oSIST prEN IEC 60269-100:2026
(Main)Low-Voltage Fuses. Part 100: General requirements and tests
- Status
- Not Published
- Public Enquiry End Date
- 29-Nov-2026
- Technical Committee
- EVA - Fuses
- Current Stage
- 4020 - Public enquire (PE) (Adopted Project)
- Start Date
- 28-Sep-2026
- Due Date
- 15-Feb-2027
oSIST prEN IEC 60269-100:2026 is the SIST publication of the IEC draft for low-voltage fuses. It sets the general requirements and test methods for enclosed current-limiting fuse-links, fuse-holders and complete fuses intended for power-frequency AC circuits up to 1 000 V and DC circuits up to 1 500 V. It is meant to be used together with the relevant parts of the IEC 60269-200 series and IEC 60269-300 series for the specific utilization class and fuse system.
What does oSIST prEN IEC 60269-100:2026 specify?
oSIST prEN IEC 60269-100:2026 defines the common rules for low-voltage fuses and the tests used to verify them. It covers interchangeability by dimensions and characteristics, so compatible parts can be replaced without changing the intended protection performance.
The scope covers fuses with enclosed current-limiting fuse-links and rated breaking capacities of not less than 6 kA. It excludes miniature fuses covered by IEC 60127. The document also applies to fuse-links intended for use in fuse-combination units according to IEC 60947-3.
The document is organized into:
- Clause 1, scope
- Clause 2, normative references
- Clause 3, terms and definitions
- Clause 4, conditions for operation in service
- Clause 5, classification
- Clause 6, characteristics of fuses
- Clause 7, markings
- Clause 8, standard conditions for construction
- Clause 9, type tests
- Annexes A to G for planned companion parts, test calculations and supporting information
| Annex | What it covers |
|---|---|
| Annex A | Planned documents in the IEC 60269-200 and -300 series |
| Annex B | Measurement of short-circuit power factor |
| Annex C | Calculation of pre-arcing I²t and operating I²t at reduced voltage |
| Annex D | Effect of ambient temperature and surroundings on fuse-link performance |
| Annex E | Special test for cable overload protection |
| Annex F | Survey of complete tests |
| Annex G | Components of a fuse |
What are the key requirements of oSIST prEN IEC 60269-100:2026?
Service conditions and application limits
oSIST prEN IEC 60269-100:2026 assumes defined service conditions unless a subsequent part says otherwise. Normal ambient air temperature is up to 40 °C, with a 24 h mean not above 35 °C, altitude up to 2 000 m, and clean air with limited humidity.
For voltage, the document distinguishes AC and DC behavior and sets maximum applied-voltage values in Table 1. In practice, this means the fuse rating must match the actual system voltage and the way the voltage varies during operation, not just the nominal label.
Rated characteristics and utilization classes
oSIST prEN IEC 60269-100:2026 sets the framework for rated voltage, rated current, rated frequency, power dissipation, breaking capacity, cut-off current characteristics and I²t characteristics. Rated voltages can go up to 1 000 V AC and 1 500 V DC, with preferred values given in Table 2.
The document also separates breaking ranges into “g” fuse-links, which are full-range, and “a” fuse-links, which are partial-range. That distinction matters because it tells the buyer or designer whether the fuse alone clears overloads and short circuits, or whether it is intended mainly for short-circuit protection with another device handling smaller overcurrents.
Construction, insulation and protection
oSIST prEN IEC 60269-100:2026 requires construction suitable for replacement, reliable contacts, and adequate mechanical strength. It also sets insulation-related requirements such as clearances, creepage distances, rated impulse withstand voltage, leakage currents and suitability for isolation.
The construction rules extend to protection against electric shock, resistance to heat, corrosion and abnormal heat, and electromagnetic compatibility. In practice, this means the fuse and fuse-holder must be designed so that normal service, switching and fault conditions do not create unsafe touch risk, damage, or unexpected interaction with nearby equipment.
Marking and identification
oSIST prEN IEC 60269-100:2026 requires durable, legible markings verified by test. Fuse-holders and fuse-links must carry identification data such as manufacturer identification, rated voltage, rated current, system or size, utilization class for fuse-links, rated breaking capacity, and the IEC 60269 designation.
This matters because correct marking is what installers and inspectors use to match the fuse to its holder and to the intended application. For small fuse-links, the document allows only the essential information to be marked on the part, with the rest given in product documentation.
