ASTM B786/B786M-08(2018)
(Specification)Standard Specification for 19 Wire Combination Unilay-Stranded Aluminum Conductors for Subsequent Insulation
Standard Specification for 19 Wire Combination Unilay-Stranded Aluminum Conductors for Subsequent Insulation
ABSTRACT
This specification covers the standard requirements for bare combination unilay-stranded conductors made from round wires of aluminum 1350 and 8000 series of aluminum alloys, for insulated conductors to be used for electrical purposes. Aluminum 1350 wires in tempers -H19, -H16 or -H26, -H14 or -H24, and -H142 or -H242 and 8000 series aluminum alloy wires in tempers “0” and H1X or H2X are permitted. These conductors shall be constructed with a central core wire surrounded by two layers of helically laid wires, resulting in an outer diameter equal to the compressed-stranded equivalent conductors. Electric-butt welds, cold pressure welds, or electric-butt cold-upset welds may be made in the finished individual wires composing the conductor. Mechanical (tension) and electrical tests shall be performed on the wires composing the conductors that are annealed and not annealed after stranding. The mass and electrical resistance of a unit length of stranded conductor shall be determined as a function of the length of lay. The conductors shall meet the breaking strength, tensile strength, and bending strength requirements.
SCOPE
1.1 This specification covers bare combination unilay-stranded conductors made from round wires of aluminum 1350 and 8000 series of aluminum alloys, for insulated conductors for electrical purposes. Aluminum 1350 wires in tempers -H19 (extra hard), -H16 or -H26 (3/4 hard), -H14 or -H24 (1/2 hard), and -H142 or -H242 (1/2 hard) and 8000 series aluminum alloys wires in tempers “0” and H1X or H2X are permitted. These conductors shall be constructed with a central core wire surrounded by two layers of helically laid wires, resulting in an outer diameter equal to the compressed-stranded equivalent conductors.
Note 1: For the purpose of this specification, combination unilay conductor is defined as follows: a central core wire surrounded by a layer of six helically laid wires of the same diameter as the core wire with a helically laid outer layer containing six smaller wires alternated between six wires of the same diameter as the wires in the layer underneath. Both layers have a common length and direction of lay (see Fig. 1).
FIG. 1 Cross Section of Conductor
1.1.1 For the purpose of this specification, normal conductor classification (Class AA, A, B, C) is not applicable, as these conductors are intended for subsequent insulation. The descriptive term combination unilay-stranded shall be used in place of conductor classification (Note 2 and Note 3).
Note 2: Prior to 1975, aluminum 1350 was designated as EC aluminum.
Note 3: The aluminum and temper designations conform to ANSI Standard H35.1. Aluminum 1350 corresponds to Unified Numbering System A91350 in accordance with Practice E527. Unified Numbering System alloy designations for 8000 Series aluminum alloys in accordance with Practice E527 are listed in Table number 1 of Specification B800.
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.
1.3 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
General Information
Relations
Buy Standard
Standards Content (Sample)
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: B786/B786M −08 (Reapproved 2018)
Standard Specification for
19 Wire Combination Unilay-Stranded Aluminum
Conductors for Subsequent Insulation
This standard is issued under the fixed designation B786/B786M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 1.3 This international standard was developed in accor-
dance with internationally recognized principles on standard-
1.1 This specification covers bare combination unilay-
ization established in the Decision on Principles for the
strandedconductorsmadefromroundwiresofaluminum1350
Development of International Standards, Guides and Recom-
and 8000 series of aluminum alloys, for insulated conductors
mendations issued by the World Trade Organization Technical
for electrical purposes.Aluminum 1350 wires in tempers -H19
Barriers to Trade (TBT) Committee.
3 1
(extra hard), -H16 or -H26 ( ⁄4 hard), -H14 or -H24 ( ⁄2 hard),
and-H142or-H242( ⁄2hard)and8000seriesaluminumalloys
2. Referenced Documents
wires in tempers “0” and H1X or H2X are permitted. These
conductors shall be constructed with a central core wire
2.1 The following documents of the issue in effect on date
surroundedbytwolayersofhelicallylaidwires,resultinginan
of material purchase form a part of this specification to the
outer diameter equal to the compressed-stranded equivalent
extent referenced herein.
conductors.
2.2 ASTM Standards:
NOTE 1—For the purpose of this specification, combination unilay
B193Test Method for Resistivity of Electrical Conductor
conductor is defined as follows: a central core wire surrounded by a layer
Materials
of six helically laid wires of the same diameter as the core wire with a
B230/B230MSpecification for Aluminum 1350–H19 Wire
helically laid outer layer containing six smaller wires alternated between
six wires of the same diameter as the wires in the layer underneath. Both
for Electrical Purposes
layers have a common length and direction of lay (see Fig. 1).
B263Test Method for Determination of Cross-Sectional
1.1.1 Forthepurposeofthisspecification,normalconductor Area of Stranded Conductors
classification (Class AA, A, B, C) is not applicable, as these
B609/B609M Specification for Aluminum 1350 Round
conductorsareintendedforsubsequentinsulation.Thedescrip- Wire, Annealed and Intermediate Tempers, for Electrical
tivetermcombinationunilay-strandedshallbeusedinplaceof
Purposes
conductor classification (Note 2 and Note 3).
B800Specification for 8000 Series Aluminum Alloy Wire
forElectricalPurposes—AnnealedandIntermediateTem-
NOTE 2—Prior to 1975, aluminum 1350 was designated as EC
pers
aluminum.
