SIST EN 62386-207:2010
(Main)Digital addressable lighting interface - Part 207: Particular requirements for control gears; led modules (device type 6) (IEC 62386-207:2009)
Digital addressable lighting interface - Part 207: Particular requirements for control gears; led modules (device type 6) (IEC 62386-207:2009)
This International Standard specifies a protocol and test procedures for the control by digital signals of electronic control gear for use on a.c. or d.c. supplies, associated with LED modules.
Digital adressierbare Schnittstelle für die Beleuchtung - Teil 207: Besondere Anforderungen an Betriebsgeräte - LED-Module (Gerätetyp 6) (IEC 62386-207:2009)
Interface d'éclairage adressable numérique - Partie 207: Exigences particulières pour les appareillages; modules de del (dispositifs de type 6) (CEI 62386-207:2009)
La CEI 62386-207:2009 spécifie un protocole et des méthodes d'essai pour la commande par des signaux numériques des appareillages électroniques destinés à être utilisés dans les alimentations alternatives ou continues, associés aux modules de DEL. La présente Partie 207 est destinée à être utilisée conjointement avec la CEI 62386-101 et la CEI 62386-102, qui contiennent les exigences générales pour le type de produit concerné (appareillage ou dispositifs de commande).
Digitalni naslovljivi vmesnik za razsvetljavo - 207. del: Posebne zahteve za krmilja; moduli LED (naprava tipa 6) (IEC 62386-207:2009)
Ta mednarodni standard opredeljuje protokol in poskusne postopke za krmiljenje s pomočjo digitalnih signalov elektronskega krmilja za uporabo v izmeničnem ali enosmernem napajanju, povezanemu z moduli LED.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 62386-207:2010
01-januar-2010
Digitalni naslovljivi vmesnik za razsvetljavo - 207. del: Posebne zahteve za krmilja;
moduli LED (naprava tipa 6) (IEC 62386-207:2009)
Digital addressable lighting interface - Part 207: Particular requirements for control gears;
led modules (device type 6) (IEC 62386-207:2009)
Digital adressierbare Schnittstelle für die Beleuchtung - Teil 207: Besondere
Anforderungen an Betriebsgeräte - LED-Module (Gerätetyp 6) (IEC 62386-207:2009)
Interface d'éclairage adressable numérique - Partie 207: Exigences particulières pour les
appareillages; modules de del (dispositifs de type 6) (CEI 62386-207:2009)
Ta slovenski standard je istoveten z: EN 62386-207:2009
ICS:
29.140.50 Instalacijski sistemi za Lighting installation systems
razsvetljavo
35.200 Vmesniška in povezovalna Interface and interconnection
oprema equipment
SIST EN 62386-207:2010 en,fr
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 62386-207:2010
---------------------- Page: 2 ----------------------
SIST EN 62386-207:2010
EUROPEAN STANDARD
EN 62386-207
NORME EUROPÉENNE
November 2009
EUROPÄISCHE NORM
ICS 29.140.50; 29.140.99
English version
Digital addressable lighting interface -
Part 207: Particular requirements for control gear -
LED modules (device type 6)
(IEC 62386-207:2009)
Interface d'éclairage Digital adressierbare Schnittstelle
adressable numérique - für die Beleuchtung -
Partie 207: Exigences particulières Teil 207: Besondere Anforderungen
pour les appareillages de commande - an Betriebsgeräte -
Modules de DEL (dispositifs de type 6) LED-Module (Gerätetyp 6)
(CEI 62386-207:2009) (IEC 62386-207:2009)
This European Standard was approved by CENELEC on 2009-09-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: Avenue Marnix 17, B - 1000 Brussels
© 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 62386-207:2009 E
---------------------- Page: 3 ----------------------
SIST EN 62386-207:2010
EN 62386-207:2009 - 2 -
Foreword
The text of document 34C/888/FDIS, future edition 1 of IEC 62386-207, prepared by SC 34C, Auxiliaries
for lamps, of IEC TC 34, Lamps and related equipment, was submitted to the IEC-CENELEC parallel vote
and was approved by CENELEC as EN 62386-207 on 2009-09-01.
This standard is to be used in conjunction with EN 62386-101 and EN 62386-102, which contain general
requirements for the relevant product type (control gear or control devices).
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2010-06-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2012-09-01
Annex ZA has been added by CENELEC.
