SIGNIFICANCE AND USE
6.1 This practice is used to determine the LR of specified glass types and constructions exposed to uniform lateral loads.
6.2 Use of this practice assumes:
6.2.1 The glass is free of edge damage and is properly glazed.
6.2.2 The glass has not been subjected to abuse.
6.2.3 The surface condition of the glass is typical of glass that has been in service for several years, and is weaker than freshly manufactured glass due to minor abrasions on exposed surfaces.
6.2.4 The glass edge support system is sufficiently stiff to limit the lateral deflections of the supported glass edges to no more than 1/175 of their lengths. The specified design load shall be used for this calculation.
6.2.5 The deflection of glass or support system, or both, shall not result in loss of glass edge support. The glass bite reduction or pullout shall be considered using the method referenced in (1).3
Note 2: Glass deflections are to be reviewed. This practice does not address aesthetic issues caused by glass deflection.
Note 3: This practice does not consider the effects of deflection on insulating glass unit seal performance.
Note 4: The designer/engineer must determine what constitutes sufficient glass edge support based on Annex A1, Non-Factored Load Charts.
6.3 Many other factors shall be considered in glass type and thickness selection. These factors include but are not limited to: thermal stresses, spontaneous breakage of tempered glass, the effects of windborne debris, excessive deflections, behavior of glass fragments after breakage, blast, seismic effects, building movement, heat flow, edge bite, noise abatement, and potential post-breakage consequences. In addition, considerations set forth in building codes along with criteria presented in safety-glazing standards and site-specific concerns may control the ultimate glass type and thickness selection.
6.4 For situations not specifically addressed in this standard, the design professional shall use enginee...
SCOPE
1.1 This practice covers procedures to determine the load resistance (LR) of specified glass types, including combinations of glass types used in a sealed insulating glass (IG) unit, exposed to a uniform lateral load of short or long duration, for a specified probability of breakage.
1.2 This practice applies to vertical and sloped glazing in buildings for which the specified design loads consist of wind load, snow load and self-weight with a total combined magnitude less than or equal to 15 kPa (315 psf). This practice shall not apply to other applications including, but not limited to, balustrades, glass floor panels, aquariums, structural glass members, and glass shelves.
1.3 This practice applies only to monolithic and laminated glass constructions of rectangular shape with continuous lateral support along one, two, three, or four edges. This practice assumes that (1) the supported glass edges for two, three, and four-sided support conditions are simply supported and free to slip in plane; (2) glass supported on two sides acts as a simply supported beam; and (3) glass supported on one side acts as a cantilever. For insulating glass units, this practice only applies to insulating glass units with four-sided edge support.
1.4 This practice does not apply to any form of wired, patterned, sandblasted, drilled, notched, or grooved glass. This practice does not apply to glass with surface or edge treatments that reduce the glass strength.
Note 1: Ceramic enamel is known to affect glass load resistance. Consult the manufacturer for guidance.
1.5 This practice addresses only the determination of the resistance of glass to uniform lateral loads. The final thickness and type of glass selected also depends upon a variety of other factors (see 6.3).
1.6 Charts in this practice provide a means to determine approximate maximum lateral glass deflection. Appendix X1 provides additional procedures to determine maximu...
- Standard65 pagesEnglish language
- Standard65 pagesEnglish language
SIGNIFICANCE AND USE
5.1 This standard procedure facilitates determination of the thickness of a glass construction required to resist a specified design load with a selected probability of breakage.
5.2 For optical purposes, ATCT cab glass typically utilize only annealed glass products. For this reason, some specifying authorities mandate its use and prohibit heat-strengthened and tempered glass in control cabs. This standard procedure therefore addresses the following glass constructions: annealed monolithic, annealed laminated, and insulating glass fabricated with annealed monolithic or annealed laminated glass, or both. In cases where the specifying authority approves the use of heat-strengthened or fully tempered glass in the control cab or in areas where optical characteristics do not apply but are deemed critical to the facility operation, the NFL values obtained from standard may be adjusted using appropriate Glass Type Factors (GTF) and procedures for their use as specified in Practice E1300.