Type tests and evidence of performance
oSIST prEN IEC 60269-100:2026 uses type tests to verify insulating properties, temperature rise, operation, breaking capacity, cut-off current characteristics, I²t characteristics, enclosure protection, contact endurance, mechanical behavior and marking durability. Clause 9 also gives detailed arrangements for test specimens, circuits, measuring instruments and result acceptance.
For a manufacturer or laboratory, this is the section that turns the design rules into verifiable evidence. It shows what must be measured, under which test conditions, and how the results are judged.
What terms does oSIST prEN IEC 60269-100:2026 define?
- Fuse - a device that opens a circuit by the fusing of one or more specially designed parts when current exceeds a specified value for long enough.
- Fuse-holder - the combination of the fuse-base and its fuse-carrier.
- Fuse-link - the replaceable part of a fuse that includes the fuse-element(s) and is renewed after operation.
- Current-limiting fuse-link - a fuse-link that limits current to a substantially lower value than the prospective peak current during operation.
- Breaking capacity - the prospective current a fuse-link can interrupt at stated voltage under prescribed conditions.
- Utilization class - the combination of breaking range and application category, such as gG.
- Joule integral (I²t) - the integral of current squared over time, used to express let-through energy.
- Overcurrent selectivity - coordination so that only the intended protective device operates for a given overcurrent.
Who uses oSIST prEN IEC 60269-100:2026?
oSIST prEN IEC 60269-100:2026 is used by fuse manufacturers, switchgear and controlgear manufacturers, test laboratories, certification bodies, and technical teams that specify or buy low-voltage protection devices. It is also relevant to electrical designers, quality managers, and installers working on power distribution, industrial equipment, semiconductor protection, PV systems and battery protection.
The document is especially useful when selecting compatible fuse-links, fuse-holders and fuse systems, checking test evidence, or writing product documentation. It helps each group speak the same technical language when rating, testing and identifying fuses.
What changed in oSIST prEN IEC 60269-100:2026 from the previous edition?
oSIST prEN IEC 60269-100:2026 is the restructured form of IEC 60269-1:2024. The foreword states that it and the new IEC 60269-200 and IEC 60269-300 parts replace the earlier IEC 60269-1:2024 structure, while keeping technical changes to a minimum and correcting or clarifying some points.
It also states that IEC 60269-1:2024 and its subsequent parts 2 to 7 are not to be used together with IEC 60269-100 and the new 200 and 300 series, except for IEC TR 60269-5, which remains an independent guide.
Which standards are used with oSIST prEN IEC 60269-100:2026?
oSIST prEN IEC 60269-100:2026 relies on several normative references for vocabulary, installation conditions, insulation, safety and test methods:
- IEC 60050-151, -428, -441, -442, -482, -521, -551, -651 and -826 - vocabulary used for terms in the standard
- IEC 60364-5-51 - common rules for selection and erection of electrical equipment, used for supply-voltage conditions
- IEC 60529 - degree of protection of enclosures
- IEC 60664-1 and IEC 60664-1/AMD1:2025 - insulation coordination, clearances, creepage and impulse withstand
- IEC 60695-2-10 and IEC 60695-2-11 - glow-wire fire test methods
- IEC 60947-3 and IEC 60947-3/AMD1:2025 - fuse-combination units
- IEC 61140 - protection against electric shock
- ISO 3 - preferred numbers for selecting intermediate rated voltages
- IEC TR 60269-5:2014/AMD1:2020 - de-rating guidance at higher altitude
- IEC 60269-200 series and IEC 60269-300 series - the companion parts that add utilization-class and fuse-system requirements
What does the oSIST prEN IEC 60269-100:2026 document contain?
oSIST prEN IEC 60269-100:2026 contains the core tables, figures, formulas and test methods for low-voltage fuses. The tables cover rated voltages, temperature-rise limits, preferred values, test voltages, breaking-capacity test values, and cable overload test parameters.
The figures support practical test work, including cut-off characteristics, isolation marking, overload behavior, breaking-capacity test circuits and oscillogram interpretation. Annex B and Annex C provide calculation methods for short-circuit power factor and I²t values, while Clause 9 describes the test set-ups, calibration, result interpretation and acceptance criteria used for design verification, type testing and certification.
Get Certified
Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)
Italian electrical product certification.

SLG Prüf- und Zertifizierungs GmbH
German testing and certification body.

UL Solutions
Global safety science company with testing, inspection and certification.
