SIST-TS CLC/TS 50131-2-2:2005
(Main)Alarm systems - Intrusion systems -- Part 2-2: Requirements for passive infrared detectors
Alarm systems - Intrusion systems -- Part 2-2: Requirements for passive infrared detectors
Interim TS before EN status (draft expected November 2006 for circulation in spring 2007) * Standstill maintained
Alarmanlagen - Einbruchmeldeanlagen -- Teil 2-2: Anforderungen an Passiv-Infrarotmelder
Systèmes d'alarme - Systèmes d'alarme intrusion -- Partie 2-2: Exigences pour détecteurs infrarouges passifs
Alarmni sistemi – Sistemi za javljanje vloma – 2-2. del: Zahteve za pasivne infrardeče javljalnike
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST-TS CLC/TS 50131-2-2:2005
01-februar-2005
$ODUPQLVLVWHPL±6LVWHPL]DMDYOMDQMHYORPD±GHO=DKWHYH]DSDVLYQH
LQIUDUGHþHMDYOMDOQLNH
Alarm systems - Intrusion systems -- Part 2-2: Requirements for passive infrared
detectors
Alarmanlagen - Einbruchmeldeanlagen -- Teil 2-2: Anforderungen an Passiv-
Infrarotmelder
Systèmes d'alarme - Systèmes d'alarme intrusion -- Partie 2-2: Exigences pour
détecteurs infrarouges passifs
Ta slovenski standard je istoveten z: CLC/TS 50131-2-2:2004
ICS:
13.310 Varstvo pred kriminalom Protection against crime
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
SIST-TS CLC/TS 50131-2-2:2005 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
---------------------- Page: 2 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
TECHNICAL SPECIFICATION CLC/TS 50131-2-2
SPECIFICATION TECHNIQUE
TECHNISCHE SPEZIFIKATION August 2004
ICS 13.310
English version
Alarm systems - Intrusion systems
Part 2-2: Requirements for passive infrared detectors
Systèmes d'alarme - Alarmanlagen -
Systèmes de détection d'intrusion Einbruchmeldeanlagen
Partie 2-2: Exigences pour détecteurs Teil 2-2: Anforderungen an Passiv-
infrarouges passifs Infrarotmelder
This Technical Specification was approved by CENELEC on 2004-05-04.
CENELEC members are required to announce the existence of this TS in the same way as for an EN and to
make the TS available promptly at national level in an appropriate form. It is permissible to keep conflicting
national standards in force.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden,
Switzerland and United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2004 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. CLC/TS 50131-2-2:2004 E
---------------------- Page: 3 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
CLC/TS 50131-2-2:2004 - 2 -
Foreword
This Technical Specification was prepared by the Technical Committee CENELEC TC 79, Alarm
systems.
The text of the draft was submitted to the vote at the meeting of TC 79 in Madrid and was
approved by CENELEC as CLC/TS 50131-2-2 on 2004-05-04. Standstill is maintained.
The following date was fixed:
- latest date by which the existence of the TS (doa) 2004-11-04
has to be announced at national level
NOTE Latest date by which the TS has to be voted as EN: 2 years maximum after dav of TS.
---------------------- Page: 4 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
- 3 - CLC/TS 50131-2-2:2004
Contents
Page
1 Scope.4
2 Normative references.4
3 Definitions and abbreviations .4
4 Functional requirements.6
4.1 Indication signals or messages .6
4.2 Detection.7
4.3 Operational requirements .9
4.4 Immunity to incorrect operation.9
4.5 Tamper security.10
4.6 Electrical requirements .11
4.7 Environmental classification and conditions .12
5 Marking, identification and documentation .12
5.1 Marking and/or identification.12
5.2 Documentation .12
6 Testing.13
6.1 General test conditions.13
6.2 Basic detection test .14
6.3 Walk testing .14
6.4 Verification of detection performance .15
6.5 Switch-on delay, time interval between signals and indication of detection.17
6.6 Fault condition signals or messages: self tests.18
6.7 Immunity to incorrect operation.18
6.8 Tamper security.19
6.9 Electrical tests.20
6.10 Environmental classification and conditions .22
6.11 Marking, identification and documentation.23
Annex A (normative) Format of standard test magnets.24
Annex B (normative) General testing matrix.25
Annex C (normative) Walk test diagrams.27
Annex D (normative) Procedure for calculation of average temperature difference .30
Annex E (informative) Basic detection target for the basic test of detection capability .32
Annex F (informative) Calibration heat source .33
Annex G (normative) Calibration of the standard walk test target. .35
Annex H (informative) Equipment for walk test velocity control.35
Annex J (informative) Immunity to visible and near infrared radiation:
notes on calibration of the light source .36
Annex K (informative) Example list of small tools suitable for testing immunity
of casing to attack.37
Annex L (informative) Test for resistance to re-orientation of adjustable mountings.38
Figure A.1 - Format of standard test magnets.24
Figure C.1 - Detection across the boundary, & effect of control adjustments .27
Figure C.2 - Detection within the boundary, & effect of control adjustments.27
Figure C.3 - High velocity and intermittent movement .28
Figure C.4 - Close-in detection .28
Figure C.5 - Significant range reduction.29
Figure L.1 - Re-orientation test.38
Table 1 - Indication signals or messages .7
Table 2 - General walk test velocity and attitude requirements .8
Table 3 - Tamper security requirements .11
Table 4 - Electrical requirements .11
Table 5 - Range of materials for masking tests .20
Table 6 - Environmental tests, operational.23
Table 7 - Environmental tests, endurance.23
---------------------- Page: 5 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
CLC/TS 50131-2-2:2004 - 4 -
Introduction