NOTE 3—The aluminum and temper designations conform to ANSI B801SpecificationforConcentric-Lay-StrandedConductors
Standard H35.1. Aluminum 1350 corresponds to Unified Numbering
of 8000 SeriesAluminumAlloy for Subsequent Covering
System A91350 in accordance with Practice E527. Unified Numbering
or Insulation
System alloy designations for 8000 Series aluminum alloys in accordance
E29Practice for Using Significant Digits in Test Data to
with Practice E527 are listed in Table number 1 of Specification B800.
Determine Conformance with Specifications
1.2 The values stated in either SI units or inch-pound units
E527Practice for Numbering Metals and Alloys in the
are to be regarded separately as standard. The values stated in
Unified Numbering System (UNS)
each system may not be exact equivalents; therefore, each
2.3 ANSI Standard:
system shall be used independently of the other. Combining
ANSI H35.1/H35.1(M)Alloy and Temper Designation Sys-
values from the two systems may result in non-conformance
tems for Aluminum
with the standard.
1 2
This specification is under the jurisdiction of ASTM Committee B01 on For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Electrical Conductors and is the direct responsibility of Subcommittee B01.07 on contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Conductors of Light Metals. Standards volume information, refer to the standard’s Document Summary page on
Current edition approved March 1, 2018. Published March 2018. Originally the ASTM website.
ε1 3
approved in 1988. Last previous edition approved in 2013 as B786/B786M–13 . Available fromAmerican National Standards Institute (ANSI), 25 W. 43rd St.,
DOI: 10.1520/B0786_B0786M-08R18. 4th Floor, New York, NY 10036, http://www.ansi.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
B786/B786M − 08 (2018)
3.1.7 Whenphysicaltestsshallbemade(seeSections7and
8),
3.1.8 Package size (see 16.1),
3.1.9 Heavy wood lagging, if required (see 17.2),
3.1.10 Special package marking, if required (Section 17),
and
3.1.11 Place of inspection (Section 15).
4. Joints
FIG. 1 Cross Section of Conductor
4.1 Electric-butt welds, cold pressure welds, or electric-butt
TABLE 1 Construction Requirements for 19-Wire Combination
cold-upset welds may be made in the finished individual wires
Unilay Stranded Aluminum Conductors
composing the conductor but shall not be closer together than
A B
Wire D Wire D
Area of Size, American (or
1 2
1 ft (Explanatory Note 2).
Diameter Diameter
Cross-Section, Brown and Sharpe)
cmil Wire Gage
mils mm mils mm
5. Lay
556 500 185.3 4.71 135.6 3.44
500 000 175.6 4.46 128.5 3.26 5.1 For combination unilay conductors the lay of a layer of
477 000 171.5 4.36 125.5 3.19
wires shall be not less than 8 nor more than 16 times the
450 000 166.6 4.23 121.9 3.10
outside diameter of the outer layer.
397 500 156.6 3.98 114.6 2.91
350 000 146.9 3.73 107.5 2.73
5.2 Other lays for special purposes shall be furnished by
336 400 144.0 3.66 105.4 2.68
specialagreementbetweenthemanufacturerandthepurchaser.
300 000 136.0 3.45 99.6 2.53
266 800 128.3 3.26 93.9 2.38
NOTE4—Certaintypesofinsulationconductorsmayrequireshorterlay
250 000 124.2 3.15 90.9 2.31
than other conductors. It is expected that special requirements regarding
211 600 0000 114.2 2.90 83.6 2.12
length of lay will be specified by the purchaser in such instances.
167 800 000 101.7 2.58 74.5 1.89
133 100 00 90.6 2.30 66.3 1.68
5.3 The direction of lay shall be left-hand unless the
105 600 0 80.7 2.05 59.1 1.50
83 690 1 71.8 1.82 52.6 1.34 direction of lay is specified otherwise by the purchaser.
66 360 2 64.0 1.63 46.8 1.19
52 620 3 57.0 1.45 41.7 1.06
6. Construction (Explanatory Note 1)
41 740 4 50.7 1.29 37.1 0.94
33 090 5 45.2 1.15 33.1 0.84 6.1 The areas of cross section, numbers, and diameters of
26 240 6 40.2 1.02 29.4 0.75
wires in the various conductors shall conform to the require-
20 820 7 35.8 0.91 26.2 0.67
ments prescribed in Table 1 (Note 3) (see Fig. 1).
16 510 8 31.9 0.81 23.4 0.59
13 090 9 28.4 0.72 20.8 0.53
6.2 ThediametersofthewireslistedinTable2arenominal.
10 380 10 25.3 0.64 18.5 0.47
In order to produce an essentially round 19-wire construction,
6 530 12 20.1 0.51 14.7 0.37
A the outer 12-wire layer in the combination unilay product is
Equation to calculate D :
comprised of 6 wires of the same diameter as the wires in the
Cross2Sectional Area
D 5
Œ 7-wire core, and 6 wires approximately 25% smaller. The
16.2149
2-wire sizes are alternated around the 7-wire core.
B
Equation to calculate D :
D 5 D 30.732.
7. Mechanical and Electrical Tests of Conductors not
2 1
Annealed after Stranding
7.1 Wires composing the conductors shall be tested prior to
stranding in accordance with the applicable specification (see
2.4 NIST Standard:
11.1.2), and tests on the completed conductor are not required.
NBS Handbook 100—Copper Wire Tables
However, when requested by the purchaser and agreed to by
the manufacturer at time of ordering, the tension tests of wires
3. Ordering Information
before stranding may be waived and the completed conductor
3.1 Orders for materials under this specification shall in-
tested in accordance with 7.2, or wires removed from the
clude the following information:
completed conductor tested in accordance with 7.5.