Sponsored listings
Frequently Asked Questions
oSIST prEN IEC 60269-100:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Low-Voltage Fuses. Part 100: General requirements and tests". This standard covers: Low-Voltage Fuses. Part 100: General requirements and tests
Low-Voltage Fuses. Part 100: General requirements and tests
oSIST prEN IEC 60269-100:2026 is classified under the following ICS (International Classification for Standards) categories: 29.120.50 - Fuses and other overcurrent protection devices. The ICS classification helps identify the subject area and facilitates finding related standards.
oSIST prEN IEC 60269-100:2026 is associated with the following European legislation: EU Directives/Regulations: 2014/35/EU; Standardization Mandates: M/511. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
oSIST prEN IEC 60269-100:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
SLOVENSKI STANDARD
01-november-2026
Nizkonapetostne varovalke. 100.del: Splošne zahteve in preskusi
Low-Voltage Fuses. Part 100: General requirements and tests
Ta slovenski standard je istoveten z: prEN IEC 60269-100:2026
ICS:
29.120.50 Varovalke in druga Fuses and other overcurrent
nadtokovna zaščita protection devices
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
32B/791/CDV
COMMITTEE DRAFT FOR VOTE (CDV)
PROJECT NUMBER:
IEC 60269-100 ED1
DATE OF CIRCULATION: CLOSING DATE FOR VOTING:
2026-09-18 2026-12-11
SUPERSEDES DOCUMENTS:
32B/777/CD, 32B/783/CC
IEC SC 32B : LOW-VOLTAGE FUSES
SECRETARIAT: SECRETARY:
Germany Mr Andreas Schüppel
OF INTEREST TO THE FOLLOWING COMMITTEES: HORIZONTAL FUNCTION(S):
SC 23E,SC 37A,TC 64,SC 121A,SC 121B
ASPECTS CONCERNED:
Electricity transmission and distribution,Energy Efficiency
SUBMITTED FOR CENELEC PARALLEL VOTING NOT SUBMITTED FOR CENELEC PARALLEL VOTING
Attention IEC-CENELEC parallel voting
The attention of IEC National Committees, members of
CENELEC, is drawn to the fact that this Committee Draft
for Vote (CDV) is submitted for parallel voting.
The CENELEC members are invited to vote through the
CENELEC online voting system.
This document is still under study and subject to change. It should not be used for reference purposes.
Recipients of this document are invited to submit, with their comments, notification of any relevant patent rights of
which they are aware and to provide supporting documentation.
Recipients of this document are invited to submit, with their comments, notification of any relevant “In Some
Countries” clauses to be included should this proposal proceed. Recipients are reminded that the CDV stage is
the final stage for submitting ISC clauses. (SEE AC/22/2007 OR NEW GUIDANCE DOC).
TITLE:
Low-Voltage Fuses. Part 100: General requirements and tests
PROPOSED STABILITY DATE: 2030
NOTE FROM TC/SC OFFICERS:
download this electronic file, to make a copy and to print out the content for the sole purpose of preparing National
Committee positions. You may not copy or "mirror" the file or printed version of the document, o r any part of it, for
any other purpose without permission in writing from IEC.
IEC CDV 60269-100 © IEC 2026
Link to Committee Draft for Vote (CDV) online document:
Click here
How to access
This link leads you to the Online Standards Development (OSD) platform for National Mirror
Committee’s (NMC) comments. The project draft may be found further down this document.
Resource materials
We recommend NCs to review the available materials to better understand the member commenting
on the OSD platform. This includes the:
• OSD NC roles overview
• How to add and submit comments to the IEC
Contact
Should you require any assistance, please contact the IEC IT Helpdesk.