This Technical Specification is a specification for passive infrared detectors (to be referred to as
the detector) used as part of intrusion detection systems installed in buildings. It includes four
security grades and the first three environmental classes.
The purpose of a detector is to detect the broad spectrum infrared radiation emitted by an intruder
and to provide the necessary range of signals or messages to be used by the rest of the intruder
alarm system.
The number and scope of these signals or messages will be more comprehensive for systems that
are specified at the higher grades.
This specification is only concerned with the requirements and tests for the detector. Other types
of detector are covered by other documents identified as CLC/TS 50131-2-x.
The requirement in EN 50131-1 that detectors in grade 3 and 4 systems shall include a means to
detect a significant reduction in range may be met either by detectors having the appropriate
function (4.2.3) or by suitable system design.
1 Scope
This Technical Specification provides for security grades 1 to 4 (see EN 50131-1), specific or non-
specific wired or wire-free detectors, and uses environmental classes I to III (see EN 50130-5).
A function designated in the specification as not required for a particular grade may be provided
by the manufacturer. If provided, it will be tested, and shall meet all relevant requirements of any
higher grade. If it passes, the manufacturer may claim it as an extra feature, which does not alter
the overall grading of the detector.
The specification does not apply to system interconnections.
2 Normative references
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of the
referenced document (including any amendments) applies.
EN 50130-4:1995 Alarm systems - Part 4: Electromagnetic compatibility - Product family
standard: Immunity requirements for components of fire, intruder and
social alarm systems
EN 50130-5:1998 Alarm systems - Part 5: Environmental test methods
EN 50131-1:1997 Alarm Systems - Intrusion systems - Part 1: General requirements
EN 50131-6:1997 Alarm systems - Intrusion systems - Part 6: Power supplies
EN 60529:1991 Degree of protection provided by enclosures (IP code)
3 Definitions and abbreviations
For the purpose of this specification, the following definitions and abbreviations apply in addition
to those given in EN 50131-1.
3.1
alert/set mode
state of operation in which a detector shall generate an intrusion signal or message in response to
stimulation by a human being or the standard walk test target
3.2
basic detection target
heat source designed to verify the operation of a detector
---------------------- Page: 6 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
- 5 - CLC/TS 50131-2-2:2004
3.3
ceiling mount detector
detector capable of sensing human movement from a mounting position on the ceiling
3.4
curtain detector
detector capable of sensing human movement through a continuous layer of detection zones
3.5
incorrect operation
physical condition that causes an inappropriate signal or message from a detector
3.6
local memory
storage medium situated on board the detector, having the capability to record signals or
messages generated by the detector
3.7
long range detector
detector capable of sensing human movement in an extended field of view with horizontal angular
coverage less than 10°
3.8
masking
interference with the detector input capability by the introduction of a physical barrier such as
metal, plastics, paper or sprayed paints or lacquers in close proximity to the detector
3.9
passive infrared detector
detector of the broad-spectrum infrared radiation emitted by a human being
3.10
simulated walk test target
non-human or synthetic heat source designed to simulate the standard walk test target
3.11
standard walk test target
human being of standard weight and height clothed in close fitting clothing appropriate to the
simulation of an intruder
3.12
standby/unset mode
state of operation in which a detector is not required to generate an alarm signal or message in
response to stimulation by a human being or a standard walk test target
3.13
test mode
state of operation in which a detector will activate an intrusion indicator in response to stimulation
by a human being or the standard walk test target
3.14
volumetric detector
detector capable of sensing human movement in a volume such as a room with a field of view with
horizontal angular coverage greater than 45°
---------------------- Page: 7 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
CLC/TS 50131-2-2:2004 - 6 -
3.15
walk test
operational test during which a detector is stimulated by the standard walk test target in a
controlled environment
3.16
walk test attitude, crawling
crawling attitude shall consist of the standard walk test target moving with hands and knees in
contact with the floor
3.17
walk test attitude, upright
upright attitude shall consist of the standard walk test target standing and walking with arms by
the sides of the body. The standard walk test target begins and ends a traverse with feet together
3.18
wire free detector
detector connected to the control and indicating equipment by interconnection such as radio
frequency signals
3.19 Abbreviations
HDPE high density polyethylene
PIR passive infrared
EMC electromagnetic compatibility
SWT standard walk test target
BDT basic detection target
FOV field of view
4 Functional requirements
4.1 Indication signals or messages
All detectors shall have an alert/set mode. Grades 3 and 4 shall have an unset mode. If a detector
has only one mode of operation, then it shall always be in the alert/set mode. Tamper detection
shall be active in all modes.
