Alarm systems - Intrusion systems -- Part 2-5: Requirements for combined passive infrared and ultrasonic detectors

Interim TS before EN status (draft expected August 2006) * D117/092: Standstill maintained

Alarmanlagen - Einbruchmeldeanlagen -- Teil 2-5: Anforderungen an kombinierte Passiv-Infrarot und Ultraschallmelder

Systèmes d'alarme - Systèmes d'alarme intrusion -- Partie 2-5: Exigences pour détecteurs combinés infrarouges passifs et ultrasoniques

Alarm systems - Intrusion systems - Part 2-5: Requirements for combined passive infrared and ultrasonic detectors

General Information

Status
Withdrawn
Publication Date
31-May-2004
Withdrawal Date
13-Nov-2008
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
13-Nov-2008
Due Date
06-Dec-2008
Completion Date
14-Nov-2008

Relations

Buy Standard

Technical specification
TS CLC/TS 50131-2-5:2004
English language
36 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST-TS CLC/TS 50131-2-5:2004
01-junij-2004
Alarm systems - Intrusion systems - Part 2-5: Requirements for combined passive
infrared and ultrasonic detectors
Alarm systems - Intrusion systems -- Part 2-5: Requirements for combined passive
infrared and ultrasonic detectors
Alarmanlagen - Einbruchmeldeanlagen -- Teil 2-5: Anforderungen an kombinierte Passiv-
Infrarot und Ultraschallmelder
Systèmes d'alarme - Systèmes d'alarme intrusion -- Partie 2-5: Exigences pour
détecteurs combinés infrarouges passifs et ultrasoniques
Ta slovenski standard je istoveten z: CLC/TS 50131-2-5:2004
ICS:
13.310 Varstvo pred kriminalom Protection against crime
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
SIST-TS CLC/TS 50131-2-5:2004 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST-TS CLC/TS 50131-2-5:2004

---------------------- Page: 2 ----------------------

SIST-TS CLC/TS 50131-2-5:2004
TECHNICAL SPECIFICATION CLC/TS 50131-2-5
SPECIFICATION TECHNIQUE
TECHNISCHE SPEZIFIKATION April 2004

ICS 13.320


English version


Alarm systems - Intrusion systems
Part 2-5: Requirements for combined passive infrared
and ultrasonic detectors


Systèmes d'alarme –  Alarmanlagen –
Systèmes de détection d'intrusion Einbruchmeldeanlagen
Partie 2-5 : Exigences pour détecteurs Teil 2-5 : Anforderungen an Dualmelder
combinés infrarouges passifs et Passiv-infrarot und Ultraschall-melder
ultrasoniques






This Technical Specification was approved by CENELEC on 2003-11-22.

CENELEC members are required to announce the existence of this TS in the same way as for an EN and to
make the TS available promptly at national level in an appropriate form. It is permissible to keep conflicting
national standards in force.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden,
Switzerland and United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2004 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. CLC/TS 50131-2-5:2004 E

---------------------- Page: 3 ----------------------

SIST-TS CLC/TS 50131-2-5:2004
CLC/TS 50131-2-5:2004 - 2 -
Foreword

This Technical Specification was prepared by the Technical Committee CENELEC TC 79, Alarm systems.

The text of the draft was submitted to the formal vote and was approved by CENELEC as
CLC/TS 50131-2-5 on 2003-11-22. Standstill is maintained.

The following date was fixed:

- latest date by which the existence of the CLC/TS
 has to be announced at national level (doa) 2004-07-08

__________

---------------------- Page: 4 ----------------------

SIST-TS CLC/TS 50131-2-5:2004
– 3 – CLC/TS 50131-2-5:2004

Contents
Page
1 Scope.5
2 Normative references.5
3 Definitions and abbreviations .5
4 Functional requirements.7
4.1 Indication signals or messages.7
4.2 Detection.8
4.3 Operational requirements.10
4.4 Immunity of the individual technologies to incorrect operation.10
4.5 Tamper security.11
4.6 Electrical requirements.12
4.7 Environmental classification and conditions.13
5 Marking, identification and documentation.13
5.1 Marking and identification .13
5.2 Documentation.13
6 Testing.14
6.1 General test conditions .14
6.2 Basic detection test.15
6.3 Walk testing .16
6.4 Verification of detection performance .17
6.5 Switch-on delay, time interval between signals and indication of detection.19
6.6 Fault condition signals or messages: self tests.19
6.7 Immunity to incorrect operation.20
6.8 Tamper security.21
6.9 Electrical tests.23
6.10 Environmental classification and conditions.24
6.11 Marking and documentation.25