3.1.1 Conductor alloy,
7.2 When the completed conductor is tested as a unit, the
3.1.2 Quantity of each size,
breaking strength shall be not less than the rated strength of
3.1.3 Conductor size: Circular-mil area or American Wire
1350-H19 conductors or the minimum rated strength of 1350-
Gage, AWG (Section 6 and Table 1),
H16, -H26, -H14, -H24, -H142, and -H242 conductors if
3.1.4 Stranding (see Explanatory Note 1),
failure occurs in the free length at least 1 in. [25 mm] beyond
3.1.5 Temper (see Section 11),
theendofeithergrippingdevice.Thestrengthshallbenotless
3.1.6 Details of special-purpose lays, if required (see 5.2),
than 95% of the rated or minimum rated strength if failure
occurs inside, or within 1 in. of the end of either gripping
device.Thebreakingstrengthof1350-H16,-H26,-H14,-H24,
Available from National Institute of Standards and Technology (NIST), 100
Bureau Dr., Stop 1070, Gaithersburg, MD 20899-1070, http://www.nist.gov. -H142, and -H242 conductors shall be not greater than their
B786/B786M − 08 (2018)
A
TABLE 2 Diameters, Areas and Mass of 19-Wire Combination Unilay Stranded Aluminum Conductor
Size of
Nominal Conductor Direct Current Resistance
Nominal Area Mass
B
Conductor,
Diameter at 20°C
cmil or
2 2
in. mm in. mm lb/1000 ft kg/km Ω/1000 ft Ω/km
AWG
556 500 0.827 21.0 0.4371 282 521 775 0.0312 0.1024
500 000 0.784 19.9 0.3927 253 468 697 0.0347 0.1139
477 000 0.766 19.5 0.3746 242 447 665 0.0364 0.1194
450 000 0.744 18.9 0.3534 228 421 627 0.0385 0.1263
397 500 0.699 17.8 0.3122 201 372 554 0.0436 0.1431
350 000 0.656 16.7 0.2749 177 328 488 0.0495 0.1624
336 400 0.643 16.3 0.2642 170 315 469 0.0516 0.1693
300 000 0.607 15.4 0.2356 152 281 418 0.0578 0.1896
266 800 0.573 14.6 0.2095 135 250 372 0.0650 0.2133
250 000 0.554 14.1 0.1963 127 234 348 0.0694 0.2277
0000 0.510 13.0 0.1662 107 198 295 0.0820 0.2690
000 0.454 11.5 0.1318 85.0 157 234 0.103 0.3389
00 0.404 10.3 0.1045 67.4 125 185 0.130 0.4275
0 0.360 9.14 0.08291 53.5 98.9 147 0.164 0.5387
1 0.321 8.15 0.06573 42.4 78.4 117 0.207 0.6798
2 0.286 7.26 0.05212 33.6 62.1 92.4 0.261 0.8573
3 0.254 6.45 0.04133 26.7 49.3 73.4 0.330 1.0814
4 0.226 5.74 0.03278 21.1 39.1 58.2 0.416 1.3633
5 0.202 5.13 0.02599 16.8 31.0 46.1 0.523 1.72
6 0.179 4.55 0.02061 13.3 24.6 36.6 0.661 2.1684
7 0.160 4.06 0.01635 10.5 19.5 29.0 0.834 2.7362
8 0.143 3.63 0.01297 8.37 15.5 23.1 1.05 3.4464
9 0.127 3.23 0.01028 6.63 12.3 18.3 1.32 4.3307
10 0.113 2.87 0.00816 5.26 9.73 14.5 1.67 5.4790
12 0.090 2.29 0.00513 3.31 6.12 9.11 2.67 8.7598
A
Mass and electrical resistance are based on aluminum 1350.
B
To calculate the diameter, multiply the large wire diameter in Table 1 times 3 and add two times the small wire diameter.
Example: AWG 4/0 diameter = [3(114.2) + 2(83.6)] = 509.8
maximumratedstrengths.Thefreelengthbetweengripsofthe 105% of the maximum tensile strength prescribed in Specifi-
test specimen shall be not less than 24 in. (600 mm) and care cation B609/B609M, as applicable (Explanatory Note 4).
shall be taken to ensure that the wires in the conductor are
7.6 All wires composing the conductors shall be capable of
evenly gripped during the test (Explanatory Note 3).
meeting the bending properties stated in Specification B230/
7.3 The rated strength of 1350-H19 conductors and the
B230Mafterstranding.Routineproductiontestingafterstrand-
minimum rated strength of 1350-H16, -H26, -H14, -H24,
ing is not required.
-H142, and -H242 conductors shall be taken as 93% of the
7.7 Mechanical and electrical tests of conductors in 8000
sum of the specified minimum average tensile strengths of the
series aluminum alloys in “0” temper, H1X or H2X wire and
component wires for 1350-H19 conductors, as prescribed in
not annealed after stranding shall be in accordance with
Table 1, Tensile Requirements, of Specification B230/B230M,
Section 9 of Specification B801.
and of the sum of the specified minimum tensile strengths of
the component wires for 1350-H16, -H26, -H14, -H24, -H142,
8. Mechanical and Electrical Tests of Conductors
and -H242 conductors, as prescribed in Specification B609/
Annealed after Stranding
B609M, as applicable. The maximum rated strength of the
1350-H16, -H26, -H14, -H24, -H142 and -H242 conductors
8.1 Tensile properties and electrical resistivity shall be
shall be taken as the sum of the specified maximum strengths
determinedonsamplestakenfrom10%ofthereelsorcoilsof
of the component wires, as prescribed in Specification B609/
conductor, but from not less than five (or all if the lot is less
B609M, as applicable. The rated strengths shall be calculated
than five) reels or coils. Resistivity shall be determined as
using specified nominal wire diameters.
