Conduit systems for cable management -- Part 1: General requirements

This part of IEC 61386 specifies requirements and tests for conduit systems, including conduits and conduit fittings, for the protection and management of insulated conductors and/or cables in electrical installations or in communication systems up to 1 000 V a.c. and/or 1 500 V d.c. This standard applies to metallic, non-metallic and composite conduit systems, including threaded and non-threaded entries which terminate the system. This standard does not apply to enclosures and connecting boxes which come within the scope of IEC 60670.

Elektroinstallationsrohrsysteme für elektrische Energie und für Informationen -- Teil 1: Allgemeine Anforderungen

Systèmes de conduits pour la gestion du câblage -- Partie 1: Exigences générales

La présente partie de la CEI 61386 spécifie les règles et les essais applicables aux systèmes de conduits, incluant conduits et accessoires de conduits, pour la protection et le rangement des conducteurs et/ou des câbles isolés dans les installations électriques ou les systèmes de télécommunication jusqu'à 1 000 V c.a. et/ou 1 500 V c.c. Cette deuxième édition annule et remplace la première édition publiée en 1996 et son Amendement 1 (2000), et constitue une révision technique. Les modifications par rapport à la première édition sont les suivantes:  - modification de la longueur de l'échantillon d'essai entre accessoires pour l'essai de traction,  - mises à jour éditoriales et des références normatives.

Sistemi kanalov za električne inštalacije - 1. del: Splošne zahteve (IEC 61386-1:2008)

Ta del standarda IEC 61386 določa zahteve in preskuse za sisteme kanalov, vključno s kanali in nastavki za kanale, za zaščito in upravljanje izoliranih vodnikov in/ali kablov pri električnih inštalacijah ali komunikacijskih sistemih do 1000 V AC in/ali 1500 V DC. Ta standard se uporablja za kovinske, nekovinske in kompozitne sisteme kanalov, vključno z navojnimi in nenavojnimi vhodi, ki zaključujejo sistem. Ta standard se ne uporablja za ohišja in priključne doze v okviru standarda IEC 60670.

General Information

Status
Published
Publication Date
22-Sep-2008
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
15-Sep-2008
Due Date
20-Nov-2008
Completion Date
23-Sep-2008

Relations

Buy Standard

Standard
EN 61386-1:2008
English language
42 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 61386-1:2008
01-november-2008
1DGRPHãþD
SIST EN 61386-1:2004
6LVWHPLNDQDORY]DHOHNWULþQHLQãWDODFLMHGHO6SORãQH]DKWHYH ,(&

Conduit systems for cable management - Part 1: General requirements (IEC 61386-
1:2008)
Elektroinstallationsrohrsysteme für elektrische Energie und für Informationen - Teil 1:
Allgemeine Anforderungen (IEC 61386-1:2008)
Systèmes de conduits pour la gestion du câblage - Partie 1: Exigences générales (CEI
61386-1:2008)
Ta slovenski standard je istoveten z: EN 61386-1:2008
ICS:
29.120.10 ,QãWDODFLMVNHFHYL]D Conduits for electrical
HOHNWULþQHQDPHQH purposes
SIST EN 61386-1:2008 en,fr
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 61386-1:2008

---------------------- Page: 2 ----------------------

SIST EN 61386-1:2008

EUROPEAN STANDARD
EN 61386-1

NORME EUROPÉENNE
August 2008
EUROPÄISCHE NORM

ICS 29.120.10 Supersedes EN 61386-1:2004


English version


Conduit systems for cable management -
Part 1: General requirements
(IEC 61386-1:2008)


Systèmes de conduits  Elektroinstallationsrohrsysteme
pour la gestion du câblage - für elektrische Energie
Partie 1: Exigences générales und für Informationen -
(CEI 61386-1:2008) Teil 1: Allgemeine Anforderungen
(IEC 61386-1:2008)




This European Standard was approved by CENELEC on 2008-06-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2008 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 61386-1:2008 E

---------------------- Page: 3 ----------------------

SIST EN 61386-1:2008
EN 61386-1:2008 - 2 -
Foreword
The text of document 23A/553/FDIS, future edition 2 of IEC 61386-1, prepared by SC 23A, Cable
management systems, of IEC TC 23, Electrical accessories, was submitted to the IEC-CENELEC parallel
vote and was approved by CENELEC as EN 61386-1 on 2008-06-01.
This European Standard supersedes EN 61386-1:2004 + corrigendum April 2004.
The changes to EN 61386-1:2004 are as follows:
– change to the length of the test specimen between fittings for the tensile test,
– editorial and normative reference updates.
The following dates were fixed:

– latest date by which the EN has to be implemented

at national level by publication of an identical
(dop) 2009-03-01
national standard or by endorsement

– latest date by which the national standards conflicting
(dow) 2011-06-01
with the EN have to be withdrawn
This Part 1 is to be used in conjunction with the appropriate Part 2, which contains clauses to supplement
or modify the corresponding clauses in Part 1, to provide the relevant particular requirements for each
type of product. A conduit system which conforms to this standard is deemed safe for use.
In this publication, the following print types are used:
– Requirements proper: in roman type.
– Test specifications: in italic type.
– Explanatory matter: in smaller roman type.
For this European Standard the references to Austria and Australia in Subclauses 6.5.2 and 13.1.4 of
IEC 61386-1:2008 shall be disregarded and have been replaced by the normative Annex ZB, Special
national conditions.
Annexes ZA and ZB have been added by CENELEC.
__________
Endorsement notice
The text of the International Standard IEC 61386-1:2008 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards indicated:
IEC 60670 NOTE  Harmonized in EN 60670 series (modified).
IEC 60754-1 & NOTE  See EN 50267 series, Common test methods for cables under fire conditions - Tests on
IEC 60754-2 gases evolved during combustion of materials from cables .
__________

---------------------- Page: 4 ----------------------

SIST EN 61386-1:2008
- 3 - EN 61386-1:2008

Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications

The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.

NOTE  When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.

Publication Year Title EN/HD Year

IEC 60417 Data- Graphical symbols for use on equipment - -
base


IEC 60423 2007 Conduit systems for cable management - EN 60423 2007
Outside diameters of conduits for electrical
installations and threads for conduits and
fittings


IEC 60529 1989 Degrees of protection provided by enclosures EN 60529 1991
 (IP Code) + corr. May 1993
A1 1999 A1 2000


IEC 60695-2-11 2000 Fire hazard testing - EN 60695-2-11 2001
Part 2-11: Glowing/hot-wire based test
methods - Glow-wire flammability test method
for end-products


IEC 60695-11-2 2003 Fire hazard testing - EN 60695-11-2 2003
Part 11-2: Test flames - 1 kW nominal pre-
mixed flame - Apparatus, confirmatory test
arrangement and guidance

---------------------- Page: 5 ----------------------

SIST EN 61386-1:2008
EN 61386-1:2008 - 4 -
Annex ZB
(normative)

Special national conditions
Special national condition: National characteristic or practice that cannot be changed even over a long
period, e.g. climatic conditions, electrical earthing conditions.
NOTE  If it affects harmonization, it forms part of the European Standard / Harmonization Document.
For the countries in which the relevant special national conditions apply these provisions are normative,
for other countries they are informative.
Clause Special national condition
6.5.2 Austria
Conduits and conduit fittings may be classified with low acid gas emission.
13.1.4 Austria
Conduits and conduit fittings classified as low acid gas emission shall be tested in
accordance with EN 50267-1 and EN 50267-2-2.
__________

---------------------- Page: 6 ----------------------

SIST EN 61386-1:2008
IEC 61386-1
Edition 2.0 2008-02
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE


Conduit systems for cable management –
Part 1: General requirements

Systèmes de conduits pour la gestion du câblage –
Partie 1: Exigences générales

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
W
CODE PRIX
ICS 29.120.10 ISBN 2-8318-9623-1

---------------------- Page: 7 ----------------------

SIST EN 61386-1:2008
– 2 – 61386-1 © IEC:2008
CONTENTS
FOREWORD.4

1 Scope.6
2 Normative references .6
3 Terms and definitions .6
4 General requirements .8
5 General conditions for tests.8
6 Classification.9
6.1 According to mechanical properties .9
6.1.1 Resistance to compression.9
6.1.2 Resistance to impact .9
6.1.3 Resistance to bending .10
6.1.4 Tensile strength.10
6.1.5 Suspended load capacity.10
6.2 According to temperature .10
6.2.1 Lower temperature range.10
6.2.2 Upper temperature range.11
6.3 According to electrical characteristics.11
6.3.1 With electrical continuity characteristics .11
6.3.2 With electrical insulating characteristics .11
6.3.3 With electrical continuity and insulating characteristics.11
6.4 According to resistance to external influences .11
6.4.1 Protection against ingress of solid objects: protection in accordance
with IEC 60529 to a minimum of IP3X.11
6.4.2 Protection against ingress of water: protection in accordance with
IEC 60529 to a minimum of IPX0 .11
6.4.3 Resistance against corrosion.11
6.5 According to resistance to flame propagation .11
6.5.1 Non-flame propagating .11
6.5.2 Flame propagating.11
7 Marking and documentation.11
8 Dimensions .12
9 Construction .12
10 Mechanical properties .14
10.1 Mechanical strength .14
10.2 Compression test .15
10.3 Impact test .15
10.4 Bending test .16
10.5 Flexing test .16
10.6 Collapse test .16
10.7 Tensile test .16
10.8 Suspended load test.17
11 Electrical properties.18
11.1 Electrical requirements.18
11.2 Bonding test .18
11.3 Dielectric strength and insulation resistance.19