Each possible mode of operation is determined by the status of the intrusion detection system with
which the detector communicates. The detector signals or messages in these modes of operation
shall function in accordance with Table 1. All signals or messages apply to all modes of operation
unless stated otherwise. Where a memory display or intrusion indicator is provided on board the
detector, it shall not function in the alert/set mode.
---------------------- Page: 8 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
- 7 - CLC/TS 50131-2-2:2004
Table 1 - Indication signals or messages
Event Grades Intrusion signal Tamper signal or Fault signal or
or message message message
Intrusion 1 – 4 Required * Not permitted Not permitted
1 – 4 Not permitted Not permitted Not permitted
No stimulus
Masking 1 – 2 Not required Not required Not required
3 – 4 Required ** Not required Required **
Tamper 1 – 4 Not required Required Not required
Low supply voltage 1 – 2 Not required Not required Not required
(external)
3 – 4 Not required Not required Required
Total loss of 1 Not required Not required Not required
external power
2 – 4 *** Required Not required Not required
supply
Local self-test pass 1 – 4 Not permitted Not permitted Not permitted
Local self-test 1 – 2 Not permitted Not permitted Not required
3 – 4 Not permitted Not permitted Required
fail
Remote self-test 1 – 2 Not required Not permitted Not permitted
pass
3 – 4 Required Not permitted Not permitted
Remote self-test 1 – 2 Not permitted Not permitted Not required
fail
Not permitted Not permitted Required
3 – 4
* Not required in unset/standby mode: required in test mode.
** An independent masking signal or message may be provided instead.
*** Not required for bus systems.
NOTE For internal power supplies, see EN 50131-6.
4.2 Detection
4.2.1 Detection performance
The detector shall generate an intrusion signal or message when the standard or simulated walk
test target moves within the boundary for a distance of 3 m. The detector shall also generate an
intrusion signal or message when the standard or simulated walk test target moves across the
manufacturer’s claimed boundary of detection.
---------------------- Page: 9 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
CLC/TS 50131-2-2:2004 - 8 -
The velocities and attitudes are as specified in Table 2.
Table 2 - General walk test velocity and attitude requirements
Test Grade 1 Grade 2 Grade 3 Grade 4
Required Required Required Required
Detection across the boundary
Velocity (m/s) 1,0 1,0 1,0 1,0
Attitude
Upright Upright Upright Upright
Required Required Required Required
Detection within the boundary
Velocity (m/s) 0,3 0,3 0,2 0,1
Attitude
Upright Upright Upright Upright
Not required Required Required Required
Detection at high velocity
Velocity (m/s) # 2,0 2,5 3,0
Attitude
# Upright Upright Upright
2,0 2,0 0,5 0,5
Close-in detection performance (dist, m)
Velocity (m/s) 0,5 0,4 0,3 0,2
Attitude
Upright Upright Crawling Crawling
Not required Not required Required Required
Intermittent movement detection
performance *
# # 0,2 (1,0) 0,1 (1,0)
Velocity (m/s)
# # Upright Upright
Attitude
Not required Required Required Required
Effect of control adjustments **
Velocity (m/s) # 0,3 0,2 0,1
Attitude
# Upright Upright Crawling
Not required Not required Not required Not required
Significant reduction of specified range
*** ***
Velocity (m/s)
# # # (1,0) 1,0
Attitude
# # # Upright Upright
* The intermittent movement shall consist of the SWT moving a distance of 1 m by taking two 0,2 (5) m steps (at
1,0 m/s), pausing for 5 s then continuing until the SWT has left the area for a further 1 s.
