Standard Specification for Socket-Type Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 40

SCOPE
1.1 This specification covers chlorinated poly(vinyl chloride) (CPVC) Schedule 40 socket-type pipe fittings. Included are requirements for materials, workmanship, dimensions, and burst pressure.
Note 1—The CPVC fittings covered by this standard were covered previously in Specification D 2466.
1.2 The products covered by this specification are intended for use with the distribution of pressurized liquids only, which are chemically compatible with the piping materials. Due to inherent hazards associated with testing components and systems with compressed air or other compressed gases some manufacturers do not allow pneumatic testing of their products. Consult with specific product/component manufacturers for their specific testing procedures prior to pneumatic testing.
Note 2—Pressurized (compressed) air or other compressed gases contain large amounts of stored energy which present serious saftey hazards should a system fail for any reason.
1.3 The text of this specification references notes, footnotes, and appendixes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the specification.
1.4 The values stated in inch-pound units are to be regarded as the standard. The values in parentheses are given for information only.
1.5 The following safety hazards caveat pertains only to the test method portion, Section 8, of this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
09-Sep-2002
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM F438-02 - Standard Specification for Socket-Type Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 40
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
An American National Standard
Designation: F 438 – 02
Standard Specification for
Socket-Type Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic
1
Pipe Fittings, Schedule 40
This standard is issued under the fixed designation F 438; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1. Scope 2. Referenced Documents
1.1 This specification covers chlorinated poly(vinyl chlo- 2.1 ASTM Standards:
2
ride) (CPVC) Schedule 40 socket-type pipe fittings. Included D 618 Practice for Conditioning Plastics for Testing
are requirements for materials, workmanship, dimensions, and D 1599 Test Method for Short-Time Hydraulic Failure Pres-
3
burst pressure. sure of Plastic Pipe, Tubing, and Fittings
D 1600 Terminology for Abbreviated Terms Relating to
NOTE 1—The CPVC fittings covered by this standard were covered
2
Plastics
previously in Specification D 2466.
D 1784 Specification for Rigid Poly(Vinyl Chloride) (PVC)
1.2 The products covered by this specification are intended
Compounds and Chlorinated Poly(Vinyl Chloride)
for use with the distribution of pressurized liquids only, which
2
(CPVC) Compounds
are chemically compatible with the piping materials. Due to
D 2122 Test Method for Determining Dimensions of Ther-
inherent hazards associated with testing components and sys-
3
moplastic Pipe and Fittings
tems with compressed air or other compressed gases some
3
D 2749 Symbols for Dimensions of Plastic Pipe Fittings
manufacturers do not allow pneumatic testing of their products.
3
F 412 Terminology Relating to Plastic Piping Systems
Consult with specific product/component manufacturers for
F 1498 Specification for Taper Pipe Threads 60° for Ther-
their specific testing procedures prior to pneumatic testing.
3
moplastic Pipe and Fittings
2.2 Federal Standard:
NOTE 2—Pressurized (compressed) air or other compressed gases
4
contain large amounts of stored energy which present serious saftey
Fed. Std. No. 123 Marking for Shipment (Civil Agencies)
hazards should a system fail for any reason.
2.3 Military Standard:
5
MIL-STD-129 Marking for Shipment and Storage
1.3 The text of this specification references notes, footnotes,
2.4 NSF Standard:
and appendixes which provide explanatory material. These
Standard No. 14 for Plastic Piping Components and Related
notes and footnotes (excluding those in tables and figures) shall
5
Materials
not be considered as requirements of the specification.
1.4 The values stated in inch-pound units are to be regarded
3. Terminology
as the standard. The values in parentheses are given for
3.1 Definitions:
information only.
3.1.1 Definitions are in accordance with Terminology F 412
1.5 The following safety hazards caveat pertains only to the
and abbreviations are in accordance with Terminology D 1600,
test method portion, Section 8, of this specification: This
unless otherwise indicated. The abbreviation for chlorinated
standard does not purport to address all of the safety concerns,
poly(vinyl chloride) is CPVC.
if any, associated with its use. It is the responsibility of the user
of this standard to establish appropriate safety and health
practices and determine the applicability of regulatory limita-
tions prior to use.
2
Annual Book of ASTM Standards, Vol 08.01.
3
Annual Book of ASTM Standards, Vol 08.04.
1 4
This specification is under the jurisdiction of ASTM Committee F17 on Plastic Available from Standardization Documents Order Desk, Bldg. 4 Section D, 700
Piping Systems and is the direct responsibility of Subcommittee F17.10 on Fittings. Robbins Ave., Philadelphia, PA 19111-5094, Attn: NPODS.
5
Current edition approved Sept. 10, 2002. Published November 2002. Originally Available from the National Sanitation Foundation, P.O. Box 1468, Ann Arbor,
published as part of D 2466 – 74. Last previous edition F 438 – 01. MI 48106.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
F 438–02
4. Classification 6.3.1 The minimum burst strength of the fittings shall be not
less than that calculated for the size and wall thickness of the
4.1 General—This specification covers Schedule 40 CPVC
pipe with which it is to be used, when calculated from the
pipe fittings, socket-type, intended for use with Iron Pipe Size
following equation:
(IPS) outside-diamet
...