Standard Specification for High Voltage Detectors—Part 1 Capacitive Type to be Used for Voltages Exceeding 600 Volts AC

ABSTRACT
This specification covers portable, live-line tool-supported, direct-contact type capacitive voltage detectors to be used on electrical systems both indoors and outdoors for ac voltages. This specification establishes requirements for the design and testing of high voltage detectors, used in the electrical power industry, to determine the presence or absence of nominal operating voltage. The following tests shall be performed: voltage; low temperature impact; drop/impact; humidity; wet test; battery life test; durability of labeling; vibration resistance; continuous operation rating; response time; testing the self-test function; acceptable audible indication; acceptable visual indication; visual inspection; method to measure threshold voltage; interference voltage testing; leakage current testing; dielectric testing for detector housing; and wet testing.
SIGNIFICANCE AND USE
4.1 This specification establishes requirements for the design and testing of high voltage detectors, used in the electrical power industry, to determine the presence or absence of nominal operating voltage or the measured voltage.
SCOPE
1.1 This specification covers portable, live-line tool-supported, direct-contact type capacitive voltage detectors to be used on electrical systems both indoors and outdoors for ac voltages from 600 V to 800 kV with frequency of 50/60 Hz. The function of the voltage detector is limited to the detection of the presence or absence of nominal operating voltage.  
1.1.1 Two types of voltage detectors are provided and are designated as Type I, audible/visual and Type II, numeric, with or without audible.  
1.1.2 Two styles of voltage detectors, differing in wet conditions characteristics, are provided and are designated as Style A, indoor use and Style B indoor/outdoor use.  
1.2 The use and maintenance of these high voltage detectors and any necessary insulated tool handles are beyond the scope of this specification.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
Note 1: Except where specified, all voltage defined in this specification refer to phase-to-phase voltage in a three-phase system. Voltage detectors covered by this specification may be used in other than three-phase systems, but the applicable phase-to-phase or phase-to-ground (earth) voltages shall be used to determine the operating voltage.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Published
Publication Date
14-Jun-2019
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM F1796-19 - Standard Specification for High Voltage Detectors—Part 1 Capacitive Type to be Used for Voltages Exceeding 600 Volts AC
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview
Technical specification
REDLINE ASTM F1796-19 - Standard Specification for High Voltage Detectors—Part 1 Capacitive Type to be Used for Voltages Exceeding 600 Volts AC
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation:F1796 −19
Standard Specification for
High Voltage Detectors—Part 1 Capacitive Type to be Used
1
for Voltages Exceeding 600 Volts AC
This standard is issued under the fixed designation F1796; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 2. Referenced Documents
2
2.1 ASTM Standards:
1.1 This specification covers portable, live-line tool-
F819Terminology Relating to Electrical Protective Equip-
supported, direct-contact type capacitive voltage detectors to
ment for Workers
be used on electrical systems both indoors and outdoors for ac
3
2.2 ANSI Standard:
voltages from 600 V to 800 kV with frequency of 50/60 Hz.
ANSIC84.1Voltage Ratings for Electric Power Systems
The function of the voltage detector is limited to the detection
and Equipment
of the presence or absence of nominal operating voltage.
1.1.1 Two types of voltage detectors are provided and are
3. Terminology
designatedasTypeI,audible/visualandTypeII,numeric,with
3.1 Definitions:
or without audible.
3.1.1 capacitive voltage detector—a device that relies on
1.1.2 Two styles of voltage detectors, differing in wet
current passing through stray capacitance to ground.
conditions characteristics, are provided and are designated as
3.1.2 clear indication—a specific condition that detects and
Style A, indoor use and Style B indoor/outdoor use.
indicates the voltage state at the contact electrode.
1.2 Theuseandmaintenanceofthesehighvoltagedetectors
3.1.3 clear perception—the ability by the user to determine
and any necessary insulated tool handles are beyond the scope
that the voltage detector is in its operating position.
of this specification.
3.1.4 contact electrode—the bare conductive part of the
conductiveelementthatestablishestheelectricalconnectionto
1.3 This standard does not purport to address all of the
the component to be tested.
safety concerns, if any, associated with its use. It is the
responsibility of the user of this standard to establish appro-
3.1.5 indicator—part of the voltage detector that indicates
priate safety, health, and environmental practices and deter- thepresenceorabsenceofthenominaloperatingvoltageorthe
mine the applicability of regulatory limitations prior to use. measured voltage at the contact electrode.
