Fire detection and fire alarm systems - Part 2: Control and indicating equipment

This European Standard specifies requirements,methods of test, and performance criteria for control and indicating equipment  for use in fire detection and fire alarm systems installed in buildings.

Brandmeldeanlagen - Teil 2: Brandmelderzentralen

Diese Europäische Norm legt Anforderungen, Prüfverfahren und Leistungsmerkmale für Brandmelder¬zentralen zur Verwendung in Brandmeldesystemen, die in Gebäuden errichtet werden, fest (siehe Bild 1, Kennbuchstabe B von EN 54-1:2011).

Systèmes de détection et d'alarme incendie - Partie 2: Équipement de contrôle et de signalisation

La présente Norme européenne prescrit les exigences, les méthodes d'essai et les critères de performance des équipements de contrôle et de signalisation (voir dispositif B de la Figure 1 de l'EN 54-1:2011) destinés à être utilisés dans les systèmes de détection et d'alarme incendie installés dans les bâtiments.

Sistemi za odkrivanje in javljanje požara - 2. del: Oprema za kontrolo in indikacijo

General Information

Status
Not Published
Public Enquiry End Date
29-May-2012
Technical Committee
Current Stage
98 - Abandoned project (Adopted Project)
Start Date
02-Jun-2020
Due Date
07-Jun-2020
Completion Date
02-Jun-2020

Relations

Buy Standard

Draft
prEN 54-2:2012
English language
82 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
oSIST prEN 54-2:2012
01-april-2012
Sistemi za odkrivanje in javljanje požara - 2. del: Oprema za kontrolo in indikacijo
Fire detection and fire alarm systems - Part 2: Control and indicating equipment
Brandmeldeanlagen - Teil 2: Brandmelderzentralen
Systèmes de détection et d'alarme incendie - Partie 2: Équipement de contrôle et de
signalisation
Ta slovenski standard je istoveten z: prEN 54-2 rev
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
oSIST prEN 54-2:2012 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 54-2:2012

---------------------- Page: 2 ----------------------
oSIST prEN 54-2:2012


EUROPEAN STANDARD
DRAFT
prEN 54-2 rev
NORME EUROPÉENNE

EUROPÄISCHE NORM

February 2012
ICS 13.220.20 Will supersede EN 54-2:1997
English Version
Fire detection and fire alarm systems - Part 2: Control and
indicating equipment
Systèmes de détection et d'alarme incendie - Partie 2: Brandmeldeanlagen - Teil 2: Brandmelderzentralen
Équipement de contrôle et de signalisation
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 72.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland,
Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2012 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 54-2 rev:2012: E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
Contents Page
Foreword .3
Introduction .5
1 Scope .6
2 Normative references .6
3 Terms, definitions and abbreviations .7
4 Requirements .8
5 Tests and design assessments . 32
6 Evaluation of conformity . 42
7 Classification . 48
8 Marking, labelling and packaging . 48
Annex A (normative) Documentation and manufacturer's declarations . 49
Annex B (informative) Access levels . 52
Annex C (informative) Processing of signals from fire detectors . 54
Annex D (informative) Zones and the zonal indication of fire alarms . 55
Annex E (informative) Outputs, delays to outputs and dependencies on more than one alarm
signal . 56
Annex F (informative) Fault recognition and indication . 58
Annex G (informative) Standardised input/output interface for the connection of ancillary
equipment (e.g. a fire brigade panel) . 59
Annex H (informative) Integrity of transmission paths . 60
Annex I (informative) CIE controlled by software and related technology. 61
Annex J (informative) Schedule for full functional test and design assessment . 62
Annex K (informative) Design changes to CIE under FPC . 75
Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU
Construction Products Directive (89/106/EEC) . 77

2

---------------------- Page: 4 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
Foreword
This document (prEN 54-2:2012) has been prepared by Technical Committee CEN/TC 72 “Fire detection and
fire alarm systems”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 54-2:1997.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive.
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN shall not be held responsible for identifying any or all such patent rights
This European Standard has been prepared in co-operation with the CEA (Comite Europeen des Assurances)
and with EURALARM (Association of European Manufacturers of Fire and Intruder Alarm Systems).
EN 54-2 “Fire detection and fire alarm systems” consists of the following parts
 Part 1: Introduction
 Part 2: Control and indicating equipment
 Part 3: Fire alarm devices – Sounders
 Part 4: Power supply equipment
 Part 5: Heat detectors - Point detectors
 Part 7: Smoke detectors - Point detectors using scattered light, transmitted light or ionization
 Part 10: Flame detectors - Point detectors
 Part 11: Manual call points
 Part 12: Smoke detectors - Line detectors using an optical light beam
 Part 13: Compatibility assessment of system components
 Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance
 Part 15: Point type multi-sensor fire detectors
 Part 16: Voice alarm control and indicating equipment
 Part 17: Short-circuit isolators
 Part 18: Input/output devices
 Part 20: Aspirating smoke detectors
 Part 21: Alarm and fault warning routing equipment
3