__________
Endorsement notice
The text of the International Standard IEC 62386-207:2009 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards indicated:
IEC 60598-1 NOTE Harmonized as EN 60598-1:2008 (modified).
IEC 60669-2-1 NOTE Harmonized as EN 60669-2-1:2004 (modified).
IEC 60921 NOTE Harmonized as EN 60921:2004 (not modified).
IEC 60923 NOTE Harmonized as EN 60923:2005 (not modified).
IEC 60925 NOTE Harmonized as EN 60925:1991 (not modified).
IEC 60929 NOTE Harmonized as EN 60929:2006 (not modified).
IEC 61347-1 NOTE Harmonized as EN 61347-1:2008 (modified).
IEC 61347-2-3 NOTE Harmonized as EN 61347-2-3:2001 (not modified).
IEC 61547 NOTE Harmonized as EN 61547:1995 (not modified).
IEC 62034 NOTE Harmonized as EN 62034:2006 (not modified).
CISPR 15 NOTE Harmonized as EN 55015:2006 (not modified).
__________
---------------------- Page: 4 ----------------------
SIST EN 62386-207:2010
- 3 - EN 62386-207:2009
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.
Publication Year Title EN/HD Year
IEC 62386-101 2009 Digital addressable lighting interface - EN 62386-101 2009
Part 101: General requirements - System
IEC 62386-102 2009 Digital addressable lighting interface - EN 62386-102 2009
Part 102: General requirements - Control gear
---------------------- Page: 5 ----------------------
SIST EN 62386-207:2010
---------------------- Page: 6 ----------------------
SIST EN 62386-207:2010
IEC 62386-207
®
Edition 1.0 2009-08
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Digital addressable lighting interface –
Part 207: Particular requirements for control gear – LED modules (device type 6)
Interface d’éclairage adressable numérique –
Partie 207: Exigences particulières pour les appareillages de commande –
Modules de DEL (dispositifs de type 6)
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
X
CODE PRIX
ICS 29.140.50; 29.140.99 ISBN 2-8318-1059-5
® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale
---------------------- Page: 7 ----------------------
SIST EN 62386-207:2010
– 2 – 62386-207 © IEC:2009
CONTENTS
FOREWORD.4
INTRODUCTION.6
1 Scope.7
2 Normative references .7
3 Terms and definitions .7
4 General .8
5 Electrical specification.8
6 Interface power supply .8
7 Transmission protocol structure.8
8 Timing .8
9 Method of operation .8
10 Declaration of variables .10
11 Definition of commands .11
12 Test procedures .17
Annex A (informative) Examples of algorithms .43
Bibliography.44
Figure 1 – Application extended configuration command sequence example.11
Figure 2 – “QUERY FEATURES” .18
Figure 3 – “QUERY SHORT CIRCUIT”.19
Figure 4 – “QUERY OPEN CIRCUIT” .20
Figure 5 – “QUERY LOAD DECREASE”.21
Figure 6 – “QUERY LOAD INCREASE” .22
Figure 7 – “QUERY CURRENT PROTECTOR ACTIVE: Underload” .23
Figure 8 – “QUERY CURRENT PROTECTOR ACTIVE: Overload” .24
Figure 9 – “QUERY THERMAL SHUT DOWN” .25
Figure 10 – “QUERY THERMAL OVERLOAD”.26
Figure 11 – “Query control gear information”.27
Figure 12 – “REFERENCE SYSTEM POWER” .28
Figure 13 – “REFERENCE SYSTEM POWER: 100 ms-timeout” .29
Figure 14 – “REFERENCE SYSTEM POWER: Command in-between” .30
Figure 15 – “REFERENCE SYSTEM POWER: 15 minutes timer” .31
Figure 16 – “REFERENCE SYSTEM POWER: failed”.32
Figure 17 – “ENABLE / DISABLE CURRENT PROTECTOR” .33
Figure 18 – “SELECT DIMMING CURVE” .34
Figure 19 – “FAST FADE TIME”.35
Figure 20 – “Reset State / Persistent Memory”.37
Figure 21 – “ENABLE DEVICE TYPE: Application extended commands”.38
Figure 22 – “ENABLE DEVICE TYPE: Application extended configuration commands 1”.39
Figure 23 – “ENABLE DEVICE TYPE: Application extended configuration commands 2”.40
Figure 24 – “QUERY EXTENDED VERSION NUMBER” .41
---------------------- Page: 8 ----------------------
SIST EN 62386-207:2010
62386-207 © IEC:2009 – 3 –
Figure 25 – “RESERVED APPLICATION EXTENDED COMMANDS”.42
Table 1 – Fast fade time .10
Table 2 – Declaration of variables.10
Table 3 – Summary of the application extended command set .17
Table 4 – Parameters for the test “REFERENCE SYSTEM POWER: Command in-
between”.31
Table 5 – Parameters for test “SELECT DIMMING CURVE” .35
Table 6 – Parameters for test “FAST FADE TIME” .36