Annex A (normative) Format of standard test magnets.26
Annex B (normative) General test matrix .27
Annex C (normative) Walk test diagrams.29
Annex D (normative) Procedure for standard target calcuations .32
Annex E (informative) Basic detection target for the basic test of detection capability .33
Annex F (informative) Calibration heat source .33
Annex G (normative) Calibration of the standard walk test targets .34
Annex H (informative) Equipment for walk test velocity control.34
Annex J (informative) Immunity to visible and near infrared radiation: calibration of the light source.35
Annex K (informative) List of small tools suitable for testing immunity of casing to attack .35
Annex L (informative) Test for resistance to re-orientation of ajustable mountings .36

Figure A.1 - Format of standard test magnets.26
Figure C.1 - Detection across the boundary and effect of control adjustements.29
Figure C.2 - Detection within the boundary and effect of control adjustements .29
Figure C.3 - High velocity and intermittent movement.30
Figure C.4 - Close-in detection.30
Figure C.5 - Significant range reduction .31
Figure L.1 - Re-orientation test.36

Table 1 - Indication signals and messages .8
Table 2 - General walk test velocity and attitude requirements.9
Table 3 - Tamper security requirements.12
Table 4 - Electrical requirements.12
Table 5 - Range of materials for masking tests.22
Table 6 - Operational tests .25
Table 7 - Endurance tests .25

---------------------- Page: 5 ----------------------

SIST-TS CLC/TS 50131-2-5:2004
CLC/TS 50131-2-5:2004 - 4 -
Introduction
This Technical Specification is a specification for combined passive infrared and ultrasonic detectors (to
be referred to here as the combined detector) used as part of intrusion detection systems installed in
buildings. It includes four security grades and the first three environmental classes.

The purpose of a combined detector is to detect the broad spectrum infrared radiation emitted by an
intruder and, at the same time, to emit ultrasonic radiation over the area being protected, and analyse
signals that are returned. An intrusion signal or message is only generated when both technologies
register a positive indication of the presence of an intruder, thus reducing incorrect operation. The
combined detector shall provide the necessary range of signals or messages to be used by the rest of the
intrusion detection system.

The number and scope of these signals or messages will be more comprehensive for systems that are
specified at the higher grades.

This specification is only concerned with the requirements and tests for the combined detector. Other
types of detector are covered by other documents identified as drafts in the EN 50131-2 series.

The requirement in EN 50131-1 that detectors in grade 3 and 4 systems shall include a means to detect a
significant reduction in range may be met either by detectors having the appropriate function (see 4.2.3) or
by suitable system design.

---------------------- Page: 6 ----------------------

SIST-TS CLC/TS 50131-2-5:2004
– 5 – CLC/TS 50131-2-5:2004

1 Scope

This Technical Specification provides for security grades 1 - 4 (see EN 50131-1), specific or non-specific
wired or wire-free combined passive infrared and ultrasonic detectors, and is covered by environmental
classes 1 – 3 (see EN 50130-5).

A function designated in the specification as not required for a particular grade may be provided by
themanufacturer. If provided, it will be tested, and shall meet all relevant requirements of any higher
grade. If it passes, the manufacturer may claim it as an extra feature, which does not alter the overall
grading of the detector.

The specification does not apply to system interconnections.


2 Normative references

The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.

EN 50130-4:1995 Alarm systems - Part 4: Electromagnetic compatibility - Product family
+ A1:1996 standard: Immunity requirements for components of fire, intruder and social
+ A2:2003 alarm systems
EN 50130-5:1998 Alarm systems - Part 5: Environmental test methods
EN 50131-1:1997 Alarm systems - Intrusion systems - Part 1: General requirements
EN 50131-6:1997 Alarm systems - Intrusion systems - Part 6: sower Supplies
EN 60068-1:1994 Environmental testing - Part 1: General and guidance (IEC 60068-1:1988 +
corr. October 1988 + A2:1992)
EN 60068-2-52:1996 Environmental testing - Part 2-52: Tests - Test Kb: Salt mist, cyclic (sodium
chloride solution) (IEC 60068-2-52:1996)


3 Definitions and abbreviations

For the purpose of this document, the following definitions and abbreviations apply in addition to those
given in EN 50131-1:

3.1
alert/set mode
state of operation in which a detector will generate an intrusion signal in response to stimulation by a
human being or a standard target

3.2
basic detection target
heat source and/or ultrasonic reflector designed to verify the operation of a detector