---------------------- Page: 5 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
 Part 22: Line-type heat detectors
 Part 23: Fire alarm devices - Visual alarms
 Part 24: Components of voice alarm systems – Loudspeakers
 Part 25: Components using radio links and system requirements
 Part 26: Point fire detectors using carbon monoxide sensors
 Part 27: Duct smoke detectors
 Part 28: Non-resettable (digital) line type heat detectors
 Part 29 – Multi-sensor fire detectors – Point detectors using a combination of smoke and heat sensors
 Part 30: Multi-sensor detectors – Point detectors using a combination of carbon monoxide and heat
sensors
 Part 31: Multi-sensor fire detectors – Point detectors using a combination of smoke, carbon monoxide and
optionally heat sensors
 Part 32: Planning, design, installation, commissioning, use and maintenance of voice alarm systems

4

---------------------- Page: 6 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
Introduction
This part of the European Standard EN 54 is drafted on the basis of a set of core requirements for operational
reliability (under 4.1.1), plus a number of free-standing additional requirements for operational reliability (under
4.1.2 to 4.1.14). It is expected that the core requirements under 4.1.1 would apply to all control and indicating
equipment, together with the requirements for durability under 4.2. Each set of additional requirements may
be separately provided for use in specific applications, as recommended in application guidelines, in order to
permit control and indicating equipment with many different combinations of functions to comply with this
European Standard.
Other functions associated with fire detection and fire alarm may also be provided, even if not specified in this
European Standard.
5

---------------------- Page: 7 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
1 Scope
This European Standard specifies requirements, methods of test, and performance criteria for control and
indicating equipment (see item B of figure 1 of EN 54-1:2011) for use in fire detection and fire alarm systems
installed in buildings.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 54-1:2011, Fire detection and fire alarm systems — Part 1: Introduction
EN 54-4:1997, Fire detection and fire alarm systems — Part 4: Power supply equipment

EN 54-4:1997/A1:2002 Fire detection and fire alarm systems — Part 4: Power supply equipment

EN 54-4:1997/A2:2006 Fire detection and fire alarm systems — Part 4: Power supply equipment

EN 54-7:2000, Fire detection and fire alarm systems - Part 7: Smoke detectors - Point detectors using
scattered light, transmitted light or ionization

EN 54-7:2000/A1:2002, Fire detection and fire alarm systems - Part 7: Smoke detectors - Point detectors
using scattered light, transmitted light or ionization

EN 54-7:2000/A2:2006, Fire detection and fire alarm systems - Part 7: Smoke detectors - Point detectors
using scattered light, transmitted light or ionization

EN 54-17:2005, Fire detection and fire alarm systems - Part 17: Short circuit isolators
EN 54-25:2008, Fire detection and fire alarm systems - Part 25: Components using radio links
EN 50130-4:1995, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard:
Immunity requirements for components of fire, intruder and social alarm systems

EN 50130-4:1995/A1:1998, Alarm systems — Part 4: Electromagnetic compatibility — Product family
standard: Immunity requirements for components of fire, intruder and social alarm systems

EN 50130-4:1995/A2:2003, Alarm systems — Part 4: Electromagnetic compatibility — Product family
standard: Immunity requirements for components of fire, intruder and social alarm systems

EN 60068-1:1994, Environmental testing - Part 1: General and guidance (IEC 60068-1:1988 + Corrigendum
1988 + A1:1992)
EN 60068-2-1:2007, Environmental testing; part 2: tests; tests A: cold (IEC 60068-2-1:2007)
EN 60068-2-6:2008, Environmental testing - Part 2: Tests - Tests Fc: Vibration (sinusoidal) (IEC 60068-2-
6:2007)
EN 60068-2-47:2005, Environmental testing - Part 2-47: Test Mounting of specimens for vibration, impact and
similar dynamic tests (IEC 60068-2-47:2005)
EN 60068-2-75:1997, Environmental testing - Part 2: Tests - Test Eh: Hammer tests (IEC 60068-2-75:1997)
6

