Multi-element metallic cables used in analogue and digital communication and control - Part 2-1: Sectional specification for screened cables characterised up to 100 MHz - Horizontal and building backbone cables

EN 50288-2-1 is a sectional specification for screened cables, characterised from 1 MHz up to 100 MHz, to be used in horizontal and building backbone wiring as defined in EN 50173. This sectional specification contains the electrical, mechanical, transmission and environmental performance characteristics of the cables, when tested in accordance with the referenced test methods. This sectional specification is to be read in conjunction with EN 50288-1, which contains the essential provisions for its application. The cables covered in this sectional specification are intended to operate with voltages and currents normally encountered in communication systems. These cables are not intended to be used in conjunction with low impedance sources, for example, the electric power supplies of public utility mains.

Mehradrige metallische Daten- und Kontrollkabel für analoge und digitale Übertragung - Teil 2-1: Rahmenspezifikation für geschirmte Kabel bis 100 MHz - Kabel für den Horizontal- und Steigbereich

Câbles métalliques à éléments multiples utilisés pour les transmissions et les commandes analogiques et numériques - Partie 2-1: Spécification intermédiaire pour les câbles blindés pour applications jusqu'à 100 MHz - Câbles horizontaux et verticaux de bâtiment

Večelementni kovinski kabli za analogne in digitalne komunikacije in krmiljenje - 2-1. del: Področna specifikacija za zaslonjene kable z lastnostmi do 100 MHz - Hrbtenični kabli za vodoravno montažo in montažo v stavbah

Standard EN 50288-2-1 je področna specifikacija za zaslonjene kable, ki se lahko uporabljajo za pasovne širine od 1 MHz do 100 MHz v vodoravnem (etažnem) in stavbnem hrbteničnem (medetažnem) ožičenju, kot je določeno v standardu EN 50173. Ta področna specifikacija vsebuje električne, mehanske, prenosne in okoljske karakteristike delovanja kablov pri preskušanju v skladu z navedenimi preskusnimi metodami. Ta področna specifikacija se uporablja skupaj s standardom EN 50288-1, ki vsebuje bistvene določbe za njeno uporabo. Kabli, zajeti v tej področni specifikaciji, so namenjeni za delovanje pri napetostih in tokovih, ki so običajni v komunikacijskih sistemih. Ti kabli niso namenjeni za uporabo z viri z nizko impedanco, na primer z električnim napajanjem javnih omrežij.

General Information

Status
Published
Public Enquiry End Date
28-Mar-2012
Publication Date
10-Sep-2013
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
29-Aug-2013
Due Date
03-Nov-2013
Completion Date
11-Sep-2013

Relations

Buy Standard

Standard
EN 50288-2-1:2013
English language
16 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 50288-2-1:2013
01-oktober-2013
9HþHOHPHQWQLNRYLQVNLNDEOL]DDQDORJQHLQGLJLWDOQHNRPXQLNDFLMHLQNUPLOMHQMH
GHO3RGURþQDVSHFLILNDFLMD]D]DVORQMHQHNDEOH]ODVWQRVWPLGR0+]
+UEWHQLþQLNDEOL]DYRGRUDYQRPRQWDåRLQPRQWDåRYVWDYEDK
Multi-element metallic cables used in analogue and digital communication and control -
Part 2-1: Sectional specification for screened cables characterised up to 100 MHz -
Horizontal and building backbone cables
Mehradrige metallische Daten- und Kontrollkabel für analoge und digitale Übertragung -
Teil 2-1: Rahmenspezifikation für geschirmte Kabel bis 100 MHz - Kabel für den
Horizontal- und Steigbereich
Câbles métalliques à éléments multiples utilisés pour les transmissions et les
commandes analogiques et numériques - Partie 2-1: Spécification intermédiaire pour les
câbles blindés pour applications jusqu'à 100 MHz - Câbles horizontaux et verticaux de
bâtiment
Ta slovenski standard je istoveten z: EN 50288-2-1:2013
ICS:
33.120.20 äLFHLQVLPHWULþQLNDEOL Wires and symmetrical
cables
SIST EN 50288-2-1:2013 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 50288-2-1:2013