5.3 Use of these procedures assume:
5.3.1 The glass is free of edge damage and is properly glazed,
5.3.2 The glass has not been subjected to abuse,
5.3.3 The surface condition of the glass is typical of glass that has been in service for several years and is significantly weaker than freshly manufactured glass due to minor abrasions on exposed surfaces,
5.3.4 The glass edge support system is sufficiently stiff to limit the lateral deflections of the supported glass edges to less than 1/175 of their lengths. The specified design load shall be used for this calculation, and
5.3.5 The center of glass deflection shall not result in loss of edge support. Typically maintaining center of glass deflection at or below the magnitude of three times the nominal glass thickness assures that no loss of edge support will occur.
5.4 Many other factors affect the selection of glass type and thickness. These factors include but are not limited to: thermal stresses, the effects of win...
SCOPE
1.1 This practice covers the determination of the thickness of glass installed in airport traffic control towers (ATCT) to resist a specified design loading with a selected probability of breakage less than or equal to either 1 lite per 1000 or 4 lites per 1000 at the first occurrence of the design wind loading.
1.2 The procedures apply to common outward sloping cab glass designs for which the specified loads do not exceed 15 kPa (313 psf).
1.3 The procedures assume control tower cab glass has an aspect ratio no greater than 3.
1.4 The procedures assume control tower cab glass has an area no less than 1.86 m2 (20 ft2).
1.5 The use of the procedures assumes the following:
1.5.1 Monolithic and laminated glass installed in ATCTs shall have continuous lateral support along two parallel edges, along any three edges, or along all four edges;
1.5.2 Insulating glass shall have continuous lateral support along all four edges; and
1.5.3 Supported glass edges are simply supported and free to slip in plane.
1.6 The procedures do not apply to any form of wired, patterned, etched, sandblasted, or glass types with surface treatments that reduce the glass strength.
1.7 The procedures do not apply to drilled, notched, or grooved glass.
1.8 The procedures address the determination of thickness and construction type to resist a specified design wind load at a selected probability of breakage. The final glass thickness and construction determined also depends upon a variety of other factors (see 5.4).
1.9 These procedures do not address blast loading on glass.
1.10 These procedures do not apply to triple-glazed insulating glass units.
1.11 The values stated in SI units are to be regarded as standard. The values given in parentheses after SI units are provided for information only and are not considered standard.
1.12 This standard does not purport to address all of the safety concerns, if any, assoc...
- Standard98 pagesEnglish language
- Standard98 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Glass is a brittle material with different time and temperature-dependent properties than other solid materials used as walkways surfaces. Therefore, the type of glass is an important consideration in the design and construction of glass treads and glass landings constructed with laminated glass.
4.2 Post-breakage glass retention is an important consideration in the design of a glass walkway system as a means of minimizing tripping, cutting/piercing injuries, or fall-through or fallout of the glass.
4.3 The structural design shall be confirmed by calculations by a licensed design professional in accordance with Section 5.
4.4 If testing is required (see 4.4.1 – 4.4.3) to verify post-glass breakage behavior of the glass walkway, the testing shall be in accordance with Section 6.
4.4.1 For laminates with two glass plies, verification testing is required.
4.4.2 For laminates with more than two glass plies, verification testing is not required provided that calculations completed in accordance with 4.3 demonstrate that the glass assembly has sufficient strength to sustain the full design load with any one glass ply broken.
4.4.3 When verifying post-breakage behavior by calculation, allowable glass stress for 10 min load duration in accordance with Table 1 shall be used for all load cases.
4.5 The manufacturer or designer of glass walkway systems shall provide installation directions and fabrication and installation tolerances of their systems.
4.6 The structural integrity of the glass walkway system after glass breakage shall be sufficient to support the design loads after any one glass ply is broken. If damage of any kind occurs, the walkway shall be cordoned off and the installation shall be inspected to ensure structural integrity and pedestrian safety of the system.
SCOPE
1.1 This practice addresses elements related to load-bearing glass walkways, glass treads, and glass landings constructed with laminated glass. This standard includes performance, design, and safe behavior considerations. It addresses the characteristics unique to glass and laminated glass. Issues that are common to all walkways, such as slip resistance, are addressed in existing referenced standards.
1.2 This practice does not address glass walkways constructed with monolithic glass, glass block, insulating glass units, glass tiles that are directly bonded to a non-glass structural substrate, or glass walkways intended to support vehicular traffic.