prescribed in the Resistivity section of Specification B230/
B230M on one wire from each conductor sample except this
7.4 Rated strength and breaking strength values shall be
test is not required if performed previously on the 1350-H19
rounded to three significant figures, in the final value only, in
wire.At the manufacturer’s option, tension tests shall be made
accordance with the rounding method in Practice E29.
either on one of the inner seven wires and one wire from each
7.5 When wires are removed from the completed conductor
additional layer of each conductor sample to determine con-
and tested, 1350-H19 wires shall have minimum tensile
formance with 8.2 or on the conductor as a unit to determine
strengths not less than 95% of the tensile strengths prescribed
conformation with 8.3.
for individual tests in Table 1, Tensile Requirements, of
Specification B230/B230M. 1350-H16, -H26, -H14, -H24, 8.2 When wires removed from the completed conductor are
-H142, and -H242 wires shall have tensile strengths not less tested, 1350-H26, -H24, and -H242 wires shall have tensile
than 95% of the minimum tensile strength nor more than strengths not less than 95% of the minimum tensile strength
B786/B786M − 08 (2018)
nor more than 105% of the maximum tensile strength pre- 11. Requirements for Wires
scribed in Specification B609/B609M, as applicable (Explana-
11.1 Thepurchasershalldesignatethetemperofwirestobe
tory Note 4).
used in the conductor.
8.3 When the completed conductor is tested as a unit, the 11.1.1 Forconductorsofaluminum1350withtempersother
breaking strengths of 1350-H26, -H24, a
...
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: B786/B786M − 08 (Reapproved 2018)
Standard Specification for
19 Wire Combination Unilay-Stranded Aluminum
Conductors for Subsequent Insulation
This standard is issued under the fixed designation B786/B786M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 1.3 This international standard was developed in accor-
dance with internationally recognized principles on standard-
1.1 This specification covers bare combination unilay-
ization established in the Decision on Principles for the
stranded conductors made from round wires of aluminum 1350
Development of International Standards, Guides and Recom-
and 8000 series of aluminum alloys, for insulated conductors
mendations issued by the World Trade Organization Technical
for electrical purposes. Aluminum 1350 wires in tempers -H19
Barriers to Trade (TBT) Committee.
3 1
(extra hard), -H16 or -H26 ( ⁄4 hard), -H14 or -H24 ( ⁄2 hard),
and -H142 or -H242 ( ⁄2 hard) and 8000 series aluminum alloys
2. Referenced Documents
wires in tempers “0” and H1X or H2X are permitted. These
conductors shall be constructed with a central core wire
2.1 The following documents of the issue in effect on date
surrounded by two layers of helically laid wires, resulting in an
of material purchase form a part of this specification to the
outer diameter equal to the compressed-stranded equivalent
extent referenced herein.
conductors.
2.2 ASTM Standards:
NOTE 1—For the purpose of this specification, combination unilay
B193 Test Method for Resistivity of Electrical Conductor
conductor is defined as follows: a central core wire surrounded by a layer
Materials
of six helically laid wires of the same diameter as the core wire with a
B230/B230M Specification for Aluminum 1350–H19 Wire
helically laid outer layer containing six smaller wires alternated between
six wires of the same diameter as the wires in the layer underneath. Both
for Electrical Purposes
layers have a common length and direction of lay (see Fig. 1).
B263 Test Method for Determination of Cross-Sectional
1.1.1 For the purpose of this specification, normal conductor
Area of Stranded Conductors
classification (Class AA, A, B, C) is not applicable, as these B609/B609M Specification for Aluminum 1350 Round
conductors are intended for subsequent insulation. The descrip-
Wire, Annealed and Intermediate Tempers, for Electrical
tive term combination unilay-stranded shall be used in place of
Purposes
conductor classification (Note 2 and Note 3).
B800 Specification for 8000 Series Aluminum Alloy Wire
for Electrical Purposes—Annealed and Intermediate Tem-
NOTE 2—Prior to 1975, aluminum 1350 was designated as EC
pers
aluminum.
NOTE 3—The aluminum and temper designations conform to ANSI
B801 Specification for Concentric-Lay-Stranded Conductors
Standard H35.1. Aluminum 1350 corresponds to Unified Numbering
of 8000 Series Aluminum Alloy for Subsequent Covering
System A91350 in accordance with Practice E527. Unified Numbering
or Insulation
System alloy designations for 8000 Series aluminum alloys in accordance
E29 Practice for Using Significant Digits in Test Data to
with Practice E527 are listed in Table number 1 of Specification B800.
Determine Conformance with Specifications
1.2 The values stated in either SI units or inch-pound units
E527 Practice for Numbering Metals and Alloys in the
are to be regarded separately as standard. The values stated in
Unified Numbering System (UNS)
each system may not be exact equivalents; therefore, each
2.3 ANSI Standard:
system shall be used independently of the other. Combining
ANSI H35.1/H35.1(M) Alloy and Temper Designation Sys-
values from the two systems may result in non-conformance
tems for Aluminum
with the standard.
1 2
This specification is under the jurisdiction of ASTM Committee B01 on For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Electrical Conductors and is the direct responsibility of Subcommittee B01.07 on contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Conductors of Light Metals. Standards volume information, refer to the standard’s Document Summary page on
Current edition approved March 1, 2018. Published March 2018. Originally the ASTM website.
