Fire detection and fire alarm system - Part 31: Multi-sensor fire detectors - Point detectors using a combination of smoke, carbon monoxide and optionally heat sensors

This European Standard specifies requirements, test methods and performance criteria for point-type multi-sensor fire detectors for use in fire detection systems installed in buildings (see EN 54-1:1996), incorporating in one mechanical enclosure at least one optical or ionization smoke sensor and at least one carbon monoxide (CO) sensor and optionally one or more heat sensors. The overall fire detection performance is determined utilizing the combination of the detected phenomena.
This European standard specifies the evaluation of conformity (EoC) and the marking of the products concerned (i.e. multi-sensor fire detectors).
Multi-sensor fire detectors having special characteristics suitable for the detection of specific fire risks are not covered by this standard. The performance requirements for any additional functions are beyond the scope of this standard (e.g. additional features or enhanced functionality for which this standard does not define a test or assessment method).
NOTE   Certain types of detector contain radioactive materials. The national requirements for radiation protection differ from country to country and they are not specified in this standard.

Brandmeldeanlagen - Teil 31: Mehrfachsensor-Brandmelder-Punktförmige Melder mit Kombinierten Rauch-, CO-und optionalen Wärmesensoren

Diese Europäische Norm legt Anforderungen, Prüfverfahren und Leistungsmerkmale für punktförmige Mehrfachsensor-Brandmelder fest, die in Brandmeldeanlagen für Gebäude eingesetzt werden (siehe EN 54-1:1996) und die in einem Gehäuse mindestens einen Rauchsensor nach dem Durchlicht- oder Ionisationsprinzip und mindestens einen Kohlenmonoxid-(CO-)Sensor sowie optional einen oder mehrere Wärmesensoren enthalten. Ihre Gesamtleistung bei der Brandmeldung ergibt sich aus der Kombination der erkannten Brandphänomene.
Diese Europäische Norm legt Anforderungen an die Konformitätsbewertung und die Kennzeichnung der betreffenden Produkte fest (d. h. Mehrfachsensor-Brandmelder).
Mehrfachsensormelder mit speziellen Merkmalen, geeignet für die Erkennung besonderer Brandrisiken, sind nicht Gegenstand dieser Norm. Die Leistungsanforderungen an alle zusätzlichen Funktionen fallen nicht in den Anwendungsbereich dieser Norm (z. B. werden in dieser Norm für zusätzliche Merkmale oder für eine verbesserte Funktionstüchtigkeit keine Prüf- oder Bewertungsverfahren festgelegt).
ANMERKUNG Einige Meldertypen enthalten radioaktive Stoffe. Die nationalen Anforderungen für den Schutz gegen ionisierende Strahlung sind in den Ländern unterschiedlich und werden deshalb in der vorliegenden Norm nicht festgelegt.

Systèmes de détection et d'alarme incendie - Partie 31 : Détecteurs d'incendie multicapteurs - Détecteurs ponctuels combinant l'utilisation de capteurs de fumée, de capteurs de monoxyde de carbone et éventuellement de capteurs de chaleur

La présente Norme européenne spécifie les exigences, les méthodes d’essai et les critères de performance applicables aux détecteurs d’incendie ponctuels multicapteurs destinés à être utilisés dans les systèmes de détection d’incendie et d'alarme incendie installés dans les bâtiments et aux alentours (voir EN 54 1:2011), incorporant dans une seule enveloppe mécanique au moins un capteur de fumée optique ou à ionisation et au moins un capteur de monoxyde de carbone (CO) et éventuellement un ou plusieurs capteurs de chaleur, en utilisant la combinaison des phénomènes détectés. La présente Norme européenne traite uniquement des modes de fonctionnement, dans lesquels au moins les signaux des capteurs de fumée et des capteurs de monoxyde de carbone sont évalués en continu.
La présente Norme européenne prévoit l'évaluation et la vérification de la constance des performances (EVCP) des détecteurs ponctuels combinant l’utilisation de capteurs de fumée, de capteurs de monoxyde de carbone et éventuellement de capteurs de chaleur de la présente Norme européenne.
Les détecteurs ponctuels combinant l’utilisation de capteurs de fumée, de capteurs de monoxyde de carbone et éventuellement de capteurs de chaleur possédant des caractéristiques particulières adaptées à la détection de risques d’incendie spécifiques ne sont pas pris en compte dans la présente Norme européenne. Les exigences de performance relatives à toute autre fonction ne relèvent pas du domaine d’application de la présente norme (par exemple, des caractéristiques supplémentaires ou une fonctionnalité améliorée pour lesquelles la présente Norme européenne ne définit pas d’essai ou de méthode d’évaluation).