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system are not necessarily exact equivalents; therefore, to ensure conformance with the standard, each system shall be used independently of the other, and values from the two systems shall not be combined.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Glass specimens to be tested shall be mounted in a standard test frame with four sides supported, or in a test frame designed to represent specific glazing conditions.
5.2 Loads on glass in windows, curtain walls, and doors may vary greatly in magnitude, direction, and duration. Any design load (wind, snow, etc.) that can reasonably be applied to the test specimens or transformed into an equivalent uniform design load can be considered. Load transformation techniques are addressed in the literature (1, 2, 3).3
5.3 The strength of glass varies with many different factors including surface condition, load duration, geometry, relative humidity, and temperature (4). A thorough understanding of those strength variations is required to interpret results of this test method.
SCOPE
1.1 This proof load test method is a procedure to determine, with a 90 % confidence level, if the probability of breakage under design loads for a given population of glass specimens is less than a selected value. It is not intended to be a design standard for determining the load resistance of glass. Practice E1300 shall be used for this purpose.
1.2 This test method describes apparatus and procedures to select and apply a proof load to glass specimens, to determine the number of glass specimens to be tested, and to evaluate statistically the probability of breakage. This test method may be conducted using the standard test frame specified herein or a test frame of the user's design.
1.3 Proper use of this test method requires a knowledge of the principles of pressure measurement and an understanding of recommended glazing practices.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. Specific precautionary statements are given in Section 7.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard11 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Use of this practice assumes:
5.1.1 the glass edges shall be free from damage,
5.1.2 the glass shall be properly glazed,
5.1.3 the glass shall not have been subjected to abuse, and
5.1.4 the glass edge support allows in-plane movement of the glass due to thermal expansion and contraction.
5.2 This practice does not address all factors that cause thermally induced stresses in annealed glass. Factors that are not addressed include: transient thermal stresses, HVAC registers, thermally insulating window coverings, drop ceilings and other heat traps, increased solar irradiance caused by exterior reflections, variations in heat transfer coefficients other than those assumed for the steady state analysis described herein, and stresses induced by thermal sources other than the sun. Factors other than those listed above may also induce thermal stress.
5.3 Many other factors shall be considered in glass selection. These factors include, but are not limited to, mechanically induced stresses, wind effects, windborne debris impacts, excessive deflections, seismic effects, heat flow, noise abatement, potential post-breakage consequences, and so forth. In addition, considerations set forth in building codes along with criteria presented in safety glazing standards and site specific concerns may control the ultimate glass type and thickness selection.
5.4 The proper use of this practice is intended to reduce the risk of thermally induced breakage of annealed window glass in buildings.
SCOPE
1.1 This practice covers a procedure to determine the resistance of annealed architectural flat glass to thermally induced stresses caused by exposure to sun and shadows for a specified probability of breakage (Pb). Proper use of this procedure is intended to reduce the possibility of thermal breakage of annealed glass in buildings.
1.2 This practice applies to vertical or sloped glazing in buildings.
1.3 This practice applies to monolithic and laminated glass of rectangular shape and assumes that all glass edges are simply supported.
1.4 This practice applies only to annealed flat soda-lime silica glass with clean cut, seamed, flat ground, or ground and polished edges that are free from damage. The glass may be clear or tinted as well as coated (not including coatings that reduce emissivity of the glass).
1.5 This practice does not apply to any form of wired, patterned, etched, sandblasted, drilled, notched, or grooved glass or glass with surface and edge treatments, other than those described in 1.4, that alter the glass strength.
1.6 This practice does not address uniform loads such as wind and snow loads, safety requirements, fire, or impact resistance.
1.7 The values stated in SI units are to be regarded as standard. The values given in parentheses after SI units are provided for information only and are not considered standard. For conversion of quantities in various systems of measurements to SI units, refer to IEEE/ASTM SI-10.
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard10 pagesEnglish language
SIGNIFICANCE AND USE
5.1 This test method is a general procedure for testing architectural glass products under uniform static loads.
5.2 Loads on glass in windows, curtain walls, and doors may vary greatly in magnitude, direction, and duration. An understanding of wind loads on the building is required for selection of test loads and interpretation of results with respect to expected exposure at a particular site.
5.3 A thorough understanding of the variations of the strength of glass and the nature of loading is required to interpret results of this test method.
5.4 The proper use of this test method requires a knowledge of the principles of pressure, deflection, and strain measurement.
