarding the enclosure .13
6.1 Marking .13
6.2 Documentation.13
7 Service conditions.13
7.1 Normal service conditions .15
7.2 Special service conditions .15
7.3 Conditions during transport and storage .17
8 Design and construction.17
8.1 General .17
8.2 Dimensions.17
8.3 Mounting arrangements .17
8.4 Static loads.17
8.5 Lifting and transport support.19
8.6 Access to the interior of the enclosure.19
8.7 Protective circuit .19
8.8 Dielectric strength.19
8.9 Degree of protection (IK code) .19
8.10 Degree of protection (IP code) .21
9 Type tests .21
9.1 General conditions of tests.21
9.2 Marking .23
9.3 Static loads.23
9.4 Lifting .23
9.5 Verification of axial loads of metal inserts.23
9.6 Verification of degree of protection against external mechanical impacts (IK code) .25
9.7 Verification of degree of protection (IP code).27
9.8 Properties of insulating materials .29
9.9 Verification of dielectric strength .33
9.10 Verification of the continuity of the protective circuit .35
9.11 Verification of resistance to weathering .35
9.12 Verification of resistance to corrosion.37
Bibliography .41
Figure 1 – Ball-pressure apparatus .39
Table 1 – Number of samples to be tested and order of test per sample.21
Table 2 – Axial loads of metal inserts.25
Table 3 – Relation between IK code and impact energy.27

---------------------- Page: 8 ----------------------

SIST EN 62208:2004
62208  IEC:2002 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
EMPTY ENCLOSURES FOR LOW-VOLTAGE SWITCHGEAR
AND CONTROLGEAR ASSEMBLIES –
GENERAL REQUIREMENTS
FOREWORD
1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, the IEC publishes International Standards. Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may
participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. The IEC collaborates closely with the International Organization
for Standardization (ISO) in accordance with conditions determined by agreement between the two
organizations.
2) The formal decisions or agreements of the IEC on technical matters express, as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form
of standards, technical specifications, technical reports or guides and they are accepted by the National
Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject
of patent rights. The IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 62208 has been prepared by subcommittee 17D: Low-voltage
switchgear and controlgear assemblies, of IEC technical committee 17: Switchgear and
controlgear.
The text of this standard is based on the following documents:
FDIS Report on voting
17D/262/FDIS 17D/272/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
The committee has decided that the contents of this publication will remain unchanged until 2005.
At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
The United States of America (USA) uses enclosure “Type” designations instead of IP ratings.
For these markets, replace “the degree of protection according to IEC 60529” with
“the appropriate enclosure Type designation according to NEMA 250.”

---------------------- Page: 9 ----------------------

SIST EN 62208:2004
62208  IEC:2002 – 7 –
EMPTY ENCLOSURES FOR LOW-VOLTAGE SWITCHGEAR
AND CONTROLGEAR ASSEMBLIES –
GENERAL REQUIREMENTS
1 Scope
This International Standard applies to empty enclosures, prior to the incorporation of
switchgear and controlgear components by the user, as supplied by the enclosure
manufacturer.
This standard specifies definitions, classifications, characteristics and test requirements of
enclosures to be used as part of switchgear and controlgear assemblies in accordance with the
IEC 60439 series, the rated voltage of which does not exceed 1 000 V a.c. at frequencies not
exceeding 1 000 Hz, or 1 500 V d.c. and suitable for general use for either indoor or outdoor
applications.
This standard does not apply to enclosures, which are covered by other specific products
standards (e.g. IEC 60670).
Compliance with the safety requirements of the applicable product standard is the responsibility
of the final assembly manufacturer.
NOTE This standard may serve as a basis for other technical committees.
2 Normative references
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 60068-2-2:1974, Basic environmental testing procedures – Part 2: Tests – Tests B:
Dry heat
Amendment 2 (1994)
IEC 60068-2-11:1981, Basic environmental testing procedures – Part 2: Tests – Test Ka:
Salt mist
IEC 60068-2-30:1980, Basic environmental testing procedures – Part 2: Tests – Test Db and
guidance: Damp heat, cyclic (12 + 12 hour cycle)
Amendment 1 (1985)
IEC 60068-2-75:1997, Environmental testing – Part 2: Tests – Test Eh: Hammer tests
IEC 60439 (all parts), Low-voltage switchgear and controlgear assemblies
IEC 60439-1:1999, Low-voltage switchgear and controlgear assemblies – Part 1: Type-tested
and partially type-tested assemblies
IEC 60439-5:1996, Low-voltage switchgear and controlgear assemblies – Part 5: Particular
requirements for assemblies intended to be installed outdoors in public places – Cable
distribution cabinets (CDCs) for power distribution in networks
IEC 60529:1989, Degrees of protection provided by enclosures (IP code)