---------------------- Page: 8 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
EN 60068-2-78:2001, Environmental testing — Part 2-78: Tests, Test Cab: Damp heat, steady state (IEC
60068-2-78:2001)
EN 60529:1991, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989)
EN 60721-3-3:1995, Classification of environmental conditions - Part 3: Classification of groups of
environmental parameters and their severities - Section 3: Stationary use at weatherprotected locations (IEC
60721-3-3:1994
3 Terms, definitions and abbreviations
For the purposes of this European Standard , the terms, definitions and abbreviations given in EN 54-1:2011
apply together with the following.
3.1
addressable device
a device that can be individually identified at the CIE
3.2
alphanumeric display
indicator that is capable of giving information by the display of messages consisting of text, numeric
characters, or both
3.3
confirmation alarm signal
signal from a fire detector or manual call point which terminates a first alarm state
3.4
earth fault
unwanted connection between earth potential and any part of the CIE, transmission paths to the CIE, or
transmission paths between parts of the CIE
3.5
field
sub-division of a window
3.6
first alarm signal
signal from a fire detector which is interpreted as a fire alarm, but following which the CIE enters a first alarm
state
3.7
first alarm state
state of the CIE following the receipt of a first alarm signal during which mandatory functions of the CIE may
be inhibited
3.8
functional condition
state of the CIE characterised by mandatory indication(s)
3.9
indicator
device which can change its state to give information
3.10
module
part of the program that fulfils specified functions
7

---------------------- Page: 9 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
3.11
non-volatile memory
memory elements that do not require the presence of an energy source for the retention of their contents
3.12
program
software necessary for a CIE to comply with at least the requirements of this European Standard, including
initialising data, reset and interrupt vectors, operating code, and declarations
3.13
running data
alterable data subject to temporary modification during operation, either automatically or by manual controls
3.14
separate
physically separate, and exclusively provided for the purpose or purposes stated in this European Standard
3.15
silencing
switching off the audible signal of a sounding device that is capable of being re-sounded by a new event
3.16
site specific data
alterable data required for the CIE to operate in a defined system configuration
3.17
volatile memory
memory elements that require the presence of an energy source for the retention of their contents
3.18
window
area of the alphanumeric display, realized either by mechanical separation or under software control, that is
used for information relating to one functional condition at a given time
NOTE A window may be realized either by mechanical separation or under software control.
3.2 Abbreviations
For the purposes of this European Standard the abbreviations given in EN 54-1:2011 apply together with the
following.
AL access level
4 Requirements
4.1 Operational reliability
4.1.1 Functional conditions and related indications
4.1.1.1 Primary functions
4.1.1.1.1 The CIE shall be capable of unambiguously indicating the following functional conditions:
(1) quiescent condition;
(2) fire alarm condition;
8

---------------------- Page: 10 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
(3) fault warning condition;
(4) disablement condition;
(5) test condition.
4.1.1.1.2 The CIE shall be capable of being simultaneously in any combination of the following
functional conditions:
(1) fire alarm condition;
(2) fault warning condition;
(3) disablement condition;
(4) test condition.
4.1.1.1.3 All mandatory indications shall be clearly identifiable, except where otherwise specified in this
European Standard.
4.1.1.1.4 Mandatory indications shall not be falsified.
4.1.1.1.5 Where light emitting indicators and an alphanumeric display are both provided, at least one of these
means shall meet the requirements for each indication in this European Standard. The other means may give
supplementary information.
4.1.1.1.6 Where an alphanumeric display is used to display indications relating to different functional
conditions these may be displayed at the same time. However, for each functional condition there shall be
only one window, in which all of the fields relating to that functional condition are grouped.
4.1.1.1.7 A visible indication shall be given by means of a separate light emitting indicator while the CIE is
supplied with power.
4.1.1.1.8 Any kind of system information may be displayed during the quiescent condition. However, no
indications shall be given which could be confused with indications used in the:
(1) fire alarm condition;
(2) fault warning condition;
(3) disablement condition;
(4) test condition.
9