SCOPE
1.1 This test method is a general test procedure for load tests of glass subjected to uniform static loads. It is applicable for test protocols involving specified loads, load durations, and loading rates.
1.2 This test method is applicable to architectural flat glass of various types; for example, annealed, heat-strengthened, fully tempered, laminated, insulating, and combinations thereof.
1.3 This test method describes a process of applying specific test loads to glass. The test may be conducted using a standard test frame specified herein or a test frame of the user's design.
1.4 The values stated in SI units are to be regarded as standard. The values given in parentheses after SI units are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety problems, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements see Section 7.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard9 pagesEnglish language
- Standard9 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Glass is a brittle material with different time and temperature-dependent properties than other solid materials used as walkways surfaces. Therefore, the type of glass is an important consideration in the design and construction of glass treads and glass landings constructed with laminated glass.
4.2 Post-breakage glass retention is an important consideration in the design of a glass walkway system as a means of minimizing tripping, cutting/piercing injuries, or fall-through or fallout of the glass.
4.3 The structural design shall be confirmed by calculations by a licensed design professional in accordance with Section 5.
4.4 If testing is required (see 4.4.1 – 4.4.3) to verify post-glass breakage behavior of the glass walkway, the testing shall be in accordance with Section 6.
4.4.1 For laminates with two glass plies, verification testing is required.
4.4.2 For laminates with more than two glass plies, verification testing is not required provided that calculations completed in accordance with 4.3 demonstrate that the glass assembly has sufficient strength to sustain the full design load with any one glass ply broken.
4.4.3 When verifying post-breakage behavior by calculation, allowable glass stress for 10 min load duration in accordance with Table 1 shall be used for all load cases.
TABLE 1 Allowable Glass Stresses for Nominal Load Conditions
Note 1: An allowable stress reduction factor of 0.5 is recommended for disruptive surface treatments, for example, sandblasting, unless otherwise provided by the manufacturer. A glass stress reduction factor may be required for some acid etched or patterned glasses; consult the manufacturer.
Note 2: Values derived from Practice E1300, Table X9.1 (seamed edges), factored for load duration using Practice E1300, Equation X7.1, using n = 16 for annealed glass, n = 32 for heat strengthened glass, and n = 48 for tempered glass.
Glass Type
3-sec
MPa [psi]
10-min
MPa [psi]
60-min
MPa [p...
SCOPE
1.1 This practice addresses elements related to load-bearing glass walkways, glass treads, and glass landings constructed with laminated glass. This standard includes performance, design, and safe behavior considerations. It addresses the characteristics unique to glass and laminated glass. Issues that are common to all walkways, such as slip resistance, are addressed in existing referenced standards.
1.2 This practice does not address glass walkways constructed with monolithic glass, glass block, insulating glass units, glass tiles that are directly bonded to a non-glass structural substrate, or glass walkways intended to support vehicular traffic.
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
5.1 This standard procedure facilitates determination of the thickness of a glass construction required to resist a specified design load with a selected probability of breakage.
5.2 This standard procedure addresses the following glass constructions: annealed monolithic, annealed laminated, and insulating glass fabricated with annealed monolithic or annealed laminated glass, or both.
5.3 Use of these procedures assume:
5.3.1 The glass is free of edge damage and is properly glazed,
5.3.2 The glass has not been subjected to abuse,
5.3.3 The surface condition of the glass is typical of glass that has been in service for several years, and is significantly weaker than freshly manufactured glass due to minor abrasions on exposed surfaces,
5.3.4 The glass edge support system is sufficiently stiff to limit the lateral deflections of the supported glass edges to less than 1/175 of their lengths. The specified design load shall be used for this calculation, and
5.3.5 The center of glass deflection shall not result in loss of edge support. Typically maintaining center of glass deflection at or below the magnitude of three times the nominal glass thickness assures that no loss of edge support will occur.
5.4 Many other factors affect the selection of glass type and thickness. These factors include but are not limited to: thermal stresses, the effects of windborne debris, excessive deflections, behavior of glass fragments after breakage, seismic effects, heat flow, edge bite, noise abatement, potential post-breakage consequences, and so forth. In addition, considerations set forth in federal, state, and local building codes along with criteria presented in safety glazing standards and site specific concerns may control the ultimate glass type and thickness selection.