** If means for continuous adjustment of detection sensitivity is provided, the effect of any setting shall be indicated
with a tolerance of less than 25 % of the maximum reading.
*** The means to detect a significant reduction in range may be met either by detectors having the appropriate
function (4.2.3) or by suitable system design.
# To test features that are not required in a particular grade, parameters from a higher grade shall be specified.
4.2.2 Indication of detection
An indicator, if provided at the detector, shall indicate when detection causes an intrusion signal
or message. This indicator shall be capable of being enabled/disabled. This operation shall only
be performed locally after removal of the cover or remotely at the control and indicating
equipment.
4.2.3 Significant reduction of specified range
If the facility to detect reduction in specified range is provided, then range reduction along the
principal axis of detection of more than 50 % shall generate an alarm or fault signal or message
within a maximum period of 180 s, according to the requirements given in Table 2. The
requirements of 4.3.5 (self test) and 4.5.5 (resistance to masking) can provide range reduction
detection.
If additional equipment is required to detect significant reduction in range, reference shall be
made to the manufacturer’s documentation.
---------------------- Page: 10 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
- 9 - CLC/TS 50131-2-2:2004
4.3 Operational requirements
4.3.1 Time interval between intrusion signals or messages
Wired detectors shall be able to provide an intrusion signal or message not more than 15 s after
the end of the preceding intrusion signal or message. Wire free detectors shall perform the same
function in a time as follows:
Grade 1: 300 s,
Grade 2: 300 s,
Grade 3: 30 s,
Grade 4: 15 s (see EN 50131-1 for amendment).
4.3.2 Switch on delay
The detector shall meet all functional requirements within 180 s of the power supply reaching its
nominal voltage.
4.3.3 Fault condition signalling
When a detector suffers a fault, a fault signal or message shall be generated in accordance with
the manufacturer's specification, and the provisions of Table 1.
4.3.4 Power supply faults
Detectors of all grades shall signal complete power failure according to the provisions of Table 1.
Additionally, detectors of grades 3 and 4 shall signal when the supply voltage moves below the
manufacturer’s specified range according to the provisions of Table 1.
4.3.5 Self tests
Grade 3 and grade 4 detectors shall monitor the function of the sensor and associated on-board
signal processing circuitry. A self-test shall be performed under the control of the detector.
When a remote self-test is initiated, a signal or message shall be generated between 1 s and 5 s
later, and shall be signalled within 5 s of that initiation. The test duration shall not exceed 10 s.
After the test is completed, the detector shall resume its previous state within 5 s. Fault indication
requirements appear in Table 1.
Where normal operation of the detector is inhibited during a local test of function monitoring the
detector inhibition time shall be limited to a maximum of 15 s in a period of 1 h.
4.4 Immunity to incorrect operation
The detector shall be considered to have sufficient immunity to incorrect operation if the following
requirements have been met. No intrusion signal or message shall be generated during the tests.
4.4.1 Immunity to air flow
The detector shall not generate any signal or message when air is blown over the face of the
detector.
4.4.2 Immunity to visible and near infrared radiation
The detector shall not generate any signal or message when visible and near Infrared radiation
from a light source such as a car headlamp is directed on to the front window or lens through a
pane of glass.
---------------------- Page: 11 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
CLC/TS 50131-2-2:2004 - 10 -
4.5 Tamper security
Tamper security requirements for each grade of detector are shown in Table 3.
4.5.1 Prevention of unauthorized access to the inside of the detector through covers and
existing holes
Access holes shall not allow interference with the operation of the detector by probing with
commonly available tools. Damage shall not be caused that would be visible to a person with
normal eyesight viewing from a distance of 1 m with the detector illuminated at a level of
2 000 lux.
A tool shall be required to open the unit. All covers giving access to components which could
affect adversely the operation of the detector shall be fitted with a tamper detection device in
accordance with Table 3. A tamper signal or message shall be generated before access is gained
with any tool.
4.5.2 Detection of removal from the mounting surface
A tamper detection device shall be fitted which signals a tamper if the detector is removed from
the mounting surface, in accordance with Table 3. Mounting screws shall only be accessible from
within the unit. Operation of the device shall not be preventable by external means. This device
shall activate before access can be gained to it.