3.3
ceiling mount detector
detector capable of sensing human movement from a mounting position on the ceiling

3.4
combined passive infrared and ultrasonic detector
detector of the broad-spectrum infrared emitted by a human being, with an active ultrasonic emitter and
detector installed in the same casing

---------------------- Page: 7 ----------------------

SIST-TS CLC/TS 50131-2-5:2004
CLC/TS 50131-2-5:2004 - 6 -
3.5
curtain detector
detector capable of sensing human movement through a continuous layer of detection zones

3.6
local memory
storage medium situated on board the detector, and having the capability to record signals or messages
generated by the detector

3.7
long range detector
detector capable of sensing human movement in an extended field of view with horizontal angular
coverage less than 10 degrees

3.8
masking
interference with the detector input capability by the introduction of a physical barrier such as metal,
plastic, paper or sprayed paints or lacquers in close proximity to the detector

3.9
ultrasonic detector
detector having an active ultrasonic emitter and detector installed in the same casing

3.10
passive infrared detector
detector of the broad-spectrum infrared radiation emitted by a human being

3.11
simulated walk test target
non-human or synthetic heat source or ultrasonic reflector designed to simulate the standard walk test
target

3.12
incorrect operation
physical condition that causes an inappropriate signal from a detector

3.13
standard walk test target
human being of standard weight and height clothed in close fitting clothing appropriate to the simulation of
an intruder

3.14
standby/unset mode
state of operation in which a detector is not required to generate an intrusion signal or message in
response to stimulation by a human being or a standard target

NOTE  For environmental reasons, the ultrasonic emitter may be switched off.

3.15
test mode
state of operation in which a detector will activate an intrusion indicator in response to stimulation by a
human being or a standard walk test target

3.16
volumetric detector
detector capable of sensing human movement in a volume such as a room with a field of view with
horizontal angular coverage greater than 45°

---------------------- Page: 8 ----------------------

SIST-TS CLC/TS 50131-2-5:2004
– 7 – CLC/TS 50131-2-5:2004

3.17
walk test
operational test during which a detector is stimulated by the standard walk test target in a controlled
environment

3.18
walk test attitude, upright
upright attitude shall consist of the standard walk test target standing and walking with arms held at the
sides of the body. The standard walk test target begins and ends a traverse with feet together

3.19
walk test attitude, crawling
crawling attitude shall consist of the standard walk test target moving with hands and knees in contact with
the floor

3.20
wire free detector
detector connected to the control and indicating equipment by non-physical means such as radio
frequency signals

3.21 Abbreviations

HDPE - high density polyethylene

PIR - passive infrared

EMC - electromagnetic compatibility

SWT - standard walk test target

BDT - basic detection target

FOV - field of view


4 Functional requirements

4.1 Indication signals or messages

All combined detectors shall have an alert/set mode. Grades 3 and 4 shall also have an unset mode. If a
combined detector has only one mode of operation, then it shall always be in the alert/set mode. Tamper
detection shall be active in all modes.

Each possible mode of operation is determined by the status of the intrusion detection system with which
the combined detector communicates. The combined detector signals or messages in these modes of
operation shall function in accordance with Table 1. All signals or messages apply to all modes of
operation unless stated otherwise.

Where a memory display is provided on board the combined detector, it shall not function in the alert /set
mode.

---------------------- Page: 9 ----------------------

SIST-TS CLC/TS 50131-2-5:2004
CLC/TS 50131-2-5:2004 - 8 -
Table 1 - Indication signals or messages
Event Grades Intrusion signal Tamper signal Fault signal
or message or message or message
a
1 – 4 Required Not permitted Not permitted
Intrusion
No stimulus 1 – 4 Not permitted Not permitted Not permitted
Masking 1 – 2 Not required Not required Not required
b b
3 – 4 Required Not required Required
Tamper 1 – 4 Not required Required Not required
Low supply voltage (external) 1 – 2 Not required Not required Not required
3 – 4 Not required Not required Required
1 Not required Not required Not required
Total loss of external power
supply
2 – 4 Required Not required Not required
Local self test pass 1 – 4 Not permitted Not permitted Not permitted
1 – 2 Not permitted Not permitted Not required
Local self test fail
3 – 4 Not permitted Not permitted Required
Remote self test pass 1 – 2 Not required Not permitted Not permitted
3 – 4 Required Not permitted Not permitted
Remote self test fail 1 – 2 Not permitted Not permitted Not required
3 – 4 Not permitted Not permitted Required
a
Not required in unset / standby mode - required in test mode.
b
An independent masking signal or message may be provided instead.
c
Not required for bus systems.