IEC CDV 60269-100 © IEC 2026
CONTENTS
CONTENTS . 1
FOREWORD . 6
Introduction. 8
1 Scope . 9
2 Normative references . 9
3 Terms and definitions . 10
3.1 Fuses and their component parts . 11
3.2 General terms . 13
3.3 Characteristic quantities . 16
3.4 Application related terms . 21
3.4.1 Semiconductor protection . 21
3.4.2 PV systems . 22
3.4.3 Battery protection . 22
4 Conditions for operation in service . 22
4.1 General . 22
4.2 Ambient air temperature (T ) . 22
a
4.3 Altitude . 22
4.4 Atmospheric conditions . 22
4.5 Voltage . 23
4.6 Current . 23
4.7 Frequency, power factor and time constant . 23
4.7.1 Frequency . 23
4.7.2 Power factor . 23
4.7.3 Time constants . 23
4.8 Conditions of installation . 23
4.8.1 General . 23
4.8.2 Utilization class . 24
4.8.3 Selectivity . 24
4.8.4 Selection of a fuse-link . 24
5 Classification . 24
6 Characteristics of fuses . 24
6.1 Summary of characteristics . 24
6.1.1 General . 24
6.1.2 Fuse-holders . 24
6.1.3 Fuse-links . 24
6.1.4 Complete fuses. 25
6.2 Rated voltage . 25
6.3 Rated current . 25
6.3.1 Rated current of the fuse-link . 25
6.3.2 Rated current of the fuse-holder . 25
6.3.3 Peak withstand current of a fuse-holder . 26
6.4 Rated frequency . 26
6.5 Rated power dissipation of a fuse-link and rated maximum power
acceptance of a fuse-holder . 26
6.6 Limits of time-current characteristics . 26
6.6.1 General . 26
IEC CDV 60269-100 © IEC 2026
6.6.2 Time-current characteristics, time-current zones . 26
6.6.3 Conventional times and currents . 27
6.6.4 Gates . 27
6.7 Utilization class and rated breaking capacity . 27
6.7.1 General . 27
6.7.2 Identification of the breaking range . 27
6.7.3 Application category . 27
6.7.4 Rated breaking capacity . 27
6.8 Cut-off current and I t characteristics . 28
6.8.1 General . 28
6.8.2 Cut-off current characteristics . 28
6.8.3 I t characteristics . 28
7 Markings . 29
7.1 General . 29
7.2 Markings of fuse-holders . 29
7.3 Markings of fuse-links . 29
8 Standard conditions for construction . 30
8.1 Mechanical design . 30
8.1.1 Replacement of fuse-links. 30
8.1.2 Connections, including terminals . 30
8.1.3 Fuse-contacts . 30
8.1.4 Construction of a gauge-piece . 31
8.1.5 Mechanical strength of the fuse-link . 31
8.2 Insulating properties and suitability for isolation . 31
8.2.1 General . 31
8.2.2 Clearances and creepage distances . 31
8.2.3 Rated impulse withstand voltage . 32
8.2.4 Leakage currents of fuses. 33
8.2.5 Additional constructional requirements for fuses with linked fuse-
carriers . 33
8.3 Temperature rise, power dissipation of the fuse-link and maximum power
acceptance of a fuse-holder . 33
8.4 Operation . 34
8.5 Breaking capacity . 35
8.6 Cut-off current characteristic . 35
8.7 I t characteristics . 35
8.8 Overcurrent selectivity of fuse-links . 36
8.9 Protection against electric shock . 36
8.9.1 General . 36
8.9.2 Requirements for fuses to be used by authorized persons only . 36
8.9.3 Additional requirements for fuses to be used by ordinary persons . 37
8.10 Resistance to heat . 37
8.11 Mechanical strength . 38
8.12 Resistance to corrosion . 38
8.12.1 General . 38
8.12.2 Resistance to rusting . 38
8.12.3 Resistance to season cracking . 38
8.13 Resistance to abnormal heat, and fire . 38
IEC CDV 60269-100 © IEC 2026
8.14 Electromagnetic compatibility . 38
9 Type Tests . 38
9.1 General requirements for Type Tests . 38
9.1.1 General . 38
9.1.2 Ambient air temperature (T ) . 39
a
9.1.3 Condition of the fuse. 39
9.1.4 Arrangement of the fuse and dimensions . 39
9.1.5 Testing of fuse-links . 39
9.1.6 Testing of fuse-holders . 39
9.1.7 Complete tests . 40
9.1.8 Testing of fuse-links of a homogeneous series . 40
9.2 Verification of the insulating properties and of the suitability for isolation . 40
9.2.1 Arrangement of the fuse-holder . 40
9.2.2 Verification of the insulating properties . 41
9.2.3 Verification of the suitability for isolation . 42
9.2.4 Acceptability of test results . 43
9.3 Verification of temperature rise and power dissipation . 43
9.3.1 Arrangement of the fuse . 43
9.3.2 Measurement of the temperature rise . 43
9.3.3 Measurement of the power dissipation of the fuse-link . 43
9.3.4 Temperature rise of the fuse-holder . 44
9.3.5 Test method . 45
9.3.6 Acceptability of test results . 45
9.4 Verification of operation . 45
9.4.1 Arrangement of the fuse . 45
9.4.2 Ambient air temperature . 45
9.4.3 Test method and acceptability of test results . 45
9.5 Verification of the breaking capacity. 49
9.5.1 General . 49
9.5.2 Arrangement of the fuse . 49
