Standard Guide for Fire-Resistance Experiments

SIGNIFICANCE AND USE
4.1 The methods and procedures set forth in this guide relate to the conduct and reporting of fire-resistance tests obtained from particular fire-resistance tested specimens tested using conditions different than those addressed by Test Methods E119.  
4.2 Data derived from fire tests conducted and reported under this guide are useful for general fire research and as potential input data for use in fire models.  
4.3 It is necessary that users of this guide have knowledge and understanding of the provisions of Test Methods E119, including those pertaining to conditions of acceptance in order to understand how the alternative test conditions relate to those specified in Test Methods E119.  
4.4 Users of this guide should be aware that tests conducted using exposure conditions different than those specified in Test Methods E119 do not provide or generate fire resistance ratings suitable for determining compliance with code or regulatory requirements.  
4.4.1 In Test Methods E119, standard test specimens are subjected to specific exposure conditions. Substitution of different exposure conditions can change the measured fire-test-response characteristics of a test specimen. Therefore, the data are valid for only the alternative exposure conditions used.
SCOPE
1.1 This guide covers the conduct of fire-resistance tests using conditions different than those addressed in Test Methods E119. This guide also addresses the reporting of data derived from those tests.  
1.2 This guide does not provide or generate fire-resistance ratings suitable for determining compliance with code or regulatory requirements comparable to those resulting from tests conducted in accordance with Test Methods E119.  
1.3 The values stated in SI units are to be regarded as standard. The values in parentheses are for information only.  
1.4 This guide is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products, or assemblies under actual fire conditions.  
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Dec-2016
Technical Committee
Drafting Committee
Current Stage
Ref Project

Buy Standard

Guide
ASTM E2748-12a(2017) - Standard Guide for Fire-Resistance Experiments
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview
Guide
REDLINE ASTM E2748-12a(2017) - Standard Guide for Fire-Resistance Experiments
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E2748 − 12a (Reapproved 2017) An American National Standard
Standard Guide for
Fire-Resistance Experiments
This standard is issued under the fixed designation E2748; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
INTRODUCTION
This guide provides a means for ensuring comparability of findings among different researchers
conducting fire-resistance experiments employing innovative and creative variations to standard test
methods. This guide is intended to bring uniformity and consistency to tests and reports covering
fire-resistance research that is generally conducted as a variation of Test Methods E119. Its provisions
are voluntary and users are free to pick and choose from the provisions herein provided. The
overriding goal is to make it possible to begin to provide data that ultimately can be used in fire safety
engineering and fire-resistance modeling as those fields evolve. When the purpose of the research is
to study the effect of changing specific individual variables on the outcome of Test Methods E119
fire-resistance tests, sound research practices dictate that only one variable should be changed at a
time.
1. Scope 2. Referenced Documents
1.1 This guide covers the conduct of fire-resistance tests
2.1 ASTM Standards:
using conditions different than those addressed in Test Methods E119 Test Methods for Fire Tests of Building Construction
E119. This guide also addresses the reporting of data derived
and Materials
from those tests. E176 Terminology of Fire Standards
E603 Guide for Room Fire Experiments
1.2 This guide does not provide or generate fire-resistance
E1529 Test Methods for Determining Effects of Large Hy-
ratings suitable for determining compliance with code or
drocarbon Pool Fires on Structural Members and Assem-
regulatory requirements comparable to those resulting from
blies
tests conducted in accordance with Test Methods E119.
2.2 Other Standards:
1.3 The values stated in SI units are to be regarded as
ISO 834-1 Fire Resistance Tests – Elements of Building
standard. The values in parentheses are for information only.
Construction – Part 1: General Requirements
1.4 This guide is used to measure and describe the response
NFPA 251 Standard Methods of Tests of Fire Resistance of
of materials, products, or assemblies to heat and flame under
Building Construction and Materials
controlled conditions, but does not by itself incorporate all
factors required for fire hazard or fire risk assessment of the
3. Terminology
materials, products, or assemblies under actual fire conditions.
3.1 For definitions of terms used in this guide, refer to
1.5 This standard does not purport to address all of the
Terminology E176.
safety concerns, if any, associated with its use. It is the
responsibility of the user of this standard to establish appro-
priate safety and health practices and determine the applica-
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
bility of regulatory limitations prior to use.