Sistemi za odkrivanje in javljanje požara ter alarmiranje - 31. del: Večsenzorski javljalniki  požara - Kombinirani točkovni javljalniki požara s senzorji za zaznavanje dima, ogljikovega monoksida in izbrane toplote

Ta evropski standard določa zahteve, preskusne metode in merila učinkovitosti za točkovne večsenzorske javljalnike požara za uporabo v sistemih za odkrivanje in javljanje požara, nameščenih v stavbah (glej EN 54-1:1996), ki v enem mehanskem ohišju vsebujejo najmanj en optični ali ionizacijski senzor za zaznavanje dima in vsaj en senzor za zaznavanje ogljikovega monoksida (CO) ter izbirno en ali več senzorjev toplote. Skupna učinkovitost odkrivanja požara se določi z uporabo kombinacije odkritih pojavov.
Ta evropski standard določa vrednotenje skladnosti (EoC) in označevanje zadevnih izdelkov (tj. večsenzorskih javljalnikov požara).
Večsenzorski javljalniki požara s posebnimi lastnostmi, primernimi za odkrivanje posebnih tveganj za nastanek požara, niso zajeti v tem standardu. Zahteve glede učinkovitosti za katere koli dodatne funkcije se v tem standardu ne obravnavajo (npr. dodatne funkcije ali izboljšana funkcionalnost, za katero ta standard ne določa preskusne ali ocenjevalne metode).
OPOMBA Nekatere vrste javljalnikov vsebujejo radioaktivne materiale. Nacionalne zahteve za zaščito pred sevanjem se razlikujejo po posameznih državah in niso določene v tem standardu.

General Information

Status
Withdrawn
Public Enquiry End Date
29-Jun-2012
Publication Date
19-Jan-2015
Withdrawal Date
19-May-2016
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
20-May-2016
Due Date
12-Jun-2016
Completion Date
20-May-2016

Relations

Buy Standard

Standard
EN 54-31:2015
English language
113 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 54-31:2015
01-februar-2015
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO9HþVHQ]RUVNL
MDYOMDOQLNLSRåDUD.RPELQLUDQLWRþNRYQLMDYOMDOQLNLSRåDUDVVHQ]RUML]D
]D]QDYDQMHGLPDRJOMLNRYHJDPRQRNVLGDLQL]EUDQHWRSORWH
Fire detection and fire alarm system - Part 31: Multi-sensor fire detectors - Point
detectors using a combination of smoke, carbon monoxide and optionally heat sensors
Brandmeldeanlagen - Teil 31: Mehrfachsensor-Brandmelder-Punktförmige Melder mit
Kombinierten Rauch-, CO-und optionalen Wärmesensoren
Systèmes de détection et d'alarme incendie - Partie 31 : Détecteurs d'incendie
multicapteurs - Détecteurs ponctuels combinant l'utilisation de capteurs de fumée, de
capteurs de monoxyde de carbone et éventuellement de capteurs de chaleur
Ta slovenski standard je istoveten z: EN 54-31:2014
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
SIST EN 54-31:2015 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 54-31:2015

---------------------- Page: 2 ----------------------

SIST EN 54-31:2015

EUROPEAN STANDARD
EN 54-31

NORME EUROPÉENNE

EUROPÄISCHE NORM
December 2014
ICS 13.220.20
English Version
Fire detection and fire alarm system - Part 31: Multi-sensor fire
detectors - Point detectors using a combination of smoke,
carbon monoxide and optionally heat sensors
Systèmes de détection et d'alarme incendie - Partie 31: Brandmeldeanlagen - Teil 31: Mehrfachsensor-
Détecteurs d'incendie multicapteurs - Détecteurs ponctuels Brandmelder - Punktförmige Melder mit kombinierten
combinant l'utilisation de capteurs de fumée, de capteurs Rauch-, CO- und optionalen Wärmesensoren
de monoxyde de carbone et éventuellement de capteurs de
chaleur
This European Standard was approved by CEN on 25 October 2014.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same
status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.





EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2014 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-31:2014 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST EN 54-31:2015
EN 54-31:2014 (E)
Contents Page
Foreword .6
Introduction .8
1 Scope .9
2 Normative references .9
3 Terms and definitions . 10
4 Requirements . 10
4.1 General . 10
4.2 Categorization . 10
4.3 Nominal activation conditions/sensitivity . 11
4.3.1 Individual alarm indication . 11
4.3.2 Response to slowly developing fires, aging and contamination . 11
4.3.3 Rate sensitive CO response . 11
4.3.4 Repeatability of smoke response. 11
4.3.5 Directional dependence of smoke response . 12
4.3.6 Repeatability of CO response . 12
4.3.7 Directional dependence of CO response . 12
4.3.8 Directional dependence of heat response . 12
4.3.9 Lower limit of heat response . 12
4.3.10 Reproducibility of smoke response . 12
4.3.11 Reproducibility of CO response . 12
4.3.12 Reproducibility of heat response . 12
4.3.13 Air movement . 12
4.3.14 Dazzling . 12
4.4 Operational reliability . 13
4.4.1 Connection of ancillary devices . 13
4.4.2 Monitoring of detachable detectors . 13
4.4.3 Manufacturer's adjustments . 13
4.4.4 On-site adjustment of response behaviour . 13
4.4.5 Protection against the ingress of foreign bodies . 13
4.4.6 Software controlled detectors . 13
4.4.7 Long term stability . 15
4.5 Tolerance to supply parameters - Variation in supply parameters . 15
4.6 Performance parameters under fire conditions - Fire sensitivity . 15
4.7 Durability of nominal activation conditions/sensitivity . 15
4.7.1 Temperature resistance . 15
4.7.2 Humidity resistance . 15
4.7.3 Shock and vibration resistance . 16
4.7.4 Electrical stability - EMC, immunity (operational) . 16
4.7.5 Resistance to chemical agents . 16
4.8 Detector sensitivity to single fire phenomena . 16
4.8.1 Sensitivity to smoke . 16
4.8.2 Sensitivity to carbon monoxide . 17
4.8.3 Sensitivity to heat . 17
5 Testing, assessment and sampling methods . 17
5.1 General . 17
5.1.1 Atmospheric conditions for tests . 17
5.1.2 Operating conditions for tests . 17
2

---------------------- Page: 4 ----------------------

SIST EN 54-31:2015
EN 54-31:2014 (E)
5.1.3 Mounting arrangements . 17
5.1.4 Tolerances . 17
5.1.5 Measurement of smoke response value . 18
5.1.6 Measurement of CO response value . 19
5.1.7 Measurement of heat response value . 19
5.1.8 Provision for tests . 20
5.1.9 Test schedule . 20
5.2 Nominal activation conditions/sensitivity . 22
5.2.1 Individual alarm indication . 22
5.2.2 Response to slowly developing fires, aging and contamination . 22
5.2.3 Rate sensitive CO response . 23
5.2.4 Repeatability of smoke response . 23
5.2.5 Directional dependence of smoke response . 23
5.2.6 Repeatability of CO response . 24
5.2.7 Directional dependence of CO response . 24
5.2.8 Directional dependence of heat response . 25
5.2.9 Lower limit of heat sensitivity . 25
5.2.10 Reproducibility of smoke response . 26
5.2.11 Reproducibility of CO response . 26
5.2.12 Reproducibility of heat response . 26
5.2.13 Air movement . 27
5.2.14 Dazzling . 28
5.3 Operational reliability . 28
5.3.1 Connection of ancillary devices . 28
5.3.2 Monitoring of detachable detectors . 29
5.3.3 Manufacturer's adjustments . 29
5.3.4 On-site adjustment of behaviour . 29
5.3.5 Protection against the ingress of foreign bodies . 29
5.3.6 Software controlled devices . 29
5.3.7 Long term stability . 29
5.4 Tolerance to supply parameters . 30
5.4.1 Variation in supply parameters . 30
5.5 Performance parameters under fire conditions . 30
5.5.1 Fire sensitivity . 30
5.6 Durability of nominal activation conditions/sensitivity . 33
5.6.1 Temperature resistance . 33
5.6.2 Humidity resistance . 36
5.6.3 Shock and vibration resistance . 41
5.6.4 Electrical stability . 45
5.6.5 Resistance to chemical agents . 47
5.7 Non-response to single fire phenomena . 50
5.7.1 Sensitivity to smoke . 50
5.7.2 Sensitivity to carbon monoxide . 51
5.7.3 Sensitivity to heat . 51
6 Assessment and verification of constancy of performance (AVCP) . 52
6.1 General . 52
6.2 Type testing . 52
6.2.1 General . 52
6.2.2 Test samples, testing and compliance criteria . 53
6.2.3 Test reports . 53
6.3 Factory production control (FPC) . 53
6.3.1 General . 53
6.3.2 Requirements . 54
6.3.3 Product specific requirements . 56
6.3.4 Initial inspection of factory and FPC . 57
6.3.5 Continuous surveillance of FPC . 57
3