9.5.3 Characteristics of the test circuit . 49
9.5.4 Measuring instruments . 51
9.5.5 Calibration of test circuit . 51
9.5.6 Test method . 53
9.5.7 Interpretation of oscillograms . 54
9.5.8 Acceptability of test results . 57
9.6 Verification of the cut-off current characteristics. 57
9.6.1 Test method . 57
9.6.2 Acceptability of test results . 57
9.7 Verification of I t characteristics and overcurrent selectivity . 57
9.7.1 Test method . 57
9.7.2 Acceptability of test results . 58
9.7.3 Verification of overcurrent selectivity . 58
9.8 Verification of the degree of protection of enclosures . 58
9.9 Verification of resistance to heat . 58
9.10 Verification of non-deterioration of contacts . 58
9.10.1 Arrangement of the fuse . 58
9.10.2 Test method . 58
IEC CDV 60269-100 © IEC 2026
9.10.3 Acceptability of test results . 59
9.11 Mechanical and miscellaneous tests . 59
9.11.1 Mechanical strength . 59
9.11.2 Verification of freedom from season cracking. 59
9.11.3 Verification of resistance of insulating materials to abnormal heat, and
fire . 60
9.11.4 Verification of resistance to rusting . 60
9.12 Test of durability of markings . 60
Annex A (informative) List of planned documents within IEC 60269-200 and -300
series . 61
Annex B (normative) Measurement of short-circuit power factor . 63
Annex C (normative) Calculation of pre-arcing I t values and calculation of operating
I t values at reduced voltage . 66
C.1 Approximation of the pre-arcing I2t value at 0,01 s . 66
C.2 Calculation of the value of pre-arcing I²t under the conditions of test no. 2 . 66
C.3 Calculation of the value of operating I²t at reduced voltage . 66
Annex D (informative) Effect of change of ambient temperature and surroundings on
the performance of fuse-links . 68
D.1 Effect of increase of ambient temperature . 68
D.1.1 Effect on current rating . 68
D.1.2 Effect on temperature rise . 68
D.1.3 Effect on conventional fusing and non-fusing current (I and I ) . 68
f nf
D.1.4 Effects on motor starting conditions . 68
D.2 Effects caused by a decrease in ambient air temperature . 68
D.3 Influences of installation conditions . 68
Annex E (normative) Special test for cable overload protection . 69
E.1 General . 69
E.2 Arrangement of the fuse. 69
E.2.1 Special test for fuses according to IEC 60269-301 (NH system) for
cable overload protection . 69
E.2.2 Special test for fuses according to IEC 60269-302 (D) for cable
overload protection . 69
E.3 Test method and acceptability of test results . 70
Annex F (normative) Survey of complete tests . 71
Annex G (informative) Components of a fuse . 72
Bibliography . 74
Figure 1 – General presentation of the cut-off characteristics for a series of AC fuse-
links 28
Figure 2 – Symbol for marking fuse-holders suitable for isolation . 33
Figure 3 – Overload curve and time-current characteristic for "a" fuse-links . 47
Figure 4 – Typical diagram of the circuit used for breaking capacity test . 50
Figure 5 – Interpretation of oscillograms taken during the AC breaking-capacity tests
(see 9.5.7) . 55
Figure 6 – Interpretation of oscillograms taken during the DC breaking-capacity tests
(see 9.5.7) . 56
Figure B.1 – Determination of circuit-impedance for calculation of power factor in
accordance with method I . 65
IEC CDV 60269-100 © IEC 2026
Figure G.1 – Characteristic parts of fuses . 73
Table 1 – Maximum values of applied voltage . 23
Table 2 – preferred values of rated voltages . 25
Table 3 – Conventional times . 27
Table 4 – Minimum clearances in air . 31
Table 5 – Minimum creepage distances . 32
Table 6 – rated impulse withstand voltage . 32
Table 7 – Temperature rise limits Δ𝑇 = (𝑇 − 𝑇𝑎) for terminals . 34
Table 8 – Maximum arc voltage . 35
Table 9 – Test voltages. 41
Table 10 – Test voltages across the open contacts of fuses suitable for isolation . 42
Table 11 – Cross-sectional area of copper conductors for tests according to 9.3 and
9.4 44
Table 12 – Conventional cable overload protection test parameters . 48
Table 13 – Values for breaking-capacity tests on AC fuses . 51
Table 14 – Values for breaking capacity tests on DC fuses . 52
Table A.1 – Subsequent parts of IEC 60269-200 series (planned). 61
Table A.2 – Subsequent parts of IEC 60269-300 series (planned). 62
IEC CDV 60269-100 © IEC 2026
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
Low-Voltage Fuses. Part 100: General requirements and tests
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for
standardization comprising all national electrotechnical committees (IEC National Committees).