ε1 3
approved in 1988. Last previous edition approved in 2013 as B786/B786M – 13 . Available from American National Standards Institute (ANSI), 25 W. 43rd St.,
DOI: 10.1520/B0786_B0786M-08R18. 4th Floor, New York, NY 10036, http://www.ansi.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
B786/B786M − 08 (2018)
3.1.7 When physical tests shall be made (see Sections 7 and
8),
3.1.8 Package size (see 16.1),
3.1.9 Heavy wood lagging, if required (see 17.2),
3.1.10 Special package marking, if required (Section 17),
and
3.1.11 Place of inspection (Section 15).
4. Joints
FIG. 1 Cross Section of Conductor
4.1 Electric-butt welds, cold pressure welds, or electric-butt
TABLE 1 Construction Requirements for 19-Wire Combination
cold-upset welds may be made in the finished individual wires
Unilay Stranded Aluminum Conductors
composing the conductor but shall not be closer together than
A B
Wire D Wire D
Area of Size, American (or 1 2
1 ft (Explanatory Note 2).
Diameter Diameter
Cross-Section, Brown and Sharpe)
cmil Wire Gage mils mm mils mm
5. Lay
556 500 185.3 4.71 135.6 3.44
500 000 175.6 4.46 128.5 3.26 5.1 For combination unilay conductors the lay of a layer of
477 000 171.5 4.36 125.5 3.19
wires shall be not less than 8 nor more than 16 times the
450 000 166.6 4.23 121.9 3.10
outside diameter of the outer layer.
397 500 156.6 3.98 114.6 2.91
350 000 146.9 3.73 107.5 2.73
5.2 Other lays for special purposes shall be furnished by
336 400 144.0 3.66 105.4 2.68
special agreement between the manufacturer and the purchaser.
300 000 136.0 3.45 99.6 2.53
266 800 128.3 3.26 93.9 2.38
NOTE 4—Certain types of insulation conductors may require shorter lay
250 000 124.2 3.15 90.9 2.31
than other conductors. It is expected that special requirements regarding
211 600 0000 114.2 2.90 83.6 2.12
length of lay will be specified by the purchaser in such instances.
167 800 000 101.7 2.58 74.5 1.89
133 100 00 90.6 2.30 66.3 1.68
5.3 The direction of lay shall be left-hand unless the
105 600 0 80.7 2.05 59.1 1.50
direction of lay is specified otherwise by the purchaser.
83 690 1 71.8 1.82 52.6 1.34
66 360 2 64.0 1.63 46.8 1.19
52 620 3 57.0 1.45 41.7 1.06
6. Construction (Explanatory Note 1)
41 740 4 50.7 1.29 37.1 0.94
33 090 5 45.2 1.15 33.1 0.84 6.1 The areas of cross section, numbers, and diameters of
26 240 6 40.2 1.02 29.4 0.75
wires in the various conductors shall conform to the require-
20 820 7 35.8 0.91 26.2 0.67
ments prescribed in Table 1 (Note 3) (see Fig. 1).
16 510 8 31.9 0.81 23.4 0.59
13 090 9 28.4 0.72 20.8 0.53
6.2 The diameters of the wires listed in Table 2 are nominal.
10 380 10 25.3 0.64 18.5 0.47
In order to produce an essentially round 19-wire construction,
6 530 12 20.1 0.51 14.7 0.37
A
the outer 12-wire layer in the combination unilay product is
Equation to calculate D :
comprised of 6 wires of the same diameter as the wires in the
Cross 2 Sectional Area
D 5
Œ 7-wire core, and 6 wires approximately 25 % smaller. The
16.2149
2-wire sizes are alternated around the 7-wire core.
B
Equation to calculate D :
D 5 D 3 0.732.
2 1 7. Mechanical and Electrical Tests of Conductors not
Annealed after Stranding
7.1 Wires composing the conductors shall be tested prior to
stranding in accordance with the applicable specification (see
2.4 NIST Standard:
11.1.2), and tests on the completed conductor are not required.
NBS Handbook 100 —Copper Wire Tables
However, when requested by the purchaser and agreed to by
the manufacturer at time of ordering, the tension tests of wires
3. Ordering Information
before stranding may be waived and the completed conductor
3.1 Orders for materials under this specification shall in-
tested in accordance with 7.2, or wires removed from the
clude the following information:
completed conductor tested in accordance with 7.5.