SCOPE
1.1 This practice covers the determination of the thickness of glass installed in airport traffic control towers (ATCT) to resist a specified design loading with a selected probability of breakage less than or equal to either 1 lite per 1000 or 4 lites per 1000 at the first occurrence of the design wind loading.
1.2 The procedures apply to common outward sloping cab glass designs for which the specified loads do not exceed 10 kPa (210 psf).
1.3 The procedures assume control tower cab glass has an aspect ratio no greater than 2.
1.4 The procedures assume control tower cab glass has an area no less than 1.86 square metres (20 square feet).
1.5 The procedures apply only to annealed monolithic, annealed laminated, or annealed insulating glass having a rectangular or trapezoidal shape.
1.6 The use of the procedures assumes the following:
1.6.1 Annealed monolithic and annealed laminated glass installed in ATCTs shall have continuous lateral support along two parallel edges, along any three edges, or along all four edges;
1.6.2 Insulating glass shall have continuous lateral support along all four edges; and
1.6.3 Supported glass edges are simply supported and free to slip in plane.
1.7 The procedures do not apply to any form of wired, patterned, etched, sandblasted, or glass types with surface treatments that reduce the glass strength.
1.8 The procedures do not apply to any form of heat treated glass, chemically strengthened glass, or any type of glass with surface treatments intended to increase the glass strength.
1.9 The procedures address the determination of thickness and construction type to resist a specified design wind load at a selected probability of breakage. The final glass thickness and construction determined also depends upon a variety of other factors (see 5.3).
1.10 These procedures do not address blast loading on glass.
1.11 The values stated in SI units are to be regarded as standard. The values given in parentheses are mathematical conversions to inch-pound units that are provided for information only and are not considered standard.
1.12 This standard do...
- Standard17 pagesEnglish language
- Standard17 pagesEnglish language
SIGNIFICANCE AND USE
5.1 This practice is used to determine the LR of specified glass types and constructions exposed to uniform lateral loads.
5.2 Use of this practice assumes:
5.2.1 The glass is free of edge damage and is properly glazed,
5.2.2 The glass has not been subjected to abuse,
5.2.3 The surface condition of the glass is typical of glass that has been in service for several years, and is weaker than freshly manufactured glass due to minor abrasions on exposed surfaces,
5.2.4 The glass edge support system is sufficiently stiff to limit the lateral deflections of the supported glass edges to no more than 1/175 of their lengths. The specified design load shall be used for this calculation.
5.2.5 The deflection of glass or support system, or both, shall not result in loss of glass edge support.
Note 1: Glass deflections are to be reviewed. This practice does not address aesthetic issues caused by glass deflection.
Note 2: This practice does not consider the effects of deflection on insulating glass unit seal performance.
5.3 Many other factors shall be considered in glass type and thickness selection. These factors include but are not limited to: thermal stresses, spontaneous breakage of tempered glass, the effects of windborne debris, excessive deflections, behavior of glass fragments after breakage, blast, seismic effects, building movement, heat flow, edge bite, noise abatement, and potential post-breakage consequences. In addition, considerations set forth in building codes along with criteria presented in safety-glazing standards and site-specific concerns may control the ultimate glass type and thickness selection.
5.4 For situations not specifically addressed in this standard, the design professional shall use engineering analysis and judgment to determine the LR of glass in buildings.
SCOPE
1.1 This practice describes procedures to determine the load resistance (LR) of specified glass types, including combinations of glass types used in a sealed insulating glass (IG) unit, exposed to a uniform lateral load of short or long duration, for a specified probability of breakage.
1.2 This practice applies to vertical and sloped glazing in buildings for which the specified design loads consist of wind load, snow load and self-weight with a total combined magnitude less than or equal to 15 kPa (315 psf). This practice shall not apply to other applications including, but not limited to, balustrades, glass floor panels, aquariums, structural glass members, and glass shelves.
1.3 This practice applies only to monolithic and laminated glass constructions of rectangular shape with continuous lateral support along one, two, three, or four edges. This practice assumes that (1) the supported glass edges for two, three, and four-sided support conditions are simply supported and free to slip in plane; (2) glass supported on two sides acts as a simply supported beam; and (3) glass supported on one side acts as a cantilever. For insulating glass units, this practice only applies to insulating glass units with four-sided edge support.