---------------------- Page: 2 ----------------------

SIST EN 50288-2-1:2013

EUROPEAN STANDARD
EN 50288-2-1

NORME EUROPÉENNE
May 2013
EUROPÄISCHE NORM

ICS 33.120.10 Supersedes EN 50288-2-1:2003

English version

Multi-element metallic cables used in analogue and digital communication
and control -
Part 2-1: Sectional specification for screened cables characterised
up to 100 MHz -
Horizontal and building backbone cables


Câbles métalliques à éléments multiples Mehradrige metallische Daten- und
utilisés pour les transmissions et les Kontrollkabel für analoge und digitale
commandes analogiques et numériques - Übertragung -
Partie 2-1: Spécification intermédiaire Teil 2-1: Rahmenspezifikation für
pour les câbles blindés pour applications geschirmte Kabel bis 100 MHz -
jusqu'à 100 MHz - Kabel für den Horizontal- und
Câbles horizontaux et verticaux de Steigbereich
bâtiment





This European Standard was approved by CENELEC on 2013-03-18. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the CEN-CENELEC Management Centre or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the CEN-CENELEC Management Centre has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany,
Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland,
Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Management Centre: Avenue Marnix 17, B - 1000 Brussels


© 2013 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50288-2-1:2013 E

---------------------- Page: 3 ----------------------

SIST EN 50288-2-1:2013
EN 50288-2-1:2013 - 2 -



Contents
Page
Foreword . 3
1 Scope . 4
2 Normative references. 4
3 Terms, definitions, symbols and abbreviations . 4
3.1 Terms and definitions . 4
3.2  Symbols and abbreviations . 5
4 Cable construction . 5
4.1 Conductor . 5
4.2 Insulation . 5
4.3 Cabling elements . 5
4.4 Identification of cabling elements . 5
4.5 Screening of cabling elements . 5
4.6 Cable make-up . 5
4.7 Filling compound . 5
4.8 Interstitial fillers . 5
4.9 Screening of the cable core . 5
4.10 Moisture barriers . 5
4.11 Wrapping layers . 6
4.12 Sheath . 6
5 Tests and requirements for completed cables . 6
5.1 Electrical tests . 6
5.2 Mechanical test requirements . 9
5.3 Environmental tests . 10
5.4 Fire performance tests . 10
Annex A (informative) Maximum voltage, current and temperature rating for cables used
for POE applications . 11
Annex B (informative) Blank Detail Specification . 12

---------------------- Page: 4 ----------------------

SIST EN 50288-2-1:2013
- 3 - EN 50288-2-1:2013

Foreword
This document (EN 50288-2-1:2013) has been prepared by CLC/SC 46XC "Multicore, Multipair and
Quad Data communication cables," of CLC/TC 46X, "Communication cables".
The following dates are fixed:
• latest date by which this document has to
(dop) 2014-03-18
be implemented at national level by publication
of an identical national standard or by
endorsement
• latest date by which the national standards
(dow) 2016-03-18
conflicting with this document have to
be withdrawn
This document supersedes EN 50288-2-1:2003.
EN 50288-2-1:2013 includes the following significant technical changes with respect to EN 50288-2-
1:2003:
- the addition of the Blank Detail Specification Annex;
- a number minor corrections and updating of references;
- the re-classification of ‘ELFEXT’ to ‘ACR-F’.
This Part 2-1 is to be read in conjunction with EN 50288-1.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such
patent rights.
This standard covers the Principle Elements of the Safety Objectives for Electrical Equipment
Designed for Use within Certain Voltage Limits (LVD - 2006/95/EC)