3.1.1 Conductor alloy,
7.2 When the completed conductor is tested as a unit, the
3.1.2 Quantity of each size,
breaking strength shall be not less than the rated strength of
3.1.3 Conductor size: Circular-mil area or American Wire
1350-H19 conductors or the minimum rated strength of 1350-
Gage, AWG (Section 6 and Table 1),
H16, -H26, -H14, -H24, -H142, and -H242 conductors if
3.1.4 Stranding (see Explanatory Note 1),
failure occurs in the free length at least 1 in. [25 mm] beyond
3.1.5 Temper (see Section 11),
the end of either gripping device. The strength shall be not less
3.1.6 Details of special-purpose lays, if required (see 5.2),
than 95 % of the rated or minimum rated strength if failure
occurs inside, or within 1 in. of the end of either gripping
4 device. The breaking strength of 1350-H16, -H26, -H14, -H24,
Available from National Institute of Standards and Technology (NIST), 100
Bureau Dr., Stop 1070, Gaithersburg, MD 20899-1070, http://www.nist.gov. -H142, and -H242 conductors shall be not greater than their
B786/B786M − 08 (2018)
A
TABLE 2 Diameters, Areas and Mass of 19-Wire Combination Unilay Stranded Aluminum Conductor
Size of
Nominal Conductor Direct Current Resistance
Nominal Area Mass
B
Conductor,
Diameter at 20°C
cmil or
2 2
in. mm in. mm lb/1000 ft kg/km Ω/1000 ft Ω/km
AWG
556 500 0.827 21.0 0.4371 282 521 775 0.0312 0.1024
500 000 0.784 19.9 0.3927 253 468 697 0.0347 0.1139
477 000 0.766 19.5 0.3746 242 447 665 0.0364 0.1194
450 000 0.744 18.9 0.3534 228 421 627 0.0385 0.1263
397 500 0.699 17.8 0.3122 201 372 554 0.0436 0.1431
350 000 0.656 16.7 0.2749 177 328 488 0.0495 0.1624
336 400 0.643 16.3 0.2642 170 315 469 0.0516 0.1693
300 000 0.607 15.4 0.2356 152 281 418 0.0578 0.1896
266 800 0.573 14.6 0.2095 135 250 372 0.0650 0.2133
250 000 0.554 14.1 0.1963 127 234 348 0.0694 0.2277
0000 0.510 13.0 0.1662 107 198 295 0.0820 0.2690
000 0.454 11.5 0.1318 85.0 157 234 0.103 0.3389
00 0.404 10.3 0.1045 67.4 125 185 0.130 0.4275
0 0.360 9.14 0.08291 53.5 98.9 147 0.164 0.5387
1 0.321 8.15 0.06573 42.4 78.4 117 0.207 0.6798
2 0.286 7.26 0.05212 33.6 62.1 92.4 0.261 0.8573
3 0.254 6.45 0.04133 26.7 49.3 73.4 0.330 1.0814
4 0.226 5.74 0.03278 21.1 39.1 58.2 0.416 1.3633
5 0.202 5.13 0.02599 16.8 31.0 46.1 0.523 1.72
6 0.179 4.55 0.02061 13.3 24.6 36.6 0.661 2.1684
7 0.160 4.06 0.01635 10.5 19.5 29.0 0.834 2.7362
8 0.143 3.63 0.01297 8.37 15.5 23.1 1.05 3.4464
9 0.127 3.23 0.01028 6.63 12.3 18.3 1.32 4.3307
10 0.113 2.87 0.00816 5.26 9.73 14.5 1.67 5.4790
12 0.090 2.29 0.00513 3.31 6.12 9.11 2.67 8.7598
A
Mass and electrical resistance are based on aluminum 1350.
B
To calculate the diameter, multiply the large wire diameter in Table 1 times 3 and add two times the small wire diameter.
Example: AWG 4/0 diameter = [3(114.2) + 2(83.6)] = 509.8
maximum rated strengths. The free length between grips of the 105 % of the maximum tensile strength prescribed in Specifi-
test specimen shall be not less than 24 in. (600 mm) and care cation B609/B609M, as applicable (Explanatory Note 4).
shall be taken to ensure that the wires in the conductor are
7.6 All wires composing the conductors shall be capable of
evenly gripped during the test (Explanatory Note 3).
meeting the bending properties stated in Specification B230/
7.3 The rated strength of 1350-H19 conductors and the
B230M after stranding. Routine production testing after strand-
minimum rated strength of 1350-H16, -H26, -H14, -H24,
ing is not required.
-H142, and -H242 conductors shall be taken as 93 % of the
7.7 Mechanical and electrical tests of conductors in 8000
sum of the specified minimum average tensile strengths of the
series aluminum alloys in “0” temper, H1X or H2X wire and
component wires for 1350-H19 conductors, as prescribed in
not annealed after stranding shall be in accordance with
Table 1, Tensile Requirements, of Specification B230/B230M,
Section 9 of Specification B801.
and of the sum of the specified minimum tensile strengths of
the component wires for 1350-H16, -H26, -H14, -H24, -H142,
8. Mechanical and Electrical Tests of Conductors
and -H242 conductors, as prescribed in Specification B609/
Annealed after Stranding
B609M, as applicable. The maximum rated strength of the
1350-H16, -H26, -H14, -H24, -H142 and -H242 conductors
8.1 Tensile properties and electrical resistivity shall be
shall be taken as the sum of the specified maximum strengths
determined on samples taken from 10 % of the reels or coils of
of the component wires, as prescribed in Specification B609/
conductor, but from not less than five (or all if the lot is less
B609M, as applicable. The rated strengths shall be calculated
than five) reels or coils. Resistivity shall be determined as
using specified nominal wire diameters.
prescribed in the Resistivity section of Specification B230/
B230M on one wire from each conductor sample except this
7.4 Rated strength and breaking strength values shall be
test is not required if performed previously on the 1350-H19
rounded to three significant figures, in the final value only, in
wire. At the manufacturer’s option, tension tests shall be made
accordance with the rounding method in Practice E29.
either on one of the inner seven wires and one wire from each
7.5 When wires are removed from the completed conductor
additional layer of each conductor sample to determine con-
and tested, 1350-H19 wires shall have minimum tensile
formance with 8.2 or on the conductor as a unit to determine
strengths not less than 95 % of the tensile strengths prescribed
conformation with 8.3.
for individual tests in Table 1, Tensile Requirements, of
Specification B230/B230M. 1350-H16, -H26, -H14, -H24, 8.2 When wires removed from the completed conductor are
-H142, and -H242 wires shall have tensile strengths not less tested, 1350-H26, -H24, and -H242 wires shall have tensile
than 95 % of the minimum tensile strength nor more than strengths not less than 95 % of the minimum tensile strength
B786/B786M − 08 (2018)
nor more than 105 % of the maximum tensile strength pre- 11. Requirements for Wires
scribed in Specification B609/B609M, as applicable (Explana-
11.1 The purchaser shall designate the temper of wires to be
tory Note 4).
used in the conductor.