---------------------- Page: 10 ----------------------

SIST EN 62208:2004
62208  IEC:2002 – 9 –
IEC 60695-2-10:2000, Fire hazard testing – Part 2-10: Glowing/hot-wire based test methods –
Glow-wire apparatus and common test procedure
IEC 60695-2-11: 2000, Fire hazard testing – Part 2-11: Glowing/hot-wire based test methods –
Glow-wire flammability test methods for end-products
IEC 60890:1987, A method of temperature-rise assessment by extrapolation for partially type-
tested assemblies (PTTA) of low-voltage switchgear and controlgear
Amendment 1 (1995)
IEC 62262:2002, Degrees of protection provided by enclosures for electrical equipment against
external mechanical impacts (IK code)
ISO 178:2001, Plastics – Determination of flexural properties
ISO 179 (all parts), Plastics – Determination of Charpy impact strength
ISO 2409:1992, Paints and varnishes – Cross-cut test
ISO 4628-3:1982, Paints and varnishes – Evaluation of degradation of paint coatings –
Designation of intensity, quantity and size of common types of defect – Part 3: Designation of
degree of rusting
ISO 4892-2:1994, Plastics – Methods of exposure to laboratory light sources – Part 2: Xenon-
arc sources
ISO 11469:2000, Plastics – Generic identification and marking of plastic products
3 Terms and definitions
For the purposes of this International Standard, the following definitions apply.
3.1
empty enclosure
enclosure intended for support and installation of electrical equipment, whose internal space
provides suitable protection against external influences as well as a specified degree of
protection against approach to or contact with live parts and against contact with moving parts
NOTE Throughout this standard, the word enclosure is used for empty enclosure.
3.2
protected space
internal space or portion of the internal space of the enclosure as specified by the
manufacturer intended for the mounting of switchgear and controlgear for which the specified
protection is provided by the enclosure
3.3
cover
external part of the enclosure
3.4
door
hinged or sliding cover

---------------------- Page: 11 ----------------------

SIST EN 62208:2004
62208  IEC:2002 – 11 –
3.5
mounting plate
separate internal accessory of the enclosure intended for the mounting of electrical
components
3.6
cable gland plate
removable accessory of the enclosure, intended for securing and sealing of cables, conductors
and conduits at their point of entry
3.7
removable cover
cover which is designed for closing an opening in the external enclosure and which can be
removed for carrying out certain operations and maintenance work.
NOTE A lid is considered as a removable cover.
3.8
enclosure manufacturer
manufacturer of an enclosure or the vendor who resells under his own responsibility
3.9
box
enclosure, generally of small dimensions and, in principle, intended to be mounted on a vertical
plane
3.10
cubicle
empty enclosure, generally of large dimensions, and in principle of the floor standing type,
which may comprise several sections, sub-sections or compartments
NOTE Enclosures with an irregular shape, such as a desk, are considered cubicles for testing purposes.
4 Classification
Enclosures are classified according to
a) the type of material:
− insulating
− metallic
− combination of insulating and metallic
b) method of fixing:
− floor standing
− wall mounting
− flush mounting
− pole mounting
c) the intended location:
− outdoor
− indoor
d) the degree of protection:
− IP code, according to IEC 60529
− IK code, according to IEC 62262
e) rated insulation voltage (for enclosures made of insulating materials)

---------------------- Page: 12 ----------------------

SIST EN 62208:2004
62208  IEC:2002 – 13 –
5 EMC requirements
EMC requirements are not applicable for enclosures to this standard. For degrees of protection
provided by enclosures against electromagnetic disturbances (EM code) see IEC 61000-5-7.
6 Information to be given regarding the enclosure
The following information shall be given by the manufacturer.
6.1 Marking
The enclosure shall be identifiable, making it possible for the final assembler to obtain relevant
information from the enclosure manufacturer. Such identification shall comprise:
– either the name, trade mark or identification mark of the enclosure manufacturer;
– type designation or identification number of the enclosure.
The marking shall be durable and easily legible and may be inside the enclosure.
Compliance is checked according to the test of 9.2 and by inspection.
Marking for the recycling of plastic parts shall be as stated in ISO 11469.
NOTE Marking of enclosures intended for class II assemblies with the symbol IEC 60417-5172 is the responsibility
of the final assembly manufacturer.
6.2 Documentation
The manufacturer's documentation shall include all relevant constructional, mechanical
characteristics, the enclosure classification (see clause 4) and any instruction necessary for
the correct handling, assembling, mounting and service conditions of the enclosure as well as
reference to this standard.
Information shall also be available concerning the thermal power dissipation relative to the
effective cooling surface. This will provide the user with the correct data for the selection of
electrical equipment to be installed. For the purpose of the calculation, it is assumed that the
heat generated by the selected equipment is distributed uniformly inside the protected space.
NOTE 1 Thermal power dissipation may be determined using an appropriate method of calculation (see e.g.
IEC 60890), or by test (see e.g. 8.2.1.4 of IEC 60439-1).
NOTE 2 The basis external ambient temperature is defined in clause 7.
7 Service conditions
Enclosures conforming to this standard are intended for use under the following service
conditions.
The enclosure manufacturer shall specify the locations for which the enclosure is intended.