---------------------- Page: 8 ----------------------

SIST EN 61386-1:2008
61386-1 © IEC:2008 – 3 –
12 Thermal properties .20
13 Fire hazard.21
13.1 Reaction to fire.21
13.1.1 Initiation of fire .21
13.1.2 Contribution to fire.21
13.1.3 Spread of fire .21
13.1.4 Additional reaction to fire characteristics .23
13.2 Resistance to fire .23
14 External influences .23
14.1 Degree of protection provided by enclosure.23
14.1.1 General .23
14.1.2 Degree of protection – Ingress of foreign solid objects.23
14.1.3 Degree of protection – Ingress of water .23
14.2 Resistance against corrosion.24
15 Electromagnetic compatibility .25

Annex A (normative) Classification coding for conduit systems .33
Annex B (normative) Determination of material thickness.36

Bibliography.38

Figure 1 – Arrangement for compression test.26
Figure 2 – Impact test apparatus.26
Figure 3 – Assembly of conduit and conduit fitting for bonding test .27
Figure 4 – Arrangement for dielectric strength and insulation resistance tests – Rigid
conduit.28
Figure 5 – Arrangement for dielectric strength and insulation resistance tests – Pliable
and flexible conduit.29
Figure 6 – Steel enclosure for test for resistance to flame propagation .30
Figure 7 – Test arrangement for resistance to flame propagation .31
Figure 8 – Test apparatus for resistance to heat .32

Table 1 – Lower temperature range .10
Table 2 – Upper temperature range .11
Table 3 – Torque values for screw tests.14
Table 4 – Compression force .15
Table 5 – Impact test values .16
Table 6 – Tensile force .17
Table 7 – Suspended load .18
Table 8 – Load for heating test .20
Table 9 – Times of exposure of the sample to the flame .22
Table 10 – Resistance to corrosion classification .24

---------------------- Page: 9 ----------------------

SIST EN 61386-1:2008
– 4 – 61386-1 © IEC:2008
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________

CONDUIT SYSTEMS FOR CABLE MANAGEMENT –

Part 1: General requirements


FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61386-1 has been prepared by subcommittee 23A: Cable
management systems, of IEC technical committee 23: Electrical accessories.
This second edition cancels and replaces the first edition published in 1996, and its
Amendment 1 (2000), and it constitutes a technical revision. The changes to the first edition
are as follows:
– change to the length of the test specimen between fittings for the tensile test,
– editorial and normative reference updates.

---------------------- Page: 10 ----------------------

SIST EN 61386-1:2008
61386-1 © IEC:2008 – 5 –
The text of this standard is based on the following documents:
FDIS Report on voting
23A/553/FDIS 23A/558/RVD

Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all the parts in the IEC 61386 series, under the general title Conduit systems for cable
management, can be found on the IEC website.
This Part 1 is to be used in conjunction with the appropriate Part 2, which contains clauses to
supplement or modify the corresponding clauses in Part 1, to provide the relevant particular
requirements for each type of product. A conduit system which conforms to this standard is
deemed safe for use.
In this publication, the following print types are used:
– Requirements proper: in roman type.
– Test specifications: in italic type.
Explanatory matter: in smaller roman type.

The following differences exist in some countries:
6.5.2: In Australia and Austria, conduits and conduit fittings may be classified with low acid
gas emission.
13.1.4: In Australia conduits and conduit fittings classified as low acid gas emission shall be
tested in accordance with IEC 60754-1, evolve not more than the equivalent of 5 mg of
hydrochloride-acid per gram of sample.
In Austria conduits and conduit fittings classified as low acid gas emission shall be tested in
accordance with IEC 60754-2.
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.