8.3 When the completed conductor is tested as a unit, the 11.1.1 For conductors o
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
´1
Designation: B786/B786M − 08 (Reapproved 2013) B786/B786M − 08 (Reapproved 2018)
Standard Specification for
19 Wire Combination Unilay-Stranded Aluminum
Conductors for Subsequent Insulation
This standard is issued under the fixed designation B786/B786M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
ε NOTE—Designation was corrected editorially in October 2013.
1. Scope
1.1 This specification covers bare combination unilay-stranded conductors made from round wires of aluminum 1350 and 8000
series of aluminum alloys, for insulated conductors for electrical purposes. Aluminum 1350 wires in tempers -H19 (extra hard),
3 1 1
-H16 or -H26 ( ⁄4 hard), -H14 or -H24 ( ⁄2 hard), and -H142 or -H242 ( ⁄2 hard) and 8000 series aluminum alloys wires in tempers
“0” and H1X or H2X are permitted. These conductors shall be constructed with a central core wire surrounded by two layers of
helically laid wires, resulting in an outer diameter equal to the compressed-stranded equivalent conductors.
NOTE 1—For the purpose of this specification, combination unilay conductor is defined as follows: a central core wire surrounded by a layer of six
helically laid wires of the same diameter as the core wire with a helically laid outer layer containing six smaller wires alternated between six wires of
the same diameter as the wires in the layer underneath. Both layers have a common length and direction of lay (see Fig. 1).
1.1.1 For the purpose of this specification, normal conductor classification (Class AA, A, B, C) is not applicable, as these
conductors are intended for subsequent insulation. The descriptive term combination unilay-stranded shall be used in place of
conductor classification (Note 2 and Note 3).
NOTE 2—Prior to 1975, aluminum 1350 was designated as EC aluminum.
NOTE 3—The aluminum and temper designations conform to ANSI Standard H35.1. Aluminum 1350 corresponds to Unified Numbering System
A91350 in accordance with Practice E527. Unified Numbering System alloy designations for 8000 Series aluminum alloys in accordance with Practice
E527 are listed in Table number 1 of Specification B800.
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each
system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the
two systems may result in non-conformance with the standard.
1.3 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2.1 The following documents of the issue in effect on date of material purchase form a part of this specification to the extent
referenced herein.
2.2 ASTM Standards:
B193 Test Method for Resistivity of Electrical Conductor Materials
B230/B230M Specification for Aluminum 1350–H19 Wire for Electrical Purposes
B263 Test Method for Determination of Cross-Sectional Area of Stranded Conductors
B609/B609M Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
B800 Specification for 8000 Series Aluminum Alloy Wire for Electrical Purposes—Annealed and Intermediate Tempers
B801 Specification for Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or
Insulation
This specification is under the jurisdiction of ASTM Committee B01 on Electrical Conductors and is the direct responsibility of Subcommittee B01.07 on Conductors
of Light Metals.
Current edition approved April 1, 2013March 1, 2018. Published April 2013March 2018. Originally approved in 1988. Last previous edition approved in 20082013 as
ε1
B786 – 08.B786/B786M – 13 . DOI: 10.1520/B0786_B0786M-08R13E01.10.1520/B0786_B0786M-08R18.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’sstandard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
B786/B786M − 08 (2018)
FIG. 1 Cross Section of Conductor
TABLE 1 Construction Requirements for 19-Wire Combination
Unilay Stranded Aluminum Conductors
A B
Wire D Wire D
Area of Size, American (or
1 2
Diameter Diameter
Cross-Section, Brown and Sharpe)
cmil Wire Gage
mils mm mils mm
556 500 185.3 4.71 135.6 3.44
500 000 175.6 4.46 128.5 3.26
477 000 171.5 4.36 125.5 3.19
450 000 166.6 4.23 121.9 3.10
397 500 156.6 3.98 114.6 2.91
350 000 146.9 3.73 107.5 2.73
336 400 144.0 3.66 105.4 2.68
300 000 136.0 3.45 99.6 2.53
266 800 128.3 3.26 93.9 2.38
250 000 124.2 3.15 90.9 2.31
211 600 0000 114.2 2.90 83.6 2.12
167 800 000 101.7 2.58 74.5 1.89
133 100 00 90.6 2.30 66.3 1.68
105 600 0 80.7 2.05 59.1 1.50
83 690 1 71.8 1.82 52.6 1.34
66 360 2 64.0 1.63 46.8 1.19
52 620 3 57.0 1.45 41.7 1.06
41 740 4 50.7 1.29 37.1 0.94
33 090 5 45.2 1.15 33.1 0.84
26 240 6 40.2 1.02 29.4 0.75
20 820 7 35.8 0.91 26.2 0.67
16 510 8 31.9 0.81 23.4 0.59
13 090 9 28.4 0.72 20.8 0.53
10 380 10 25.3 0.64 18.5 0.47
6 530 12 20.1 0.51 14.7 0.37
A
Equation to calculate D :
Cross 2Sectional Area
D 5
Œ
16.2149
B
Equation to calculate D :
D 5D 30.732.