---------------------- Page: 5 ----------------------

SIST EN 54-31:2015
EN 54-31:2014 (E)
6.3.6 Procedure for modifications . 58
6.3.7 One-off products, pre-production products, (e.g. prototypes) and products produced in

very low quantities. 58
7 Classification and designation . 59
8 Marking, Labelling and Packaging . 59
Annex A (normative) Smoke tunnel for smoke response values . 60
Annex B (normative) Test aerosol for smoke response value measurements. 61
Annex C (normative) Smoke measuring instruments . 62
C.1 Obscuration meter . 62
C.2 Measuring ionization chamber (MIC) . 62
Annex D (normative) Gas test chamber for CO response threshold value and cross-sensitivity to

chemical agents . 66
Annex E (normative) Heat tunnel for heat response value . 67
Annex F (normative) Measuring instruments for CO . 68
F.1 General . 68
F.2 CO measuring instrument . 68
Annex G (informative) Establishing exposure levels of chemical agents . 69
G.1 General . 69
G.2 Establishing concentration of chemical agents for test gases 1 to 9 of 5.6.5.3 . 69
G.3 Verification of test chamber leakage . 69
G.4 Establishing concentration of ozone . 69
Annex H (normative) Apparatus for dazzling test . 70
Annex I (informative) Apparatus for impact test . 72
Annex J (normative) Fire test room . 74
Annex K (normative) Open wood fire (TF1) . 76
K.1 Fuel . 76
K.2 Arrangement . 76
K.3 Method of ignition . 76
K.4 Variables . 76
K.5 End-of-test condition . 76
K.6 Test validity criteria . 76
Annex L (normative) Smouldering (pyrolysis) wood fire (TF2) . 80
L.1 Fuel . 80
L.2 Hotplate . 80
L.3 Arrangement . 80
L.4 Heating rate . 80
L.5 End-of-test condition . 80
L.6 Test validity criteria . 80
Annex M (normative) Glowing smouldering cotton fire (TF3) . 85
M.1 Fuel . 85
M.2 Arrangement . 85
M.3 Ignition . 86
M.4 End-of-test condition . 86
M.5 Test validity criteria . 87
Annex N (normative) Open plastics (polyurethane) fire (TF4) . 90
N.1 Fuel . 90
N.2 Conditioning . 90
N.3 Arrangement . 90
N.4 Ignition . 90
4

---------------------- Page: 6 ----------------------

SIST EN 54-31:2015
EN 54-31:2014 (E)
N.5 Method of ignition . 90
N.6 End-of-test condition . 90
N.7 Test validity criteria . 90
Annex O (normative) Liquid (heptane) fire (TF5) . 93
O.1 Fuel . 93
O.2 Arrangement . 93
O.3 Ignition . 93
O.4 End-of-test condition . 93
O.5 Test validity criteria . 93
Annex P (normative) Low temperature black smoke (decalene) liquid fire (TF8) . 96
P.1 Fuel . 96
P.2 Arrangement . 96
P.3 Ignition . 96
P.4 End-of-test condition . 96
P.5 Test validity criteria . 96
Annex Q (informative) Information concerning the construction of the smoke tunnel . 99
Annex R (informative) Information concerning the construction of the gas test chamber . 102
Annex S (informative) Construction of the heat tunnel . 104
Annex T (informative) Information concerning test procedures and requirements for response to

slowly developing fires, aging and contamination . 107
Annex U (informative) Information concerning the construction of the measuring ionization

chamber . 111
Bibliography . 113

5

---------------------- Page: 7 ----------------------

SIST EN 54-31:2015
EN 54-31:2014 (E)
Foreword
This document (EN 54-31:2014) has been prepared by Technical Committee CEN/TC 72 “Fire detection and
fire alarm systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by June 2
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.