---------------------- Page: 11 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
4.1.1.1.9 Where indications are used in addition to mandatory indications these shall not result in contradiction
or confusion.
4.1.1.1.10 If functions other than those specified in this European Standard are provided they shall not
jeopardize compliance with any requirements of this European Standard.
4.1.1.2 Fire alarm condition
4.1.1.2.1 Reception and processing of fire signals (see also annex C)
4.1.1.2.1.1 The CIE shall enter the fire alarm condition when signals are received which after any
necessary processing are interpreted as a fire alarm.
4.1.1.2.1.2 The CIE shall be capable of receiving, processing and indicating signals from all zones. A
signal from one zone shall not falsify the processing, storing and indication of signals from other zones.
4.1.1.2.1.3 Unless 4.1.8 applies, the time taken by scanning, interrogation, or other processing of signals
from fire detectors, in addition to that required to take the fire alarm decision, shall not delay the entry to the
fire alarm condition with its indication, or the indication of a new zone in alarm, by more than 10 s.
4.1.1.2.1.4 The CIE shall enter the fire alarm condition within 10 s of the activation of any manual call
point. The manufacturer may specify a time shorter than 10 s. In this case, this specification shall be tested
and verified.
4.1.1.2.1.5 The mandatory indications and outputs shall not be falsified by multiple fire signals received
from fire detectors, manual call points or input devices, from the same or different detection circuits, resulting
from:
(1) the simultaneous reception of two signals followed by the reception of a further signal;
(2) the sequential reception of more than one signal.
4.1.1.2.2 Indication of the fire alarm condition
The fire alarm condition shall be indicated without prior manual intervention. The indication is established
when all of the following are present:
(1) a visible indication, by means of a separate light emitting indicator (the general fire alarm indicator);
2) a visible indication, as specified in 4.1.1.2.3, of the zones in alarm, which may be omitted for CIE capable
of receiving signals from only one zone;
(3) an audible indication, as specified in 4.1.1.2.4 .
4.1.1.2.3 Indication of the zones in alarm (see also annex D)
4.1.1.2.3.1 The zones in alarm shall be visibly indicated by means of one or both of the following:
(1) a separate light emitting indicator for each zone;
(2) an alphanumeric display.
10

---------------------- Page: 12 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
4.1.1.2.3.2 If the zonal indications are on an alphanumeric display, which cannot simultaneously indicate all
the zones in alarm because of its limited capacity, at least the following shall apply.
a) The first zone in alarm shall be displayed in a field at the top of the display.
(b) If there is more than one zone in alarm, the most recent zone in alarm shall be permanently displayed in
another defined field.
(c) If there is more than one zone in alarm, the total number of zones in alarm shall be displayed.
(d) Zones in alarm, but not currently indicated, shall be capable of being displayed at AL1. A single manual
action shall be required for the display of each additional zone in alarm. Either individual fields, or the whole
alarm window, may be temporarily suppressed to permit the display of additional zones in alarm. However,
the display shall meet the requirements of 4.1.1.2.3.2 (a) to (c) within 30 s following the last interrogation.
4.1.1.2.4 Audible indication
4.1.1.2.4.1 The audible indication for the fire alarm condition may be the same as that for the fault warning
condition. If they are different, the fire alarm indication shall have priority.
4.1.1.2.4.2 The audible indication shall be capable of being silenced by means of a separate manual control at
AL1 or AL2. This control shall only be used for silencing the audible indication, and may be the same as that
used for silencing in the fault warning condition.
The silencing of the audible indication may be accompanied by changes in the visible indications of fire or
fault, provided that the required indication of functional conditions is still provided (e.g. the indication of light
emitting indicators may change from flashing to steady, or the information given on an alphanumeric display
may be updated).
4.1.1.2.4.3 The audible indication shall not be silenced automatically.
4.1.1.2.4.4 The audible indication shall re-sound for each new zone in alarm.
4.1.1.2.5 Other indications during the fire alarm condition
4.1.1.2.5.1 If faults, disablements or tests are indicated by means of one or more light emitting indicators, and
such indications are suppressed during the fire alarm condition, it shall be possible to reveal these by means
of a manual operation at AL1 or AL2.
4.1.1.2.5.2 If the fire alarm indications are on an alphanumeric display, the following shall apply to the display
of other information on the alphanumeric display.
(a) Information not related to the fire alarm condition shall be suppressed, unless the display has more than
one window, one of which is exclusively reserved for fire alarm indications.
(b) Suppressed indications of faults, disablements and tests shall be capable of being displayed, at any time,
by manual operations at AL1 or AL2, which are different from, or additional to that specified in 4.1.1.2.3.2 (d)
to display zones in fire alarm, and which are capable of displaying faults, disablements and tests
independently.
(c) Either individual fields, or the whole fire alarm window, may be temporarily suppressed to permit the
display of faults, disablements and tests. However, the display shall meet the requirements of 4.1.1.2.3.2 (a)
to (c) within 30 s following the last interrogation.
11