3.1.6 indoor style—a detector designed for use in dry
NOTE 1—Except where specified, all voltage defined in this specifica-
conditions, normally indoors.
tion refer to phase-to-phase voltage in a three-phase system. Voltage
detectors covered by this specification may be used in other than 3.1.7 interference field—electrical field affecting the indica-
three-phasesystems,buttheapplicablephase-to-phaseorphase-to-ground
tion.
(earth) voltages shall be used to determine the operating voltage.
3.1.8 interference voltage—voltages other than the signal
1.4 This international standard was developed in accor-
voltage capable of making the device operate.
dance with internationally recognized principles on standard-
3.1.9 limit marking—distinctivelocationormarktoindicate
ization established in the Decision on Principles for the
to the user the physical limit to which the detector may be
Development of International Standards, Guides and Recom-
inserted between live components or may touch them.
mendations issued by the World Trade Organization Technical
3.1.10 nominal operating voltage—a nominal value consis-
Barriers to Trade (TBT) Committee.
tent with the latest revision of ANSI C84.1.
1 2
This specification is under the jurisdiction of ASTM Committee F18 on For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Electrical Protective Equipment for Workers and is the direct responsibility of contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Subcommittee F18.35 on Tools & Equipment. Standards volume information, refer to the standard’s Document Summary page on
Current edition approved June 15, 2019. Published July 2019. Originally the ASTM website.
3
approvedin1997.Lastpreviouseditionapprovedin2014asF1796-09(2014).DOI: Available from American National Standards Institute, 11 West 42nd St., 13th
10.1520/F1796-19. Floor, New York, NY 10036.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
F1796−19
3.1.11 outdoor style—a detector designed for use either 6.1.2 Style,
indoors or outdoors. 6.1.3 Voltage
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: F1796 − 09 (Reapproved 2014) F1796 − 19
Standard Specification for
High Voltage Detectors—Part 1 Capacitive Type to be Used
1
for Voltages Exceeding 600 Volts AC
This standard is issued under the fixed designation F1796; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This specification covers portable, live-line tool-supported, direct-contact type capacitive voltage detectors to be used on
electrical systems both indoors and outdoors for ac voltages from 600 V to 800 kV with frequency of 6050/60 Hz. The function
of the voltage detector is limited to the detection of the presence or absence of nominal operating voltage.
1.1.1 Two types of voltage detectors are provided and are designated as Type I, audible/visual and Type II, numeric, with or
without audible.
1.1.2 Two styles of voltage detectors, differing in wet conditions characteristics, are provided and are designated as Style A,
indoor use and Style B indoor/outdoor use.
1.2 The use and maintenance of these high voltage detectors and any necessary insulated tool handles are beyond the scope of
this specification.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety safety, health, and healthenvironmental practices and determine the
applicability of regulatory limitations prior to use.
NOTE 1—Except where specified, all voltage defined in this specification refer to phase-to-phase voltage in a three-phase system. Voltage detectors
covered by this specification may be used in other than three-phase systems, but the applicable phase-to-phase or phase-to-ground (earth) voltages shall
be used to determine the operating voltage.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2
2.1 ASTM Standards:
F819 Terminology Relating to Electrical Protective Equipment for Workers
3
2.2 ANSI Standard:
ANSI C84.1 Voltage Ratings for Electric Power Systems and Equipment
3. Terminology
3.1 Definitions:
3.1.1 capacitive voltage detector—a device that relies on current passing through stray capacitance to ground.
3.1.2 clear indication—a specific condition that detects and indicates the voltage state at the contact electrode.
3.1.3 clear perception—the ability by the user to determine that the voltage detector is in its operating position.
3.1.4 contact electrode—the bare conductive part of the conductive element that establishes the electrical connection to the
component to be tested.
1
This specification is under the jurisdiction of ASTM Committee F18 on Electrical Protective Equipment for Workers and is the direct responsibility of Subcommittee
F18.35 on Tools & Equipment.
Current edition approved Oct. 1, 2014June 15, 2019. Published November 2014July 2019. Originally approved in 1997. Last previous edition approved in 20092014 as
F1796-09. -09 (2014). DOI: 10.1520/F1796-09R14.10.1520/F1796-19.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from American National Standards Institute, 11 West 42nd St., 13th Floor, New York, NY 10036.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
F1796 − 19
3.1.5 indicator—part of the voltage detector that indicates the presence or absence of the nominal operating voltage or the
measured voltage at the contact electrode.
3.1.6 indoor style—a detector designed for use in dry conditions, normally indoors.
3.1.7 interference field—electrical field affecting the indication.
3.1.8 interference voltage—voltages other than the signal voltage capable of making the device operate.
3.1.9 limit marking—distinctive location or mark to indicate to the user the physical limit to which the det
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.