ASTM F1040-87(2001)
(Specification)Standard Specification for Filter Units, Air Conditioning Viscous-Impingement and Dry Types, Replaceable
Standard Specification for Filter Units, Air Conditioning Viscous-Impingement and Dry Types, Replaceable
SCOPE
1.1 This specification covers throw-away, flat panel-type filter units for use in air conditioning, heating, and ventilating systems. This specification also includes panel-type filters with pleated media.
1.2 The values stated in inch-pound units are to be regarded as the standard.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: F 1040 – 87 (Reapproved 2001)
Standard Specification for
Filter Units, Air Conditioning: Viscous-Impingement and Dry
1
Types, Replaceable
This standard is issued under the fixed designation F1040; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1. Scope 4.1.2 Type 2—Permanent frames with replaceable media.
4.2 The filters are furnished in three grades as follows:
1.1 This specification covers throw-away, flat panel-type
4.2.1 Grade A—Standard dust-holding capacity,
filter units for use in air conditioning, heating, and ventilating
4.2.2 Grade B—High dust-holding capacity, and
systems.Thisspecificationalsoincludespanel-typefilterswith
4.2.3 Grade C—High arrestance.
pleated media.
1.2 The values stated in inch-pound units are to be regarded
5. Ordering Information
as the standard.
5.1 Contracts or orders for the units under this specification
2. Referenced Documents shall include the following information:
2
5.1.1 Quantity,
2.1 ASTM Standards:
5.1.2 MaterialformediaframeforType2filter,(seesection
D3951 Practice for Commercial Packaging
6.4.4),
2.2 ASHRAE Standard:
5.1.3 Size, (See 7.1),
52 Method of Testing Air-Cleaning Devices Used in Gen-
3
5.1.4 Certification of the filter units by the producer or
eral Ventilation for Removing Particulate Matter
supplier, if required, (see Section 10).
2.3 Federal Standard:
Fed. Std. No. 123 Military Standard for Marking for Ship-
6. Materials and Manufacture
4
ment and Storage
6.1 Filters shall be the manufacturer’s standard commercial
2.4 Military Standard:
4 product with any added features needed to comply with the
MIL-STD-129 Marking for Shipment and Storage
specified requirements.
2.5 UL Standard:
5
UL900 Test Performance of Air Filter Units
7. Physical Properties
3. Descriptions of Term Specific to This Standard 7.1 The filter units shall be the flat panel type, with or
without pleated media. They shall be designed and fabricated
3.1 net face area—the net upstream area of the medium
for disposal when, because of accumulated dust loading, the
exposed to air flow measured in the plane or planes of the
dust-load limit is reached. In Type 2 filters, the media frames
media, excluding sealing flanges, framing supports, etc.
shall be permanent and the media padonly shall be disposable.
4. Classification The filter media shall be dry or adhesive-coated in accordance
with the manufacturer’s recommendations.
4.1 The filters are furnished in two types as follows:
7.2 Filter Construction—Filters shall be constructed with
4.1.1 Type 1—Throw-away frames and media, and
1
90° corners. Frame edges shall be parallel to within ⁄16 in.
Mediapadreinforcementintheformofgrilles,retaininggrids,
1
This specification is under the jurisdiction of ASTM Committee D22 on Air
fabric netting, or the equivalent shall be installed on both faces
Quality and is the direct responsibility of Subcommittee D22.05 on Indoor Air.
of the filter in accordance with the manufacturer’s recommen-
Current edition approved Jan. 30, 1987. Published March 1987.
2 dations. The media shall be attached to the frame of Type 1
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
filters, and supported in the frame of Type 2 filters, in such a
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
manner that the media pad will not slump or otherwise be
the ASTM website.
permanently displaced under the conditions of maximum air
3
Available from ASHRAE Inc., 1791 Tullie Circle, N.E., Atlanta, GA 30329.
4 velocity (350 ft/min (1.78 m/s)) and filter resistance specified
Available from Naval Publications and Forms Center, 5801 Tabor Ave.,
Philadelphia, PA 19120. herein.
5
Available from Underwriters Laboratories, 333 Pfingster Road, Northbrook, IL
60062.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
F 1040 – 87 (2001)
7.2.1 Filter Media—Filter media shall be suitable for the 8.3.4 Dissimilar Metals—Joints between dissimilar metals,
intended use and shall be composed of natural, synthetic, or including bolts, nuts, rivets, and other fastenings and fittings
inorganic fibers, or any combination of such fibers. The media shall be protected against galvanic corrosion by the proper
shall be nontoxic. The media shall be suitable for continuous selection of materials, plating isolation, insulation, area rela-
use at temper
...