1.4 This practice does not apply to any form of wired, patterned, sandblasted, drilled, notched, or grooved glass. This practice does not apply to glass with surface or edge treatments that reduce the glass strength.
1.5 This practice addresses only the determination of the resistance of glass to uniform lateral loads. The final thickness and type of glass selected also depends upon a variety of other factors (see 5.3).
1.6 Charts in this practice provide a means to determine approximate maximum lateral glass deflection. Appendix X1 provides additional procedures to determine maximum lateral deflection for glass simply supported on four sides.
1.7 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for mathematical conversions to inch-pound units that are provided for information only and are n...
- Standard62 pagesEnglish language
- Standard62 pagesEnglish language
- Standard62 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Glass specimens to be tested shall be mounted in a standard test frame with four sides supported, or in a test frame designed to represent specific glazing conditions.
5.2 Loads on glass in windows, curtain walls, and doors may vary greatly in magnitude, direction, and duration. Any design load (wind, snow, etc.) that can reasonably be applied to the test specimens or transformed into an equivalent uniform design load can be considered. Load transformation techniques are addressed in the literature (1, 2, 3).3
5.3 The strength of glass varies with many different factors including surface condition, load duration, geometry, relative humidity, and temperature (4). A thorough understanding of those strength variations is required to interpret results of this test method.
SCOPE
1.1 This proof load test method is a procedure to determine, with a 90 % confidence level, if the probability of breakage under design loads for a given population of glass specimens is less than a selected value. It is not intended to be a design standard for determining the load resistance of glass. Practice E1300 shall be used for this purpose.
1.2 This test method describes apparatus and procedures to select and apply a proof load to glass specimens, to determine the number of glass specimens to be tested, and to evaluate statistically the probability of breakage. This test method may be conducted using the standard test frame specified herein or a test frame of the user's design.
1.3 Proper use of this test method requires a knowledge of the principles of pressure measurement and an understanding of recommended glazing practices.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Specific precautionary statements are given in Section 7.
- Standard11 pagesEnglish language
- Standard11 pagesEnglish language
SIGNIFICANCE AND USE
5.1 This practice is used to determine the LR of specified glass types and constructions exposed to uniform lateral loads.
5.2 Use of this practice assumes:
5.2.1 The glass is free of edge damage and is properly glazed,
5.2.2 The glass has not been subjected to abuse,
5.2.3 The surface condition of the glass is typical of glass that has been in service for several years, and is weaker than freshly manufactured glass due to minor abrasions on exposed surfaces,
5.2.4 The glass edge support system is sufficiently stiff to limit the lateral deflections of the supported glass edges to no more than 1/175 of their lengths. The specified design load shall be used for this calculation.
5.2.5 The center of glass deflection will not result in loss of edge support.Note 1—This practice does not address aesthetic issues caused by glass deflection.
5.3 Many other factors shall be considered in glass type and thickness selection. These factors include but are not limited to: thermal stresses, spontaneous breakage of tempered glass, the effects of windborne debris, excessive deflections, behavior of glass fragments after breakage, seismic effects, heat flow, edge bite, noise abatement, potential post-breakage consequences, and so forth. In addition, considerations set forth in building codes along with criteria presented in safety glazing standards and site specific concerns may control the ultimate glass type and thickness selection.
5.4 For situations not specifically addressed in this standard, the design professional shall use engineering analysis and judgment to determine the LR of glass in buildings.
SCOPE
1.1 This practice describes procedures to determine the load resistance (LR) of specified glass types, including combinations of glass types used in a sealed insulating glass (IG) unit, exposed to a uniform lateral load of short or long duration, for a specified probability of breakage.
1.2 This practice applies to vertical and sloped glazing in buildings for which the specified design loads consist of wind load, snow load and self-weight with a total combined magnitude less than or equal to 15 kPa (315 psf). This practice shall not apply to other applications including, but not limited to, balustrades, glass floor panels, aquariums, structural glass members, and glass shelves.
1.3 This practice applies only to monolithic and laminated glass constructions of rectangular shape with continuous lateral support along one, two, three, or four edges. This practice assumes that (1) the supported glass edges for two, three, and four-sided support conditions are simply supported and free to slip in plane; (2) glass supported on two sides acts as a simply supported beam; and (3) glass supported on one side acts as a cantilever. For insulating glass units, this practice only applies to insulating glass units with four-sided edge support.