4.5.3 Resistance to re-orientation
Where the orientation of a detector can be adjusted, resistance to re-orientation shall be provided
in accordance with Table 3.
The alignment of the boundary of detection shall not have changed by more than 5° due to a
grade dependent applied torque. Alternatively a tamper detection device shall signal before the
alignment of the boundary of detection has moved by 5°. One test arrangement is described in
Annex L.
If a detector provides a means to adjust the orientation of its coverage pattern, the access to this
means shall be protected by a tamper device.
4.5.4 Immunity to magnetic field interference
It shall not be possible to inhibit any output or signalling devices with a magnet of grade
dependent remanence, according to Table 3. The form of standard magnets shall be as described
in Annex A.
4.5.5 Resistance to masking
Means shall be provided to detect inhibition of the operation of the detector by covering its
sensing area and sensor, in the unset mode. The maximum response time for the masking
detection device shall be 180 s. Intrusion and fault signals or messages or a dedicated anti-
masking signal or message shall be generated. The signals or messages shall remain latched
until restored. Grade dependency appears in Table 3.
No anti-masking signal or message shall be generated by normal human movement at 1 m/s at a
distance greater than 1 m in the unset condition.
---------------------- Page: 12 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
- 11 - CLC/TS 50131-2-2:2004
Table 3 - Tamper security requirements
Requirement Grade 1 Grade 2 Grade 3 Grade 4
Resistance to access to the Required Required Required Required
inside of the detector
Not required Required Required
Removal from the mounting Required *
surface*
Not required Required Required Required
Resistance to re-orientation:
2 5 10
Applied torque (Nm)
Magnetic field immunity: Not required Required Required Required
Remanence (T) 0,15 0,3 1,2
Anti-masking: capability Not required Not required Required Required
* Required for wire free detectors only.
4.6 Electrical requirements
These requirements do not apply to detectors having internal power supplies. For these detectors
refer to EN 50131-6. For detectors having an external power supply, the requirements appear in
Table 4.
Table 4 - Electrical requirements
Test Grade 1 Grade 2 Grade 3 Grade 4
Required Required Required Required
Detector current consumption
Input voltage range & Not required Required Required Required
slow input voltage rise
Input voltage ripple Not required Required Required Required
Input voltage step change Not required Required Required Required
Not required Required Required Required
Total loss of supply
4.6.1 Detector current consumption
The detector's quiescent and maximum current consumption shall not exceed the figures claimed
by the manufacturer at the nominal input voltage.
4.6.2 Slow input voltage change (rise) and voltage range limits
The detector shall meet all functional requirements when the input voltage lies between ± 25 % of
the nominal value, or between the manufacturer’s stated values (range limits if greater). When the
supply voltage is raised slowly, the detector shall function normally at the specified range limits.
4.6.3 Input voltage ripple
The detector shall meet all functional requirements during the sinusoidal variation of the input
voltage by ± 10 % of nominal, at a frequency of 100 Hz.
4.6.4 Input voltage step change
No signals or messages shall be caused by a step in the input voltage between maximum or
minimum and nominal values of the input voltage.
4.6.5 Total loss of supply
An intrusion signal or message shall be caused by the total loss of the supply voltage.
---------------------- Page: 13 ----------------------
SIST-TS CLC/TS 50131-2-2:2005
CLC/TS 50131-2-2:2004 - 12 -
4.7 Environmental classification and conditions
4.7.1 Environmental classification
The environmental classification is described in EN 50131-1. All the relevant environmental tests
shall be carried out at the appropriate level for all security grades, as given in EN 50130-5.
4.7.2 Immunity to environmental conditions
All detectors shall meet the requirements of the relevant environmental class and equipment class
as specified by the manufacturer.
Impact tests shall not be carried out on delicate detector components such as LEDs, optical
windows or lenses.
For operational tests, the detector shall not generate unintentional intrusion, tamper, fault or other
signals or messages when subjected to the specified range of environmental conditions.
For endurance tests, the detector shall continue to meet the requirements of this specification
after being subjected to the specified range of environmental conditions.
5 Marking, identification and documentation
5.1 Marking and/or identification
Marking and/or identification shall be applied to the product in accordance with the requirements
of EN 50131-1.
5.2 Documentation
The product shall be accompanied with clear and concise documentation conforming to the main
systems document EN 50131-1.The documentation shall additionally state
a) a list of all options, functions (including any from higher grades), inputs, signals or messages,
indications and their re
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.