NOTE  For internal power supplies, see EN 50131-6.


4.2 Detection

4.2.1 Detection performance

The combined detector shall generate an intrusion signal or message when the SWT or simulated walk
test target moves within the boundary for a distance of 3 m or across the manufacturers claimed boundary
of detection. An intrusion signal or message shall only be generated when both technologies register a
positive indication of the presence of an intruder.

The variety of velocities and attitudes are as specified in Table 2.

---------------------- Page: 10 ----------------------

SIST-TS CLC/TS 50131-2-5:2004
– 9 – CLC/TS 50131-2-5:2004

Table 2 - General walk test velocity and attitude requirements

Test Grade 1 Grade 2 Grade 3 Grade 4
Detection at the boundary Required Required Required Required
Velocity (m/s) 1,0 1,0 1,0 1,0
Attitude Upright Upright Upright Upright
Detection within the boundary Required Required Required Required
Velocity (m/s) 0,3 0,3 0,2 0,1
Attitude Upright Upright Upright Upright
Detection at high velocity Not required Required Required Required
Velocity  (m/s) # 2,0 2,5 3,0
Attitude # Upright Upright Upright
Close-in detection performance
Distance (m) 2,0 2,0 0,5 0,5
Velocity (m/s) 0,5 0,4 0,3 0,2
Attitude Upright Upright Crawling Crawling
Intermittent movement detection Not required Not required Required Required
a
performance
Velocity (m/s) # # 1,0 1,0
Attitude # # Upright Upright
b
Effect of control adjustments Not required  Required Required Required
Velocity (m/s) # 0,3 0,2 0,1
Attitude # Upright Upright Crawling
c c
Significant reduction of specified Not required Not required Not required Not required
range
Velocity (m/s) # # 1,0 1,0
Attitude # # Upright Upright
a
The intermittent movement shall consist of the SWT moving a distance of 1 m by taking two 0,5 m steps (at 1,0 m/s), pausing
for 5 s then continuing for a further 1 s.
b
If means for continuous adjustment of detection sensitivity is provided, the effect of any setting shall be indicated with a
tolerance of less than 25 % of the maximum reading.
c
The means to detect a significant reduction in range may be met either by detectors having the appropriate function (see 4.2.3)
or by suitable system design.
# To test features that are not required in a particular grade, parameters from a higher grade shall be specified.


4.2.2 Indication of detection

An indicator shall be provided at the combined detector to indicate when detection causes an intrusion
signal or message. This indicator shall only have this function, shall not function in the event of power
failure, and be capable of being enabled/disabled. This operation shall only be performed locally after
removal of the cover or remotely at the control and indicating equipment.

---------------------- Page: 11 ----------------------

SIST-TS CLC/TS 50131-2-5:2004
CLC/TS 50131-2-5:2004 - 10 -
4.2.3 Significant reduction of specified range

If the facility to detect reduction in specified range is provided, then range reduction along the principal
axis of detection of more than 50 % shall generate an alarm or fault signal or message within a maximum
period of 180 s, according to the requirements given in Table 2. The requirements of 4.3.5 (self test) and
4.5.5 (resistance to masking) can provide range reduction detection.
If additional equipment is required to detect significant reduction in range, reference shall be made to the
manufacturers documentation.

4.3 Operational requirements

4.3.1 Time interval between intrusion signals or messages

Wired combined detectors shall be able to provide an intrusion signal or message not more than 15 s after
the end of the preceding intrusion signal or message. Wire free combined detectors shall perform the
same function in a time as follows:
Grade 1: 300 s
Grade 2: 300 s
Grade 3: 30 s
Grade 4: 15 s (see EN 50131-1 for amendment)

4.3.2 Switch on delay

The combined detector shall meet all functional requirements within 180 s of the power supply reaching its
nominal voltage.

4.3.3 Fault condition signals

When a combined detector suffers a fault, a fault signal or message shall be generated in accordance
with the manufacturer's specification, and the provisions of Table 1.

4.3.4 Power supply faults

Combined detectors of all grades shall signal complete power failure according to the provisions of
Table 1.
Additionally, combined detectors of grades 3 and 4 shall signal when the supply voltage moves below the
manufacturers specified range according to the provisions of Table 1.

4.3.5 Self tests

Grade 3 and grade 4 combined detectors shall monitor the function of the sensor and associated on-
board signal processing circuitry. A self-test shall be performed under the control of the combined
detector.