1.4 This practice does not apply to any form of wired, patterned, etched, sandblasted, drilled, notched, or grooved glass with surface and edge treatments that alter the glass strength.
1.5 This practice addresses only the determination of the resistance of glass to uniform lateral loads. The final thickness and type of glass selected also depends upon a variety of other factors (see 5.3).
1.6 Charts in this practice provide a means to determine approximate maximum lateral glass deflection. Appendix X1 provides additional procedures to determine maximum lateral deflection for glass simply supported on four sides.
1.7 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for mathematical conversions to inch-pound units that are provided for information only and are not considered standard.
1.8 Appendix X2 lists the key variables used in calculating the mandatory type factors in Tables 1-3 and comments on their conservative values. TABLE 1 Glass Type Factors (GTF) for a Single Lite of Mo...
- Standard59 pagesEnglish language
SIGNIFICANCE AND USE
This test method is a standard procedure to determine a stress pattern and estimate a probability of breakage of glass tested under uniform static loads.
Loads on glass in windows, curtain walls, and doors may vary greatly in magnitude, direction, and duration. An understanding of wind loads on the building is required for selection of test loads and interpretation of results with respect to expected exposure at a particular site.
The strength of glass varies with many different factors including surface condition, load duration, geometry, relative humidity, and temperature (1, 2, 3, 4).
A thorough understanding of the variations of the strength of glass and the nature of loading is required to interpret results of this test method.
The proper use of this test method requires a knowledge of the principles of pressure, deflection and strain measurement, stress/strain relationships, and statistical estimating techniques.
SCOPE
1.1 This test method is a nondestructive test procedure to establish the nature of stresses induced in glass subjected to uniform static loads. A procedure is provided for using this stress information to estimate the probability of breakage of the glass.
1.2 This test method is applicable to glass of various degrees of temper; for example, annealed, heat-strengthened, fully tempered, laminated, insulating, and combinations thereof.
1.3 This test method describes a process of applying specific test loads to glass. The test may be conducted using the standard test frame specified herein or a test frame of the user's design.
1.4 The values stated in SI units are to be regarded as standard. The values given in parentheses are mathematical conversions to inch-pound units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety problems, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements see Section 7.
- Standard17 pagesEnglish language
- Standard17 pagesEnglish language
SIGNIFICANCE AND USE
Use of this practice assumes:
the glass edges shall be free from damage,
the glass shall be properly glazed,
the glass shall not have been subjected to abuse, and
the glass edge support allows in-plane movement of the glass due to thermal expansion and contraction.
This practice does not address all factors that cause thermally induced stresses in annealed glass. Factors that are not addressed include: transient thermal stresses, HVAC registers, thermally insulating window coverings, drop ceilings and other heat traps, increased solar irradiance caused by exterior reflections, variations in heat transfer coefficients other than those assumed for the steady state analysis described herein, and stresses induced by thermal sources other than the sun. Factors other than those listed above may also induce thermal stress.
Many other factors shall be considered in glass selection. These factors include, but are not limited to, mechanically induced stresses, wind effects, windborne debris impacts, excessive deflections, seismic effects, heat flow, noise abatement, potential post-breakage consequences, and so forth. In addition, considerations set forth in building codes along with criteria presented in safety glazing standards and site specific concerns may control the ultimate glass type and thickness selection.
The proper use of this practice is intended to reduce the risk of thermally induced breakage of annealed window glass in buildings.
SCOPE
1.1 This practice covers a procedure to determine the resistance of annealed architectural flat glass to thermally induced stresses caused by exposure to sun and shadows for a specified probability of breakage (Pb). Proper use of this procedure is intended to reduce the possibility of thermal breakage of annealed glass in buildings.
1.2 This practice applies to vertical or sloped glazing in buildings.
1.3 This practice applies to monolithic and laminated glass of rectangular shape and assumes that all glass edges are simply supported.
1.4 This practice applies only to annealed flat soda-lime silica glass with clean cut, seamed, flat ground, or ground and polished edges that are free from damage. The glass may be clear or tinted as well as coated (not including coatings that reduce emissivity of the glass).
1.5 This practice does not apply to any form of wired, patterned, etched, sandblasted, drilled, notched, or grooved glass or glass with surface and edge treatments, other than those described in 1.4, that alter the glass strength.