---------------------- Page: 13 ----------------------

SIST EN 62208:2004
62208  IEC:2002 – 15 –
7.1 Normal service conditions
7.1.1 Ambient air temperature
7.1.1.1 Ambient air temperature for indoor locations
The ambient air temperature does not exceed +40 °C and its average over a period of 24 h
does not exceed +35 °C.
The lower limit of the ambient air temperature is –5 °C.
7.1.1.2 Ambient air temperature for outdoor locations
The ambient air temperature does not exceed +40 °C and its average over a period of 24 h
does not exceed +35 °C.
The lower limit of the ambient air temperature is –25 °C in a temperate climate and –50 °C in
an arctic climate.
NOTE The use of enclosures in an arctic climate may require a special agreement between the enclosure
manufacturer and user.
7.1.2 Atmospheric conditions
7.1.2.1 Atmospheric conditions for indoor locations
The air is clean and its relative humidity does not exceed 50 % at a maximum temperature of
+40 °C. Higher relative humidity may be permitted at lower temperatures, for example 90 %
at +20 °C.
7.1.2.2 Atmospheric conditions for outdoor locations
The relative humidity may be temporarily as high as 100 % at a maximum temperature of
+25 °C.
7.1.3 Description of locations
For outdoor locations the additional tests specified in 9.11 and 9.12 apply.
For indoor locations, the additional test specified in 9.12.1 a) applies.
7.2 Special service conditions
Where any of the following special service conditions exist, the applicable particular
requirements shall be subject to agreement between user and manufacturer.
Examples of such conditions may include the following:
– abnormal ambient air temperature and humidity;
– presence of corrosive substances;
– presence of particular dusts (coal, cement, etc.);
– abnormal mechanical stresses (seismic, etc.);
– presence of fauna, flora, mould;
– ionizing influences;
– electromagnetic interferences;
– vibrations.
Agreements reached shall not contradict any safety regulations in force.

---------------------- Page: 14 ----------------------

SIST EN 62208:2004
62208  IEC:2002 – 17 –
7.3 Conditions during transport and storage
Unless otherwise specified, the following temperature range applies during transport and
storage: between –25 °C to +55 °C and for short periods not exceeding 24 h up to +70 °C.
8 Design and construction
8.1 General
The enclosure shall be constructed only of materials capable of withstanding the mechanical,
electrical and thermal stresses, as specified in clause 9, as well as the effects of humidity
which are likely to be encountered in normal use.
Protection against corrosion shall be ensured by the use of suitable materials or by the
application of protective coating to the exposed surface, taking into account the intended
conditions of use.
Compliance to this requirement is checked by the test of 9.12.
In addition for enclosures or parts of enclosures made of insulating materials, thermal stability,
resistance to heat, fire and weathering shall be verified according to the tests of 9.8 and 9.11.
Where parts of an enclosure are designed to retain current-carrying parts in position, the
relevant standard shall apply for their design and verification.
8.2 Dimensions
The dimensions shall be given in millimetres.
The external dimensions: height, width and depth are nominal values and shall be indicated in
the catalogue of the enclosure manufacturer.
The projection of cable gland plates, removable covers and handles shall not be included in the
external nominal dimensions, the dimensions of such shall be included in the manufacturer’s
documentation.
8.3 Mounting arrangements
8.3.1 Enclosure
The means and location of the enclosure mounting shall be defined in the enclosure
manufacturer's documentation.
8.3.2 Equipment mounting surfaces
The location of the equipment mounting surfaces and their means of fixing shall be defined
in the enclosure manufacturer's documentation.
8.4 Static loads
The enclosure manufacturer shall specify, in the documentation, the maximum permissible
loads in the enclosure and on its door.
Compliance is checked according to the test of 9.3.

---------------------- Page: 15 ----------------------

SIST EN 62208:2004
62208  IEC:2002 – 19 –
8.5 Lifting and transport support
W
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.