Table 7 – Parameters for test “ENABLE DEVICE TYPE: Application extended
commands” .38
Table 8 – Parameters for test “ENABLE DEVICE TYPE: Application extended
configuration commands 1” .40
---------------------- Page: 9 ----------------------
SIST EN 62386-207:2010
– 4 – 62386-207 © IEC:2009
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
DIGITAL ADDRESSABLE LIGHTING INTERFACE –
Part 207: Particular requirements for control gear –
LED modules (device type 6)
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 62386-207 has been prepared by subcommittee 34C: Auxiliaries
for lamps, of IEC technical committee 34: Lamps and related equipment.
The text of this standard is based on the following documents:
FDIS Report on voting
34C/888/FDIS 34C/892/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
---------------------- Page: 10 ----------------------
SIST EN 62386-207:2010
62386-207 © IEC:2009 – 5 –
This Part 207 is intended to be used in conjunction with IEC 62386-101 and IEC 62386-102,
which contain general requirements for the relevant product type (control gear or control
devices).
A list of all parts of the IEC 62386 series, under the general title Digital addressable lighting
interface, can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition; or
• amended.
---------------------- Page: 11 ----------------------
SIST EN 62386-207:2010
– 6 – 62386-207 © IEC:2009
INTRODUCTION
This first edition of IEC 62386-207 is published in conjunction with IEC 62386-101 and
IEC 62386-102. The division of IEC 62386 into separately published parts provides for ease
of future amendments and revisions. Additional requirements will be added as and when a
need for them is recognised.
This International Standard, and the other parts that make up the IEC 62386-200 series, in
referring to any of the clauses of IEC 62386-101 or IEC 62386-102, specify the extent to
which such a clause is applicable and the order in which the tests are to be performed. The
parts also include additional requirements, as necessary. All parts that make up
IEC 62386-200 series are self-contained and therefore do not include references to each
other.
Where the requirements of any of the clauses of IEC 62386-101 or IEC 62386-102 are
referred to in this International Standard by the sentence "The requirements of IEC 62386-
1XX, clause ‘n’ apply”, this sentence is to be interpreted as meaning that all requirements of
the clause in question of Part 101 or Part 102 apply, except any which are inapplicable to the
specific type of lamp control gear covered by Part 207.
All numbers used in this International Standard are decimal numbers unless otherwise noted.
Hexadecimal numbers are given in the format 0xVV, where VV is the value. Binary numbers
are given in the format XXXXXXXXb or in the format XXXX XXXX, where X is 0 or 1; 'x' in
binary numbers means 'don't care'.
---------------------- Page: 12 ----------------------
SIST EN 62386-207:2010
62386-207 © IEC:2009 – 7 –
DIGITAL ADDRESSABLE LIGHTING INTERFACE –
Part 207: Particular requirements for control gear –
LED modules (device type 6)
1 Scope
This International Standard specifies a protocol and test procedures for the control by digital
signals of electronic control gear for use on a.c. or d.c. supplies, associated with LED
modules.
NOTE Tests in this standard are type tests. Requirements for testing individual control gear during production are
not included.
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 62386-101:2009, Digital addressable lighting interface – Part 101: General requirements
– System
IEC 62386-102:2009, Digital addressable lighting interface – Part 102: General requirements
– Control gear
3 Terms and definitions
For the purposes of this document, the terms and definitions given in Clause 3 of
IEC 62386-101:2009 and Clause 3 of IEC 62386-102:2009 shall apply, with the following
additional definitions.
3.1
reference measurement
process during which control gear determines the actual LED load with internal procedures
and measurements
NOTE The details of this process are a matter of detailed design of control gear and are outside the scope of this
standard.