1.6 This practice does not address uniform loads such as wind and snow loads, safety requirements, fire, or impact resistance.
1.7 The values stated in SI units are to be regarded as standard. The values given in parentheses are mathematical conversions to inch-pound units that are provided for information only and are not considered standard. For conversion of quantities in various systems of measurements to SI units refer to IEEE/ASTM SI-10.
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Standard10 pagesEnglish language
- Standard10 pagesEnglish language
SIGNIFICANCE AND USE
This standard procedure facilitates determination of the thickness of a glass construction required to resist a specified design load with a selected probability of breakage.
This standard procedure addresses the following glass constructions: annealed monolithic, annealed laminated, and insulating glass fabricated with annealed monolithic or annealed laminated glass, or both.
Use of these procedures assume:
The glass is free of edge damage and is properly glazed,
The glass has not been subjected to abuse,
The surface condition of the glass is typical of glass that has been in service for several years, and is significantly weaker than freshly manufactured glass due to minor abrasions on exposed surfaces,
The glass edge support system is sufficiently stiff to limit the lateral deflections of the supported glass edges to less than 1/175 of their lengths. The specified design load shall be used for this calculation, and
The center of glass deflection shall not result in loss of edge support. Typically maintaining center of glass deflection at or below the magnitude of three times the nominal glass thickness assures that no loss of edge support will occur.
Many other factors affect the selection of glass type and thickness. These factors include but are not limited to: thermal stresses, the effects of windborne debris, excessive deflections, behavior of glass fragments after breakage, seismic effects, heat flow, edge bite, noise abatement, potential post-breakage consequences, and so forth. In addition, considerations set forth in federal, state, and local building codes along with criteria presented in safety glazing standards and site specific concerns may control the ultimate glass type and thickness selection.
SCOPE
1.1 This practice covers the determination of the thickness of glass installed in airport traffic control towers (ATCT) to resist a specified design loading with a selected probability of breakage less than or equal to either 1 lite per 1000 or 4 lites per 1000 at the first occurrence of the design wind loading.
1.2 The procedures apply to common outward sloping cab glass designs for which the specified loads do not exceed 10 kPa (210 psf).
1.3 The procedures assume control tower cab glass has an aspect ratio no greater than 2.
1.4 The procedures assume control tower cab glass has an area no less than 1.86 square metres (20 square feet).
1.5 The procedures apply only to annealed monolithic, annealed laminated, or annealed insulating glass having a rectangular or trapezoidal shape.
1.6 The use of the procedures assumes the following:
1.6.1 Annealed monolithic and annealed laminated glass installed in ATCTs shall have continuous lateral support along two parallel edges, along any three edges, or along all four edges;
1.6.2 Insulating glass shall have continuous lateral support along all four edges; and
1.6.3 Supported glass edges are simply supported and free to slip in plane.
1.7 The procedures do not apply to any form of wired, patterned, etched, sandblasted, or glass types with surface treatments that reduce the glass strength.
1.8 The procedures do not apply to any form of heat treated glass, chemically strengthened glass, or any type of glass with surface treatments intended to increase the glass strength.
1.9 The procedures address the determination of thickness and construction type to resist a specified design wind load at a selected probability of breakage. The final glass thickness and construction determined also depends upon a variety of other factors (see 5.3).
1.10 These procedures do not address blast loading on glass.
1.11 The values stated in SI units are to be regarded as standard. The values given in parentheses are mathematical conversions to inch-pound units that are provided for information only and are not considered standard.
1.12 This standard does not purport to address all of the safety concerns, if ...
- Standard17 pagesEnglish language
- Standard17 pagesEnglish language
Frequently Asked Questions
E06.52 is a Technical Committee within ASTM International. It is named "Glass Use in Buildings". This committee has published 14 standards.
E06.52 develops ASTM standards in the area of Information technology. Currently, there are 14 published standards from this technical committee.
ASTM is a standardization organization that develops and publishes standards to support industry, commerce, and regulatory requirements.
A Technical Committee (TC) in ASTM is a group of experts responsible for developing international standards in a specific technical area. TCs are composed of national member body delegates and work through consensus to create standards that meet global industry needs. Each TC may have subcommittees (SCs) and working groups (WGs) for specialized topics.