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
This guide is under the jurisdiction of ASTM Committee E05 on Fire Standards the ASTM website.
and is the direct responsibility of Subcommittee E05.11 on Fire Resistance. Available from International Organization for Standardization, P.O. Box 56,
Current edition approved Jan. 1, 2017. Published February 2017. Originally CH-1211, Geneva 20, Switzerland.
approved in 2010 as E2748–10. Last previous edition approved in 2012 as Available from National Fire Protection Association (NFPA), 1 Batterymarch
E2748–12a. DOI: 10.1520/E2748-12AR17. Park, Quincy, MA 02169-7471, http://www.nfpa.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E2748 − 12a (2017)
4. Significance and Use 7. Alternative Pressure Differentials
4.1 The methods and procedures set forth in this guide relate 7.1 The provisions in this section are applicable to the use of
to the conduct and reporting of fire-resistance tests obtained specific furnace pressure differentials.
NOTE 2—There are a number of recognized or published furnace
from particular fire-resistance tested specimens tested using
pressure differentials in use in fire test standards around the world.
conditions different than those addressed by Test Methods
E119. 7.2 When a recognized or published furnace pressure dif-
ferential is used, the reference in which the pressure differential
4.2 Data derived from fire tests conducted and reported
is described should be cited and the pressures should be
under this guide are useful for general fire research and as
reported.
potential input data for use in fire models.
7.3 When other pressure differentials are used for explor-
4.3 It is necessary that users of this guide have knowledge
atory research or to replicate actual fire conditions, or for any
and understanding of the provisions of Test Methods E119,
other reason, they should be described and should be reported.
including those pertaining to conditions of acceptance in order
to understand how the alternative test conditions relate to those 7.4 Furnace pressure differentials should be measured as
specified in Test Methods E119. described in NFPA 251.
4.4 Users of this guide should be aware that tests conducted
8. Alternative Test Specimens
using exposure conditions different than those specified in Test
Methods E119 do not provide or generate fire resistance ratings 8.1 The provisions in this section are applicable to the use of
suitable for determining compliance with code or regulatory alternative test specimens that are different from the test
requirements. specimens specified in Test Methods E119.
4.4.1 In Test Methods E119, standard test specimens are
8.2 Test specimen dimensions, that is, height and width for
subjected to specific exposure conditions. Substitution of
walls, length and width for horizontal specimens, or lengths for
different exposure conditions can change the measured fire-
columns or beams, should be reported and the method used to
test-response characteristics of a test specimen. Therefore, the
modify the furnace opening to accommodate the specimen size
data are valid for only the alternative exposure conditions used.
should be reported.
8.3 When test specimens having exposed and unexposed
5. General Principles
surfaces that are not parallel to each other or that are not flat
5.1 Except as specifically modified herein, fire-resistance
(planar) are tested, their maximum and minimum thicknesses,
tests should be conducted using the test furnaces, exposure
and radii, if curved, should be reported.
conditions, test specimens, instrumentation, and acceptance
8.4 When test specimens having one or more designed
criteria set forth in Test Methods E119.
protrusions or indentations (pilasters, alcoves, etc.) either on
5.2 Although it is possible to vary many variables at one
the fire side, the unexposed side, or both, are tested, the size,
time, and it may be desirable to do so when evaluating the
shape, location, and dimensions of each protrusion or indenta-
response of a specimen to specific design fire conditions, it is
tion should be described and reported.
usually desirable to vary only one parameter at a time when
8.5 When test specimens exceeding the depth of the speci-
comparing results from two or more tests or when evaluating
men mounting frame are tested, the method(s) of protecting the
the effect on fire resistance of changing a specific variable.
portion of the test specimen extending beyond the frame should
5.3 Limitations—The test data is valid for only the specimen
be described and reported.
and parameters used in the test.
9. Alternative Instrumentation – Furnace Environment
6. Alternative Time-Temperature Curves
9.1 When alternative instrumentation is used in addition to
6.1 The provisions in this section are applicable to the use of
the standard instrumentation specified in Test Methods E119,
alternative time-temperature curves that are different from the
the alternative instrumentation should be spaced and mounted
time-temperature curve specified in Test Methods E119.
so as to not interfere with the standard instrumentation.