3.2
detection of load decrease
recognition that the actual LED load is significantly below the load measured during a
successful “reference measurement”
NOTE The criteria for regarding a load increase or decrease as significant can only be decided by the
manufacturer and these criteria should be described in the manual.
3.3
detection of load increase
recognition that the actual LED load is significantly above the load measured during a
successful “reference measurement”
NOTE The criteria for regarding a load increase or decrease as significant can only be decided by the
manufacturer and these criteria should be described in the manual.
---------------------- Page: 13 ----------------------
SIST EN 62386-207:2010
– 8 – 62386-207 © IEC:2009
3.4
current protector
protective device switching off the output if the actual LED load differs by more than ΔP from
the load detected during the “reference measurement”
NOTE The value ΔP can only be specified by the manufacturer of the control gear and this value should be stated
in the manual.
3.5
thermal overload
scenario where the maximum permissible control gear temperature is exceeded
3.6
thermal shut down
scenario where control gear switches off the LED because of a persistent thermal overload
3.7
light level reduction due to thermal overload
reduction of light level with the objective of decreasing control gear temperature
4 General
The requirements of Clause 4 of IEC 62386-101:2009 and Clause 4 of IEC 62386-102:2009
apply.
5 Electrical specification
The requirements of Clause 5 of IEC 62386-101:2009 and Clause 5 of IEC 62386-102:2009
apply.
6 Interface power supply
The requirements of Clause 6 of IEC 62386-101:2009 and Clause 6 of IEC 62386-102:2009
apply, if a power supply is integrated with the control gear.
7 Transmission protocol structure
The requirements of Clause 7 of IEC 62386-101:2009 and Clause 7 of IEC 62386-102:2009
apply.
8 Timing
The requirements of Clause 8 of IEC 62386-101:2009 and Clause 8 of IEC 62386-102:2009
apply.
9 Method of operation
The requirements of Clause 9 of IEC 62386-101:2009 and Clause 9 of IEC 62386-102:2009
apply, except as follows:
Addition to Clause 9 of IEC 62386-102:2009:
---------------------- Page: 14 ----------------------
SIST EN 62386-207:2010
62386-207 © IEC:2009 – 9 –
9.9 Detection of load decrease
If the actual LED load is significantly below the load measured during a successful “reference
measurement”, the gear may switch off the lamp if this is necessary for its safe operation. The
flag bit ‘load decrease’ is to be set.
9.10 Detection of load increase
If the actual LED load is significantly above the load measured during a successful “reference
measurement”, the gear may switch off if this is necessary for its safe operation. The flag bit
‘load increase’ is to be set.
9.11 Current protector
If the actual LED load of the control gear differs by more than a defined amount ΔP from the
load detected during the reference measurement, the current protector becomes active and
switches off the LED.
The current protector shall not become active until there has been a successful reference
measurement.
There are two possible situations in which the current protector becomes active:
– Overload: The actual LED load is higher than the load detected during the reference
measurement by at least ΔP.
– Underload: The actual LED load is lower than the load detected during the reference
measurement by at least ΔP.
The current protector shall become inactive either on mains voltage interruption or on receipt
of a command which causes the arc power level to be 0. If after switching on again, the
situation causing the current protector to become active still remains, the current protector
shall become active again.
The current protector can be enabled and disabled by the commands 225 “ENABLE
CURRENT PROTECTOR” and 226 “DISABLE CURRENT PROTECTOR”.
An active current protector shall become inactive upon reception of command 226 “DISABLE
CURRENT PROTECTOR”.
If the current protector is active, command 224 “REFERENCE SYSTEM POWER” shall be
ignored.
9.12 LED replacement on gear with load increase/decrease or current protector feature
If a LED is replaced with one of a different wattage without a new “REFERENCE SYSTEM
POWER” measurement being performed, the control gear shall detect a load increase or load
decrease as appropriate.
NOTE If a LED is replaced with one of the same wattage, the user should initiate a new ‘REFERENCE SYSTEM
POWER’ measurement only if this is recommended by the manufacturer.
9.13 Fast Fade Time
The Fast Fade Time is used instead of the Fade Time if the Fade Time is equal to 0. The Fast
Fade Time can be set to zero or to any value in the range “Min Fast Fade Time” to 27 as
defined in Table 1.