The object of IEC is to promote international co-operation on all questions concerning
standardization in the electrical and electronic fields. To this end and in addition to other
activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as "IEC
Publication(s)"). Their preparation is entrusted to technical committees; any IEC National
Committee interested in the subject dealt with may participate in this preparatory work.
International, governmental and non-governmental organizations liaising with the IEC also
participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two
organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as
possible, an international consensus of opinion on the relevant subjects since each technical
committee has representation from all interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted
by IEC National Committees in that sense. While all reasonable efforts are made to ensure that
the technical content of IEC Publications is accurate, IEC cannot be held responsible for the
way in which they are used or for any misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC
Publications transparently to the maximum extent possible in their national and regional
publications. Any divergence between any IEC Publication and the corres ponding national or
regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies
provide conformity assessment services and, in some areas, access to IEC marks of conformity.
IEC is not responsible for any services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including
individual experts and members of its technical committees and IEC National Committees for
any personal injury, property damage or other damage of any nature whatsoever, whether direct
or indirect, or for costs (including legal fees) and expenses arising out of the publication, use
of, or reliance upon, this IEC Publication or any other IEC Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced
publications is indispensable for the correct application of this publication.
9) IEC draws attention to the possibility that the implementation of this document may involve
the use of (a) patent(s). IEC takes no position concerning the evidence, validity or applicability
of any claimed patent rights in respect thereof. As of the date of publication of this document,
IEC [had/had not] received notice of (a) patent(s), which may be required to implement this
document. However, implementers are cautioned that this may not represent the latest
IEC CDV 60269-100 © IEC 2026
information, which may be obtained from the patent database available at https://patents.iec.ch.
IEC shall not be held responsible for identifying any or all such patent rights.
IEC 60269-100 has been prepared by subcommittee 32B: Low-voltage fuses, of IEC technical
committee 32: Fuses. It is an International Standard.
IEC 60269-1:2024 [1] has been restructured and reissued as IEC 60269-100 and subsequent
parts of 200 and 300 series. The documents IEC 60269-1:2024 [1] and its subsequent parts 2
to 7 cannot be used in conjunction with IEC 60269-100 and its subsequent parts of IEC 60269-
200 series (all parts) and IEC 60269-300 series (all parts), except part 5, which is an
independent guide, currently covering both series of standards.
The restructured IEC 60269 series consist of the following parts, under the general title Low-
voltage fuses:
– IEC 60269-100: General Rules
– IEC 60269-200 series (all parts): Supplementary and modified requirements for utilization
classes
– IEC 60269-300 series (all parts): Supplementary and modified requirements for fuse
systems
– IEC TR 60269-5:2014/AMD1:2020 [2]: Guidance for the application of low-voltage fuses
A comprehensive list of all parts in the IEC 60269 series, published under the general title Low-
voltage fuses, can be found on the IEC website.
The text of this International Standard is based on the following documents:
Draft Report on voting
XX/XX/FDIS XX/XX/RVD
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/publications.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
– reconfirmed,
– withdrawn, or
– revised.
IEC CDV 60269-100 © IEC 2026
Introduction
The IEC 60269 series is a series of International Standards with a very long history. Over the
decades, the structure and the content of its documents has changed and evolved, leading to
a mixture of fuse characteristics (e.g. "gG") and fuse systems defining geometries and specific
requirements.