---------------------- Page: 5 ----------------------

SIST EN 50288-2-1:2013
EN 50288-2-1:2013 - 4 -


1 Scope
EN 50288-2-1 is a sectional specification for screened cables, characterised from 1 MHz up to
100 MHz, to be used in horizontal and building backbone wiring as defined in EN 50173.
This sectional specification contains the electrical, mechanical, transmission and environmental
performance characteristics of the cables, when tested in accordance with the referenced test
methods.
This sectional specification is to be read in conjunction with EN 50288-1, which contains the essential
provisions for its application.
The cables covered in this sectional specification are intended to operate with voltages and currents
normally encountered in communication systems. These cables are not intended to be used in
conjunction with low impedance sources, for example, the electric power supplies of public utility
mains.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies
EN 50173 Series Information technology - Generic cabling systems
EN 50288-1 Multi-element metallic cables used in analogue and digital
communication and control - Part 1: Generic specification
EN 50289 Series Communication cables - Specifications for test methods
EN 50290 Series Communication cables
EN 60811 Series Electric and optical fibre cables - Test methods for non-metallic
materials (IEC 60811 series)
IEC 60189-2 Low-frequency cables and wires with PVC insulation and PVC sheath -
Part 2: Cables in pairs, triples, quads and quintuples for inside
installations
3 Terms, definitions, symbols and abbreviations
3.1 Terms and definitions
For the purposes of this document the terms and definitions given in EN 50288-1 and the following
apply.
3.1.1
screening of cable
a cable is considered screened when the cable core is covered by a continuous conductive layer
forming part of the shielding and grounding system
Note 1 to entry: d.c. continuity has to be given and minimum shielding requirements have to be met.

---------------------- Page: 6 ----------------------

SIST EN 50288-2-1:2013
- 5 - EN 50288-2-1:2013

3.2  Symbols and abbreviations
For the purposes of this document, the following abbreviations apply.
EX Exogenous (derived or originating externally)
POE Power Over Ethernet
4 Cable construction
4.1 Conductor
The conductor shall be solid copper and meet the requirements of EN 50288-1, 4.1. The conductor
shall be plain or metal coated.
The nominal conductor diameter shall be ≥ 0,5 mm and ≤ 0,8 mm.
NOTE  Constructions with ‘copper clad’ conductors do not meet the requirements.
4.2 Insulation
The insulation shall be of a suitable material according to the relevant part of EN 50290-2.
4.3 Cabling elements
The cable element shall be a pair or a quad.
4.4 Identification of cabling elements
Unless otherwise specified, the colour coding for identification is given in IEC 60189-2. The colours
shall meet the requirements of EN 50288-1, 4.4
4.5 Screening of cabling elements
Where appropriate, screening of the cabling elements shall be applied in accordance with 4.5 of
EN 50288-1. Coverage is defined in EN 50290-2-1.
4.6 Cable make-up
The cable elements shall be laid up in concentric layer(s) or units to form the cable core.
4.7 Filling compound
Not applicable.
4.8 Interstitial fillers
Where fillers are used they shall meet the requirements of EN 50288-1, 4.8
4.9 Screening of the cable core
The screening of the cable core shall be applied in accordance with EN 50288-1, 4.9. Coverage is
defined in EN 50290-2-1.
4.10 Moisture barriers
Not applicable.

---------------------- Page: 7 ----------------------

SIST EN 50288-2-1:2013
EN 50288-2-1:2013 - 6 -

4.11 Wrapping layers
Where wrapping layers are used they shall be in accordance with 4.11 of EN 50288-1.
4.12 Sheath
The sheath shall be of a suitable material according to the relevant part of EN 50290-2.
5 Tests and requirements for completed cables
The following tables give the tests to be applied, together with the respective limits, in order to
demonstrate compliance with this specification.
5.1 Electrical tests
5.1.1 Low-frequency and d.c. electrical measurements
Table 1 - Low-frequency and d.c. electrical measurements
EN 50288-1 Parameter Requirement
sub-clause
5.1.1.1 Conductor loop resistance
≤ 19,0 Ω/100 m
5.1.1.2 Conductor resistance unbalance
≤ 2,0 %
5.1.1.3 Dielectric strength 1,0 kV d.c. or 0,7 kV a.c. for 1 min
conductor/conductor or
and conductor/screen 2,5 kV d.c. or 1,7 kV a.c. for 2 s
5.1.1.4 Insulation resistance
≥ 5 000 MΩ km when tested in accordance with
EN 50289-1-4
5.1.1.5 Mutual capacitance No requirement specified
5.1.1.6 Capacitance unbalance to earth
≤ 1 200 pF/km

---------------------- Page: 8 ----------------------

SIST EN 50288-2-1:2013
- 7 - EN 50288-2-1:2013


5.1.2 High-frequency electrical and transmission requi
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.