6.1.1 When the time-temperature curve specified in Test
Methods E119 is used, it should be so stated in the report. 9.2 Furnace Temperature Measurement:
NOTE 1—There are a number of recognized time-temperature curves in
9.2.1 When the furnace control temperature measurement
use in fire-resistance test standards around the world.
method (that is, shielded thermocouples) specified in Test
6.2 When a recognized or published time-temperature curve Methods E119 is used it should be so stated in the report.
is used, the reference in which the curve is described should be 9.2.2 When Directional Flame Thermometers or plate ther-
cited and the time-temperature curve should be reported. mometers are used they should be spaced as described in
9.2.2.1 through 9.2.2.2.
6.3 Fire safety engineering and computer modeling are
methods whereby non-standard time-temperature curves can be
NOTE 3—Directional Flame Thermometers are described in Test Meth-
ods E1529. Specifications for plate thermometers are provided in ISO
derived to represent specific design conditions.
834-1.
6.3.1 When these design fires are used as the basis of a
time-temperature curve, a table or equation representing the 9.2.2.1 There should be nine plate thermometers equally
curve should be reported. distributed across the test specimen surface.
E2748 − 12a (2017)
9.2.2.2 Directional Flame Thermometers and Plate ther- 10. Alternative Instrumentation – Specimen
mometers should be located 4 6 0.2 in. (100 6 5 mm) from the
10.1 When alternative instrumentation is used in addition to
exposed surface of the test specimen at the beginning of the
the standard instrumentation specified in Test Methods E119,
test.
the alternative instrumentation should be spaced and mounted
9.2.3 Other methods, sensors, or measurement devices for
so as to not interfere with the standard instrumentation.
monitoring the furnace temperature should be described and
10.2 Unexposed Surface Temperature Measurement for
reported.
Walls and Floor/Ceilings:
9.2.4 Any special mounting methods used for plate ther-
10.2.1 When the unexposed surface temperature measure-
mometers or other temperature measuring devices should be
ment methods specified in Test Methods E119 are used, it
described and reported.
should be so stated in the report.
9.2.5 The locations of furnace temperature measuring de-
10.2.2 Other methods, sensors, or measurement devices
vices should be reported.
used for monitoring the unexposed surface temperature should
9.3 Heat Flux Measurement:
be described and reported.
10.2.2.1 Any special mounting methods should be described
9.3.1 When heat flux measurements are taken in addition to
and reported.
furnace temperature control measurements, the methods,
instrumentation, and heat flux profile should be described and 10.2.3 The locations of temperature measuring devices
should be reported.
reported.
9.3.1.1 Any special mounting methods should be described
10.3 Heat Flux Off the Unexposed Surface of Walls and
and reported.
Floor/Ceilings:
9.3.2 The locations of heat flux measurement devices
10.3.1 When total heat flux off the unexposed surface is
should be reported.
measured, it should be measured as described in 10.3.1.1
through 10.3.1.3.
9.4 Pressure Measurement:
10.3.1.1 Total heat flux coming off the unexposed surface
9.4.1 When furnace pressures are measured or controlled,
should be measured using a Schmidt-Boetler-type water-
the methods, instrumentation, and pressure differentials should
cooled total heat flux gauge.
be reported.
10.3.1.2 The heat flux gauge should be placed near the
9.4.2 Furnace pressure should be measured using the tube
center of the unexposed surface of the specimen and as close to
sensor described in ISO 834-1 and NFPA 251.
the specimen surface as practical.
9.4.2.1 In a vertical furnace, pressure should be measured at
10.3.1.3 When the test specimen contains a transparent
a minimum of two locations. The measuring locations should
element, an additional heat flux gauge should be placed near
be separated by a minimum of ⁄3 the test specimen height.
the center of the transparent element and as close as practical
9.4.2.2 In a horizontal furnace, pressure should be measured
to the surface of the transparent element.
at a single location a nominal 4 6 0.2 in. (100 6 5 mm) below
10.4 Temperature Profile Through Test Specimens:
the exposed surface of the test specimen at the beginning of the
10.4.1 When the temperature profile of test specimens is
test.
monitored, it should be monitored as described in 10.4.1.1
9.4.3 Any special mounting methods should be described
through 10.4.1.4.
and reported.