Based on the developments in the last decades, the IEC 60269 series in its current form is not
easy to apply to new products, nor is it easy to maintain. Therefore, IEC Subcommittee 32B has
decided to start a complete restructuring of the series with the following targets:
– IEC 60269-1 was not "general", it contains requirements for the characteristics "gG" and
"aM" besides other general requirements and tests for fuses; after the restructuring phase,
the new part 100 (this document) contains general requirements and tests only
– other parts of the old IEC 60269 series also contain requirements, that are needed in more
than one subsequent parts; These parts are moved to part 100, as soon as it is needed for
at least two subsequent parts, to avoid duplicated text in subsequent parts
– describe a specific fuse system (e.g. "cylindrical fuses") in one single document, not in every
single document it can be used for
– describe a specific characteristic (e.g. "gG", which is currently defined in three subsequent
parts) in one single document
– to simplify the maintenance of the standard series by reducing the need to maintain only
one document in case of necessary changes
– to enhance and simplify the development of new fuses (e.g. new characteristics) or new
combinations of fuse system and characteristic by the ability to combine these documents
in new ways
– To align the IEC US systems with the UL series of standards
– Clear and identical structure throughout the whole series of standards
– Harmonisation of requirements and tests defined in the different subsequent parts (as far
as possible)
This document defines general requirements and tests for fuses, and it is the first part to be
released within the new series. Annex A in this document provides a comprehensive list of
documents planned to represent the new structure.
At this first stage of the restructuring project, it was agreed that the technical changes should
be kept to a minimum, so that the adaptation to the new series is as easy as possible. Some
minor changes had to be made though, since the thorough rework of the documents and the
collection of requirements unveiled some errors and/or misunderstandings that have been
corrected or clarified.
The newly structured IEC 60269 series is applied as a combination of three documents: part
100 (this document) defining the general requirements, one part of 200 series to define
supplementary or modified requirements for a specific utilization class, and one part of 300
series to define supplementary or modified requirements for a specific fuse system. Single
documents are not intended to be used alone.
IEC CDV 60269-100 © IEC 2026
1 Scope
This part of IEC 60269 series is applicable to fuses incorporating enclosed current-limiting fuse-
links with rated breaking capacities of not less than 6 kA, intended for protecting power -
frequency AC circuits of rated voltages not exceeding 1 000 V or DC circuits of rated voltages
not exceeding 1 500 V.
Subsequent parts of this document cover supplementary or modified requirements for such
fuses intended for specific conditions of use or applications.
NOTE 1 Modifications of, and supplements to this document that apply for specific types of fuses for particular
applications - for example, certain fuses for rolling stock, automotive applications or fuses for high-frequency circuits
- are covered by separate standards.
NOTE 2 See Annex A for a list of (planned) subsequent parts of this document.
This standard does not apply to miniature fuses as covered by IEC 60127 [3] series.
The requirements defined in this document and its subsequent parts are also applicable to fuse-
links intended to be used in fuse-combination units according to IEC 60947-3 [4].
The object of this standard is to establish the characteristics of fuses or parts of fuses ( fuse-
base , fuse-carrier , fuse-link ) in such a way that they can be replaced by other fuses or parts
of fuses having the same characteristics provided, that they are interchangeable as far as their
dimensions are concerned. For this purpose, this standard and its subsequent parts refer to
– the following characteristics of fuses:
• their rated values
• their dielectric properties
• their temperature rise in normal service
• the power dissipation of the fuse-link and the maximum power acceptance of a fuse-
holder.
• their time-current characteristics
• their breaking capacity
• their cut-off current characteristics and their I t characteristics.
– type test for verification of the characteristics of fuses
– the marking of fuses.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies.
For undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60050-151:2001, International Electrotechnical Vocabulary (IEV) - Part 151: Electrical and
magnetic devices
IEC 60050-428:2024, International Electrotechnical Vocabulary (IEV) - Part 428: Safety of
machinery
IEC 60050-441:1984, International Electrotechnical Vocabulary (IEV) - Part 441: Switchgear,
controlgear and fuses
IEC CDV 60269-100 © IEC 2026
IEC 60050-442:1998, International Electrotechnical Vocabulary (IEV) - Part 442: Electrical
accessories
IEC 60050-482:2004, International Electrotechnical Vocabulary (IEV) - Part 482: Primary and
secondary cells and batteries
IEC 60050-521:2002, International Electrotechnical Vocabulary (IEV) - Part 521:
Semiconductor devices and integrated circuits
IEC 60050-551:1998, International Electrotechnical Vocabulary (IEV) - Part 551: Power
electronics
IEC 60050-651:2014, International Electrotechnical Vocabulary (IEV) - Part 651: Live working
IEC 60050-826:2022, International Electrotechnical Vocabulary (IEV) - Part 826: Electrical
installations
IEC 60364-5-51:2005, Electrical installations of buildings - Part 5-51: Selection and erection of
electrical equipment - Common rules
IEC 60529:1989/AMD2:2013,
IEC 60664-1:2020, Insulation coordination for equipment within low-voltage supply systems -
Part 1: Principles, requirements and tests
IEC 60664-1:2020/AMD1:2025, Amendment 1 - Insulation coordination for equipment within
low-voltage supply systems - Part 1: Principles, requirements and tests
IEC 60695-2-10:2021, Fire hazard testing - Part 2-10: Glowing/hot-wire based test methods -
Glow-wire apparatus and common test procedure
IEC 60695-2-11:2021, Fire hazard testing - Part 2-11: Glowing/hot-wire based test methods -
Glow-wire flammability test method for end products (GWEPT)
IEC 60947-3:2020/AMD1:2025, Amendment 1 - Low-voltage switchgear and controlgear - Part
3: Switches, disconnectors, switch-disconnectors and fuse-combination units
IEC 61140:2016, Protection against electric shock - Common aspects for installation and
equipment
ISO 3:1973, Preferred numbers — Series of preferred numbers
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following
addresses:
– IEC Electropedia: available at https://www.electropedia.org/
– ISO Online browsing platform: available at https://www.iso.org/obp
IEC CDV 60269-100 © IEC 2026
3.1 Fuses and their component parts
3.1.1
fuse
device that by the fusing of one or more of its specially designed and proportioned components
opens the circuit in which it is inserted by breaking the current when this exceeds a given value
for a sufficient time
Note 1 to entry: The fuse comprises all the parts that form the complete device.
Note 2 to entry: Annex G of this document shows a general drawing of a fuse and its parts.
[SOURCE: IEC 60050-441:1984 Chapter 441-18-01]
3.1.2
fuse-holder
combination of the fuse-base (3.1.2.1) with its fuse-carrier (3.1.2.2)
Note 1 to entry: Where, in this standard and its subsequent parts, the term fuse-holder (3.1.2) is used, it covers
both fuse-base (3.1.2.1) and/or fuse-carrier (3.1.2.2), if no clearer distinction is necessary.
[SOURCE: IEC 60050-441:1984 Chapter 441-18-14, modified (added note to entry)]
3.1.2.1
fuse-base
fuse-mount
fixed part of a fuse (3.1.1) provided with contacts and terminals
Note 1 to entry: Where applicable, covers are considered as part of the fuse-base (3.1.2.1).
[SOURCE: IEC 60050-441:1984 Chapter 441-18-02, modified (added note to entry)]]
3.1.2.2
fuse-carrier
movable part of a fuse (3.1.1) designed to carry a fuse-link (3.1.3)
[SOURCE: IEC 60050-441:1984 Chapter 441-18-13]
3.1.3
fuse-link
fuse-links
part of a fuse (3.1.1) including the fuse-element (3.1.5)(s), intended to be replaced after the
fuse (3.1.1) has operated
[SOURCE: IEC 60050-441:1984 Chapter 441-18-09 modified (brackets removed)]
3.1.4
fuse-contact
two or more conductive parts designed to ensure circuit continuity between a fuse-link (3.1.3)
and the corresponding fuse-holder (3.1.2)
Note 1 to entry: a fuse-contact (3.1.4) can either be a fuse-base contact according to IEC 60050-441:1984 Chapter
441-18-03, or a fuse-link contact according to IEC 60050-441:1984 chapter 441-15-04, or a fuse-carrier contact
according to IEC 60050-441:1984 Chapter 441-18-05.
3.1.5
fuse-element
part of the fuse-link (3.1.3) designed to melt under the action of current exceeding some definite
value for a definite period
Note 1 to entry: The fuse-link (3.1.3) may comprise several fuse-elements in parallel.
IEC CDV 60269-100 © IEC 2026
[SOURCE: IEC 60050-441:1984 Chapter 441-18-08, modified (added note to entry)]
3.1.6
indicating device
indicator
part of a fuse (3.1.1) provided to indicate whether the fuse-link (3.1.3) has operated
[SOURCE: IEC 60050-441:1984 Chapter 441-18-17]
3.1.7
striker
mechanical device forming part of a fuse-link (3.1.3) which, when the fuse-link (3.1.3) operates,
releases the energy required to cause operation of other apparatus or indicators or to provide
interlocking
[SOURCE: IEC 60050-441:1984 Chapter 441-18-18]
3.1.8
signalling device
fuse monitoring