When a remote self-test is initiated a signal or message shall be generated between 1 and 5 s later, and
shall be signalled within 5 s of that initiation. The test duration shall not exceed 10 s. After the test is
completed, the combined detector shall resume it’s previous state within 5 s. Fault indication requirements
appear in Table 1

Where normal operation of the combined detector is inhibited during a local test of function monitoring the
inhibition time shall be limited to a maximum of 15 s in a period of 1 h.

4.4 Immunity of the individual technologies to incorrect operation

The combined detector shall be considered to have sufficient immunity to incorrect operation if the
following requirements have been met. No intrusion signal or message shall be generated during the
tests.

---------------------- Page: 12 ----------------------

SIST-TS CLC/TS 50131-2-5:2004
– 11 – CLC/TS 50131-2-5:2004

4.4.1 Immunity to air flow

The PIR component of the combined detector shall not generate an intrusion signal or message when air
is blown over the face of the combined detector.

4.4.2 Immunity to visible and near infrared radiation

The PIR component of the combined detector shall not generate an intrusion signal or message when
visible and near infrared radiation from a light source such as a car headlamp is directed on to the front
window or lens through a pane of glass.

4.4.3 Immunity to ultrasonic signal interference by extraneous sound sources

The ultrasonic component of the combined detector shall not generate an intrusion signal or message due
to the operation of a sound source mounted nearby.

4.5 Tamper security

Tamper security requirements for each grade of combined detector are shown in Table 3.

4.5.1 Prevention of unauthorised access to the inside of the combined detector through covers
and existing holes

Access holes shall not allow interference with the operation of the combined detector by probing with
commonly available tools. Damage must not be caused that would be visible to a person with normal
eyesight viewing from a distance of 1 m with the combined detector illuminated at a level of 2 000 lux.

A tool shall be required to open the unit. All covers giving access to components which could affect
adversely the operation of the combined detector shall be fitted with a tamper detection device in
accordance with Table 3. A tamper signal or message shall be generated before access is gained with
any tool.

4.5.2 Detection of removal from the mounting surface

A tamper detection device shall be fitted which signals a tamper if the combined detector is removed from
the mounting surface in accordance with Table 3. Mounting screws shall only be accessible from within
the unit.
Operation of the device shall not be preventable by external means. This device shall activate before
access can be gained to it.

4.5.3 Resistance to re-orientation of adjustable mountings

Where the orientation of a combined detector can be adjusted, resistance to re-orientation of the mounting
shall be provided in accordance with Table 3.

The alignment of the boundary of detection shall not have changed by more than 5° due to a grade-
dependent applied torque. Alternatively a tamper detection device shall signal before the alignment of the
boundary of detection has moved by 5°.
If a combined detector provides a means to adjust the orientation of its coverage pattern, the access to
this means shall be protected by a tamper detection device.

4.5.4 Immunity to magnetic field interference

It shall not be possible to inhibit any signalling devices with a magnet of grade dependent remanence,
according to Table 3. The form of standard magnets is described in Annex A.

---------------------- Page: 13 ----------------------

SIST-TS CLC/TS 50131-2-5:2004
CLC/TS 50131-2-5:2004 - 12 -
4.5.5 Resistance to masking

Means shall be provided to detect inhibition of the operation of the detector by covering its sensing area
and sensor, in the unset mode. The maximum response time for the masking detection device shall be
180 s. Intrusion and fault signals or messages or a dedicated anti-masking signal or message shall be
generated. The signals or messages shall remain latched until restored. Grade dependency appears in
Table 3.

No anti-masking signal shall be generated by normal human movement at 1 m/s at a distance greater
than 1 m in the unset condition.

Table 3 - Tamper security requirements

Requirement Grade 1 Grade 2 Grade 3 Grade 4
Resistance to access to the inside Required Required Required Required
of the combined detector
a
Removal from the mounting surface Not Required Required Required Required
Resistance to reorientation applied Not Required Required Required Required
torque Nm 2 5 10
Magnetic field immunity T Not Required Required Required Required
0,15 0,3 1,2
Anti-masking capability Not Required Not Required Required Required
a
  Required for wire free detectors only.


4.6 Electrical requirements

These requirements do not apply to combined detectors having internal power supplies. For these
detectors refer to EN 50131-6. For a combined detector having an external power supply, the
requirements appear in Table 4.

Table 4 - Electrical requirements

Test Grade 1 Grade 2 Grade 3 Grade 4
Detector power consumption Required Required Required Required
Input voltage range and slow input Not required Required Required Required
voltage rise
Input voltage ripple Not requir
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.