---------------------- Page: 13 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
4.1.1.2.6 Reset from the fire alarm condition
4.1.1.2.6.1 The CIE shall be capable of being reset from the fire alarm condition. Unless 4.1.1.4.5(b) applies,
this shall only be possible by means of a separate manual control at AL2. This control shall be used only for
reset and may be the same as that used for reset from the fault warning condition. Another operation (e.g.
silence audible indication) may be necessary before reset.
4.1.1.2.6.2 Following a reset operation, the correct functional conditions, corresponding to any received
signals, shall either remain, or be re-established within 20 s.
4.1.1.2.7 Output of the fire alarm condition
4.1.1.2.7.1 At least one output that signals the fire alarm condition shall be provided, which may be an output
as specified in 4.1.2, 4.1.3, or 4.1.4.
4.1.1.2.7.2 Unless 4.1.7 or 4.1.8 apply, the following shall be activated within 3 s of the indication of the fire
alarm condition:
(1) at least one output of 4.1.1.2.7.1;
(2) at least one output signal of 4.1.2;
(3) at least one output signal of 4.1.3;
(4) at least one output signal of 4.1.4.
The manufacturer may specify a time shorter than 3 s. In this case, this specification shall be tested and
verified.
4.1.1.2.7.3 All other output signals of 4.1.1.2.7.1, 4.1.2, 4.1.3, or 4.1.4 which follow the first signal in
4.1.1.2.7.2 shall be activated within 10 s of the indication of the fire alarm condition.
4.1.1.3 Fault warning condition (see also annex F)
4.1.1.3.1 Reception and processing of fault signals
4.1.1.3.1.1 The CIE shall enter the fault warning condition when signals are received which, after any
necessary processing, are interpreted as a fault.
4.1.1.3.1.2 The CIE shall be capable of simultaneously recognising all faults required by this European
Standard, with the exception that the recognition of a fault in a given zone or function may be prevented by
one or more of the following.
(a) The presence of fire alarm signals from the same zone.
(b) The testing of the corresponding zone or function.
(c) The activation of the output to a transmission path which is exclusively used to transmit signals to one or
more of the following:
(1) fire alarm devices (function C of EN 54-1:2011);
(2) fire alarm routing equipment (function E of EN 54-1:2011);
(3) controls for automatic fire protection equipment (function G of EN 54-1:2011);
12

---------------------- Page: 14 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
(4) fault warning routing equipment (function J of EN 54-1:2011).
4.1.1.3.1.3 The CIE shall enter the fault warning condition within 100 s of the occurrence of the fault or the
reception of a fault signal, or within another time as specified in this European Standard or in other parts of EN
54.
4.1.1.3.2 Indication of faults
4.1.1.3.2.1 Faults shall be indicated without prior manual intervention. The fault warning condition is
established when the following are present:
(1) a visible indication by means of a separate light emitting indicator (the general fault warning indicator);
(2) a visible indication for each recognized fault, by means of light emitting indicators, an alphanumeric
display, or both;
(3) an audible indication, as specified in 4.1.1.3.3.
4.1.1.3.2.2 If the indication of 4.1.1.3.2.1 (2) is by means of separate light emitting indicators, these may be
the same as those used to indicate disablement or testing of the corresponding zones or functions, provided
that the fault indication is distinguishable from the disablement and test indications (see also 4.1.1.5.5.3).
4.1.1.3.2.3 For the indication of 4.1.1.3.2.1 (2) at least the following shall apply:
(a) The presence of fault indications that have been suppressed shall be indicated.
(b) Suppressed fault indications shall be capable of being displayed by means of a manual operation at AL1
or AL2 which interrogates only fault indications.
4.1.1.3.2.4 Faults shall be recognised and indicated as follows. The indications may be suppressed during the
fire alarm condition.
(a) An indication for each zone in which the transmission of signals from fire detectors, manual call
points or input devices to the CIE is affected by:
(1) a short circuit in a detection circuit;
(2) an interruption in a detection circuit;
(3) the removal of a detachable component.
(b) An indication, at least common to any power supply fault resulting from:
(1) a short circuit or an interruption in a transmission path to a PSE, where the power supply is
contained in a different cabinet from that of the CIE;
(2) PSE faults as specified in EN 54-4:1997 as amended by EN 54-4:1997/A1:2002 and EN 54-
4:1997/A2:2006.
(c) An indication, at least common to any single earth fault that affects a mandatory function, and which
is not otherwise indicated as a fault of a supervised function.
(d) An indication as a fault of the supervised function of the rupture of any fuse, or the operation of any
protective device which is capable of affecting a mandatory function in the fire alarm condition.
13

---------------------- Page: 15 ----------------------
oSIST prEN 54-2:2012
prEN 54-2:2012 (E)
(e) An indication of any short circuit or interruption, at least common to all transmission paths between
parts of the CIE contained in more than one mechanical cabinet, which is capable of affecting a mandatory
function, and which is not otherwise indicated as a fault of a supervised function.
4.1.1.3.3 Audible indication
4.1.1.3.3.1 The audible i
...