10.4.1.1 Temperatures should be measured through the
9.4.4 The locations of pressure measurement devices should
thickness of the test specimen at not less than two locations
be reported.
representative of each major heat-transfer path within the
9.5 Furnace Oxygen Concentration:
specimen.
9.5.1 When furnace oxygen concentration is being 10.4.1.2 The surface temperature on the exposed side
monitored, it should be measured in the furnace stack.
should be measured with a 24-gauge, Type K bare bead
thermocouple placed in contact with the exposed surface of the
9.5.1.1 Oxygen concentration should be measured using a
test specimen.
paramagnetic-type oxygen analyzer.
10.4.1.3 The surface temperature on the unexposed side
9.5.1.2 The sampling probe should be similar to the sam-
should be measured using an optical pyrometer suitable for
pling probe used in duct measurements of hood calorimeters
measuring temperatures on the unexposed side.
described in Guide .
10.4.1.4 Internal temperatures should be measured using
9.5.1.3 Gas samples should be continuously drawn out of
Inconel-sheathed Type K thermocouples with a sheath diam-
the stack through a sampling line.
eter of 0.04 in. (1.0 mm).
9.5.2 The oxygen concentration profile should be reported.
10.5 Gas Temperature Measurement:
9.6 Other Measurement Instrumentation:
10.5.1 When gas temperatures are measured they should be
9.6.1 Additional instrumentation such as load cells, addi-
measured as described in 10.5.1.1 through 10.5.1.3.
tional thermocouples, moisture c
...


This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: E2748 − 12a E2748 − 12a (Reapproved 2017) An American National Standard
Standard Guide for
Fire-Resistance Experiments
This standard is issued under the fixed designation E2748; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
INTRODUCTION
This guide provides a means for ensuring comparability of findings among different researchers
conducting fire-resistance experiments employing innovative and creative variations to standard test
methods. This guide is intended to bring uniformity and consistency to tests and reports covering
fire-resistance research that is generally conducted as a variation of Test Methods E119. Its provisions
are voluntary and users are free to pick and choose from the provisions herein provided. The
overriding goal is to make it possible to begin to provide data that ultimately can be used in fire safety
engineering and fire-resistance modeling as those fields evolve. When the purpose of the research is
to study the effect of changing specific individual variables on the outcome of Test Methods E119
fire-resistance tests, sound research practices dictate that only one variable should be changed at a
time.
1. Scope
1.1 This guide covers the conduct of fire-resistance tests using conditions different than those addressed in Test Methods E119.
This guide also addresses the reporting of data derived from those tests.
1.2 This guide does not provide or generate fire-resistance ratings suitable for determining compliance with code or regulatory
requirements comparable to those resulting from tests conducted in accordance with Test Methods E119.
1.3 The values stated in SI units are to be regarded as standard. The values in parentheses are for information only.
1.4 This guide is used to measure and describe the response of materials, products, or assemblies to heat and flame under
controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials,
products, or assemblies under actual fire conditions.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2.1 ASTM Standards:
E119 Test Methods for Fire Tests of Building Construction and Materials
E176 Terminology of Fire Standards
E603 Guide for Room Fire Experiments
E1529 Test Methods for Determining Effects of Large Hydrocarbon Pool Fires on Structural Members and Assemblies
2.2 Other Standards:
ISO 834-1 Fire Resistance Tests – Elements of Building Construction – Part 1: General Requirements
NFPA 251 Standard Methods of Tests of Fire Resistance of Building Construction and Materials
This guide is under the jurisdiction of ASTM Committee E05 on Fire Standards and is the direct responsibility of Subcommittee E05.11 on Fire Resistance.
Current edition approved Nov. 1, 2012Jan. 1, 2017. Published November 2012February 2017. Originally approved in 2010 as E2748–10. Last previous edition approved
in 2012 as E2748–12.–12a. DOI: 10.1520/E2748-12A.10.1520/E2748-12AR17.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Available from International Organization for Standardization, P.O. Box 56, CH-1211, Geneva 20, Switzerland.
Available from National Fire Protection Association (NFPA), 1 Batterymarch Park, Quincy, MA 02169-7471, http://www.nfpa.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E2748 − 12a (2017)
3. Terminology
3.1 For definitions of terms used in this guide, refer to Terminology E176.
4. Significance and Use
4.1 The methods and procedures set forth in this guide relate to the conduct and reporting of fire-resistance tests obtained from
particular fire-resistance tested specimens tested using conditions different than those addressed by Test Methods E119.