Programming the Fast Fade Time to 0 means “no fade” (change of light output as quickly as
possible).
---------------------- Page: 15 ----------------------
SIST EN 62386-207:2010
– 10 – 62386-207 © IEC:2009
Table 1 – Fast fade time
Fast fade time Fast fade time Fast fade time Fast fade time
N° N° N° N°
ms ms ms ms
0 < 25 7 175 14 350 21 525
1 25 8 200 15 375 22 550
2 50 9 225 16 400 23 575
3 75 10 250 17 425 24 600
4 100 11 275 18 450 25 625
5 125 12 300 19 475 26 650
6 150 13 325 20 500 27 675
The “Min Fast Fade Time” can be queried by command 253 “QUERY MIN FAST FADE TIME”.
10 Declaration of variables
The requirements of Clause 10 of IEC 62386-102:2009 apply, with the following additional
variables for this device type, as indicated in Table 2:
Table 2 – Declaration of variables
b
Variable Default value Reset value Range of validity Memory
(control gear leaves
the factory)
“MIN FAST FADE factory burn-in no change 1 – 27 1 byte ROM
TIME”
“FAST FADE TIME” 0 0 0 1 byte
MIN FAST FADE TIME
– 27
“GEAR TYPE” factory burn-in no change 0 – 255 1 byte ROM
“POSSIBLE factory burn-in no change 0 – 255 1 byte ROM
OPERATING MODES”
“FEATURES” factory burn-in no change 0 – 255 1 byte ROM
C a
“FAILURE STATUS” ???? ???? no change 0 – 255 1 byte RAM
C a
“OPERATING MODE” 0000 ???? no change except 0 – 255 1 byte RAM
bit 4 is reset to 0
“DIMMING CURVE” 0 0 0 – 1 1 byte
“EXTENDED VERSION 1 no change 0 – 255 1 byte ROM
NUMBER”
(See command 255)
"DEVICE TYPE" 6 no change 0 – 254 1 byte ROM
? = undefined
a
Bit 7 of “FAILURE STATUS” and bit 4 of “OPERATING MODE” shall be stored in persistent memory.
b
Persistent memory (storage time indefinite) if not stated otherwise.
c
Power up value, except bit 7 of “FAILURE STATUS” and bits 4-7 of “OPERATING MODE”
---------------------- Page: 16 ----------------------
SIST EN 62386-207:2010
62386-207 © IEC:2009 – 11 –
11 Definition of commands
The requirements of Clause 11 of IEC 62386-102:2009 apply, except as follows:
11.3.1 Queries related to status information
Command 146: YAAA AAA1 1001 0010 “QUERY LAMP FAILURE”
Replacement:
Ask if there is a lamp problem at the given address. Answer shall be ‘Yes’ or ‘No’.
“Yes” means either open circuit or short circuit or load increase or load decrease or current
protector active.
“No” does not necessarily imply that no lamps have failed.
Command 153: YAAA AAA1 1001 1001 “QUERY DEVICE TYPE”
Replacement:
The answer shall be 6.
11.3.4 Application extended commands
Replacement:
Application extended commands shall be preceded by command 272
“ENABLE DEVICE TYPE 6”. For device types other than 6 these commands may be used in a
different way. A control gear for LED modules shall not react to application extended
commands preceded by command 272 “ENABLE DEVICE TYPE X” with X ≠ 6.
11.3.4.1 Application extended configuration commands
Every configuration command (224 to 228) shall be received a second time within 100 ms
before it is executed to reduce the probability of incorrect reception. No other commands
addressing the same control gear shall be sent between these two commands, otherwise the
first such command shall be ignored and the respective configuration sequence shall be
aborted.
Command 272 shall be sent before the two instances of the respective configuration
command, but not repeated between them (see Figure 1).
application application
extended extended
command 272
configuration configuration
command command
max. 100 ms
IEC 1665/09
Figure 1 – Application extended configuration command sequence example
All values of DTR shall be checked against the values mentioned in Clause 10, i.e. the value
shall be set to the upper / lower limit if it is above / below the valid range specified in -
Clause 10.
---------------------- Page: 17 ----------------------
SIST EN 62386-207:2010
– 12 – 62386-207 © IEC:2009
Command 224: YAAA AAA1 1110 0000 “REFERENCE S
...