---------------------- Page: 11 ----------------------

SIST EN 61386-1:2008
– 6 – 61386-1 © IEC:2008
CONDUIT SYSTEMS FOR CABLE MANAGEMENT –

Part 1: General requirements



1 Scope
This part of IEC 61386 specifies requirements and tests for conduit systems, including
conduits and conduit fittings, for the protection and management of insulated conductors
and/or cables in electrical installations or in communication systems up to 1 000 V a.c. and/or
1 500 V d.c. This standard applies to metallic, non-metallic and composite conduit systems,
including threaded and non-threaded entries which terminate the system. This standard does
not apply to enclosures and connecting boxes which come within the scope of IEC 60670.
NOTE 1 Certain conduit systems may also be suitable for use in hazardous atmospheres. Regard should then be
taken of the extra requirements necessary for equipment to be installed in such conditions.
NOTE 2 Earthing conductors may or may not be insulated.
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 60417, Graphical symbols for use on equipment
IEC 60423:2007, Conduit systems for cable management – Outside diameters of conduits for
electrical installations and threads for conduits and fittings
IEC 60529:1989, Degrees of protection provided by enclosures (IP Code)
Amendment 1 (1999)
IEC 60695-2-11:2000, Fire hazard testing – Part 2-11: Glowing/hot-wire based test methods -
Glow-wire flammability test method for end-products
IEC 60695-11-2:2003, Fire hazard testing – Part 11-2: Test flames - 1 kW nominal pre-mixed
flame - Apparatus, confirmatory test arrangement and guidance
3 Terms and definitions
For the purposes of this document, the following definitions apply:
3.1
conduit system
cable management system consisting of conduits and conduit fittings for the protection and
management of insulated conductors and/or cables in electrical or communication
installations, allowing them to be drawn in and/or replaced, but not to be inserted laterally

---------------------- Page: 12 ----------------------

SIST EN 61386-1:2008
61386-1 © IEC:2008 – 7 –
3.2
conduit
part of conduit system of circular cross-section for insulated conductors and/or cables in
electrical or communication installations, allowing them to be drawn in and/or replaced
3.3
conduit fitting
device designed to join components of a conduit system, or for them to change direction
3.4
terminating conduit fitting
conduit fitting that terminates a conduit system
3.5
metallic conduit and/or conduit fitting
conduit or conduit fitting which consists of metal only
3.6
non-metallic conduit and/or conduit fitting
conduit or conduit fitting which consists uniquely of non-metallic material and which has no
metallic components whatsoever
3.7
composite conduit and/or conduit fitting
conduit or conduit fitting comprising both metallic and non-metallic materials
3.8
non-flame propagating conduit and/or conduit fitting
conduit or conduit fitting which is liable to catch fire as a result of an applied flame, but in
which the flame does not propagate, and which extinguishes itself within a limited time after
the flame is removed
3.9
plain conduit
conduit in which the profile is even in the longitudinal section (see note to 3.10)
3.10
corrugated conduit
conduit in which the profile is corrugated in the longitudinal section
NOTE Both annular and helical corrugated conduits are permissible, and a combination of both corrugated and
plain conduit is possible.
3.11
rigid conduit
conduit which cannot be bent, or which can only be bent with the help of a mechanical aid,
with or without special treatment
3.12
pliable conduit
conduit which can be bent by hand with reasonable force, and which is not intended for
frequent flexing
3.13
flexible conduit
conduit which can be bent by hand with reasonable small force, and which is intended to flex
frequently throughout its life

---------------------- Page: 13 ----------------------

SIST EN 61386-1:2008
– 8 – 61386-1 © IEC:2008
3.14
self-recovering conduit
pliable conduit which deforms when a transverse force is applied for a short time and which,
after removal of this force, returns close to its original shape within a further short time
3.15
threadable conduit and conduit fitting
conduit and conduit fittings which carry a thread for connection, or in or on which a thread can
be formed
3.16
non-threadable conduit and conduit fitting
conduit and conduit fittings which are suitable for connection only by means other than
threads
3.17
external influence
factors which may affect the conduit system
NOTE Examples of such factors are a presence of water, oil or building materials, low and high temperatures, and
corrosive or polluting substances.
4 General requirements
4.1 Conduit and conduit fittings shall be so designed and constructed that in normal use
their performance is reliable and they provide protection to the user or surroundings.
When assembled in accordance with manufacturer's instructions as part of a conduit system,
conduits and conduit fittings shall provide mechanical and, where required, electrical
protection of the insulated conductors and cables contained therein.
4.2 The protective properties of the joint between the conduit and conduit fitting shall not be
less than that declared for the conduit system.
4.3 Conduit and conduit fittings shall withstand the stresses likely to occur during transport,
storage, recommended installation practice and application.
4.4 Compliance is checked by carrying out all specified tests.
5 General conditions for tests
5.1 Tests in accordance with this standard are type tests. Conduit systems, having the same
classification, which can vary in colour only, shall be the same product type.
5.2 Unless otherwise specified, the tests shall be carried out at an ambient temperature of
°
(20 ± 5) C.
5.3 Unless otherwise specified, each test shall be made on three new samples, which may
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.