4.2 Data derived from fire tests conducted and reported under this guide are useful for general fire research and as potential input
data for use in fire models.
4.3 It is necessary that users of this guide have knowledge and understanding of the provisions of Test Methods E119, including
those pertaining to conditions of acceptance in order to understand how the alternative test conditions relate to those specified in
Test Methods E119.
4.4 Users of this guide should be aware that tests conducted using exposure conditions different than those specified in Test
Methods E119 do not provide or generate fire resistance ratings suitable for determining compliance with code or regulatory
requirements.
4.4.1 In Test Methods E119, standard test specimens are subjected to specific exposure conditions. Substitution of different
exposure conditions can change the measured fire-test-response characteristics of a test specimen. Therefore, the data are valid for
only the alternative exposure conditions used.
5. General Principles
5.1 Except as specifically modified herein, fire-resistance tests should be conducted using the test furnaces, exposure conditions,
test specimens, instrumentation, and acceptance criteria set forth in Test Methods E119.
5.2 Although it is possible to vary many variables at one time, and it may be desirable to do so when evaluating the response
of a specimen to specific design fire conditions, it is usually desirable to vary only one parameter at a time when comparing results
from two or more tests or when evaluating the effect on fire resistance of changing a specific variable.
5.3 Limitations—The test data is valid for only the specimen and parameters used in the test.
6. Alternative Time-Temperature Curves
6.1 The provisions in this section are applicable to the use of alternative time-temperature curves that are different from the
time-temperature curve specified in Test Methods E119.
6.1.1 When the time-temperature curve specified in Test Methods E119 is used, it should be so stated in the report.
NOTE 1—There are a number of recognized time-temperature curves in use in fire-resistance test standards around the world.
6.2 When a recognized or published time-temperature curve is used, the reference in which the curve is described should be
cited and the time-temperature curve should be reported.
6.3 Fire safety engineering and computer modeling are methods whereby non-standard time-temperature curves can be derived
to represent specific design conditions.
6.3.1 When these design fires are used as the basis of a time-temperature curve, a table or equation representing the curve should
be reported.
7. Alternative Pressure Differentials
7.1 The provisions in this section are applicable to the use of specific furnace pressure differentials.
NOTE 2—There are a number of recognized or published furnace pressure differentials in use in fire test standards around the world.
7.2 When a recognized or published furnace pressure differential is used, the reference in which the pressure differential is
described should be cited and the pressures should be reported.
7.3 When other pressure differentials are used for exploratory research or to replicate actual fire conditions, or for any other
reason, they should be described and should be reported.
7.4 Furnace pressure differentials should be measured as described in NFPA 251.
8. Alternative Test Specimens
8.1 The provisions in this section are applicable to the use of alternative test specimens that are different from the test specimens
specified in Test Methods E119.
8.2 Test specimen dimensions, that is, height and width for walls, length and width for horizontal specimens, or lengths for
columns or beams, should be reported and the method used to modify the furnace opening to accommodate the specimen size
should be reported.
8.3 When test specimens having exposed and unexposed surfaces that are not parallel to each other or that are not flat (planar)
are tested, their maximum and minimum thicknesses, and radii, if curved, should be reported.
E2748 − 12a (2017)
8.4 When test specimens having one or more designed protrusions or indentations (pilasters, alcoves, etc.) either on the fire side,
the unexposed side, or both, are tested, the size, shape, location, and dimensions of each protrusion or indentation should be
described and reported.
8.5 When test specimens exceeding the depth of the specimen mounting frame are tested, the method(s) of protecting the portion
of the test specimen extending beyond the frame should be described and reported.
9. Alternative Instrumentation – Furnace Environment
9.1 When alternative instrumentation is used in addition to the standard instrumentation specified in Test Methods E119, the
alternative instrumentation should be spaced and mounted so as to not interfere with the standard instrumentation.
9.2 Furnace Temperature Measurement:
9.2.1 When the furnace control temperature measurement method (that is, shielded thermocouples) specified in Test Methods
E119 is used it should be so stated in the report.
9.2.2 When Directional Flame Thermometers or plate thermometers are used they should be spaced as described in 9.2.2.1
through 9.2.2.2.
NOTE 3—Directional Flame Thermometers are described in Test Methods E1529. Specifications for plate thermometers are provided in ISO 834-1.
9.2.2.1 There should be nine plate thermometers equally distributed across the test specimen surface.
9.2.2.2 Directional Flame Thermometers and Plate thermometers should be located 4 6 0.2 in. (100 6 5 mm) from the exposed
surface of the test specimen at the beginning of the test.
9.2.3 Other methods, sensors, or measurement devices for monitoring the furnace temperature should be described and reported.
9.2.4 Any special mounting methods used for plate thermometers or other temperature measuring devices should be described
and reported.
9.2.5 The locations of furnace temperature measuring devices should be reported.
9.3 Heat Flux Measurement:
9.3.1 When heat flux measurements are taken in addition to furnace temperature control measurements, the methods,
instrumentation, and heat flux profile should be described and reported.
9.3.1.1 Any special mounting methods should be described and reported.
9.3.2 The locations of heat flux measurement devices should be reported.
9.4 Pressure Measurement:
9.4.1 When furnace pressures are measured or controlled, the methods, instrumentation, and pressure differentials should be
reported.
9.4.2 Furnace pressure should be measured using the tube sensor described in ISO 834-1 and NFPA 251.
9.4.2.1 In a vertical furnace, pressure should be measured at a minimum of two locations. The measuring locations should be
separated by a minimum of ⁄3 the test specimen height.
9.4.2.2 In a horizontal furnace, pressure should be measured at a single location a nominal 4 6 0.2 in. (100 6 5 mm) below
the exposed surface of the test specimen at the beginning of the test.
9.4.3 Any special mounting methods should be described and reported.
9.4.4 The locations of pressure measurement devices should be reported.
9.5 Furnace Oxygen Concentration:
9.5.1 When furnace oxygen concentration is being monitored, it should be measured in the furnace stack.
9.5.1.1 Oxygen concentration should be measured using a paramagnetic-type oxygen analyzer.
9.5.1.2 The sampling probe should be similar to the sampling probe used in duct measurements of hood calorimeters described
in Guide .
9.5.1.3 Gas samples should be continuously drawn out of the stack through a sampling line.
9.5.2 The oxygen concentration profile should be reported.
9.6 Other Measurement Instrumentation:
9.6.1 Additional instrumentation such as load cells, additional thermocouples, moisture content measurement devices, motion
sensors, or other instrumentation not described or specified in Test Methods E119 should be fully described and reported.
10. Alternative Instrumentation – Specimen
10.1 When alternative instrumentation is used in addition to the standard instrumentation specified in Test Methods E119, the
alternative instrumentation should be spaced and mounted so as to not interfere with the standard instrumentation.
10.2 Unexposed Surface Temperature Measurement for Walls and Floor/Ceilings:
10.2.1 When the unexposed surface temperature measurement methods specified in Test Methods E119 are used, it should be
so stated in the report.
E2748 − 12a (2017)
10.2.2 Other methods, sensors, or measurement devices used for monitoring the unexposed surface temperature should be
described and reported.
10.2.2.1 Any special mounting methods should be described and reported.
10.2.3 The locations of temperature measuring devices should be reported.
10.3 Heat Flux Off the Unexposed Surface of Walls and Floor/Ceilings:
10.3.1 When total heat flux off the unexposed surface is measured, it should be measured as described in 10.3.1.1 through
10.3.1.3.
10.3.1.1 Total heat flux coming off the unexposed surface should be measured using a Schmidt-Boetler-type water-cooled total
heat flux gauge.
10.3.1.2 The heat flux gauge should be placed near the center of the unexposed surface of the specimen and as close to the
specimen surface as practical.
10.3.1.3 When the test specimen contains a transparent element, an additional heat flux gauge should be placed near the center
of the transparent element and as close as practical to the surface of the transparent element.
10.4 Temperature Profile Through Test Specimens:
10.4.1 When the temperature profile of test specimens is monitored, it should be monitored as described in 10.4.1.1 through
10.4.1.4.
10.4.1.1 Temperatures should be measured through the thickness of the test specimen at not less than two locations
representative of each major heat-transfer path within the specimen.
10.4.1.2 The surface temperature on the exposed side should be measured with a 24-gauge, Type K bare bead thermocouple
placed in contact with the expos
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.