2 1
E29 Practice for Using Significant Digits in Test Data to Determine Conformance with Specifications
E527 Practice for Numbering Metals and Alloys in the Unified Numbering System (UNS)
2.3 ANSI Standard:
ANSI H35.1/H35.1(M) Alloy and Temper Designation Systems for Aluminum
2.4 NIST Standard:
NBS Handbook 100 — NBS Handbook 100Copper Wire Tables
3. Ordering Information
3.1 Orders for materials under this specification shall include the following information:
3.1.1 Conductor alloy,
3.1.2 Quantity of each size,
3.1.3 Conductor size: Circular-mil area or American Wire Gage, AWG (Section 6 and Table 1),
3.1.4 Stranding (see Explanatory Note 1),
Available from American National Standards Institute (ANSI), 25 W. 43rd St., 4th Floor, New York, NY 10036, http://www.ansi.org.
Available from National Institute of Standards and Technology (NIST), 100 Bureau Dr., Stop 1070, Gaithersburg, MD 20899-1070, http://www.nist.gov.
B786/B786M − 08 (2018)
3.1.5 Temper (see Section 11),
3.1.6 Details of special-purpose lays, if required (see 5.2),
3.1.7 When physical tests shall be made (see Sections 7 and 8),
3.1.8 Package size (see 16.1),
3.1.9 Heavy wood lagging, if required (see 17.2),
3.1.10 Special package marking, if required (Section 17), and
3.1.11 Place of inspection (Section 15).
4. Joints
4.1 Electric-butt welds, cold pressure welds, or electric-butt cold-upset welds may be made in the finished individual wires
composing the conductor but shall not be closer together than 1 ft (Explanatory Note 2).
5. Lay
5.1 For combination unilay conductors the lay of a layer of wires shall be not less than 8 nor more than 16 times the outside
diameter of the outer layer.
5.2 Other lays for special purposes shall be furnished by special agreement between the manufacturer and the purchaser.
NOTE 4—Certain types of insulation conductors may require shorter lay than other conductors. It is expected that special requirements regarding length
of lay will be specified by the purchaser in such instances.
5.3 The direction of lay shall be left-hand unless the direction of lay is specified otherwise by the purchaser.
6. Construction (Explanatory Note 1)
6.1 The areas of cross section, numbers, and diameters of wires in the various conductors shall conform to the requirements
prescribed in Table 1 (Note 3) (see Fig. 1).
6.2 The diameters of the wires listed in Table 2 are nominal. In order to produce an essentially round 19-wire construction, the
outer 12-wire layer in the combination unilay product is comprised of 6 wires of the same diameter as the wires in the 7-wire core,
and 6 wires approximately 25 % smaller. The 2-wire sizes are alternated around the 7-wire core.
7. Mechanical and Electrical Tests of Conductors not Annealed after Stranding
7.1 Wires composing the conductors shall be tested prior to stranding in accordance with the applicable specification (see
11.1.2), and tests on the completed conductor are not required. However, when requested by the purchaser and agreed to by the
A
TABLE 2 Diameters, Areas and Mass of 19-Wire Combination Unilay Stranded Aluminum Conductor
Nominal Conductor Direct Current Resistance
Size of
Nominal Area Mass
B
Diameter at 20°C
Conductor,
cmil or
Ω/1000/
2 2
in. mm in. mm lb/1000 ft kg/km Ω/km/km
AWG
1000 ft
556 500 0.827 21.0 0.4371 282 521 775 0.0312 0.1024
500 000 0.784 19.9 0.3927 253 468 697 0.0347 0.1139
477 000 0.766 19.5 0.3746 242 447 665 0.0364 0.1194
450 000 0.744 18.9 0.3534 228 421 627 0.0385 0.1263
397 500 0.699 17.8 0.3122 201 372 554 0.0436 0.1431
350 000 0.656 16.7 0.2749 177 328 488 0.0495 0.1624
336 400 0.643 16.3 0.2642 170 315 469 0.0516 0.1693
300 000 0.607 15.4 0.2356 152 281 418 0.0578 0.1896
266 800 0.573 14.6 0.2095 135 250 372 0.0650 0.2133
250 000 0.554 14.1 0.1963 127 234 348 0.0694 0.2277
0000 0.510 13.0 0.1662 107 198 295 0.0820 0.2690
000 0.454 11.5 0.1318 85.0 157 234 0.103 0.3389
00 0.404 10.3 0.1045 67.4 125 185 0.130 0.4275
0 0.360 9.14 0.08291 53.5 98.9 147 0.164 0.5387
1 0.321 8.15 0.06573 42.4 78.4 117 0.207 0.6798
2 0.286 7.26 0.05212 33.6 62.1 92.4 0.261 0.8573
3 0.254 6.45 0.04133 26.7 49.3 73.4 0.330 1.0814
4 0.226 5.74 0.03278 21.1 39.1 58.2 0.416 1.3633
5 0.202 5.13 0.02599 16.8 31.0 46.1 0.523 1.72
6 0.179 4.55 0.02061 13.3 24.6 36.6 0.661 2.1684
7 0.160 4.06 0.01635 10.5 19.5 29.0 0.834 2.7362
8 0.143 3.63 0.01297 8.37 15.5 23.1 1.05 3.4464
9 0.127 3.23 0.01028 6.63 12.3 18.3 1.32 4.3307
10 0.113 2.87 0.00816 5.26 9.73 14.5 1.67 5.4790
12 0.090 2.29 0.00513 3.31 6.12 9.11 2.67 8.7598
A
Mass and electrical resistance are based on aluminum 1350.
B
To calculate the diameter, multiply the large wire diameter in Table 1 times 3 and add two times the small wire diameter.
Example: AWG 4/0 diameter = [3(114.2) + 2(83.6)] = 509.8
B786/B786M − 08 (2018)
manufacturer at time of ordering, the tension tests of wires before stranding may be waived and the completed conductor tested
in accordance with 7.2, or wires removed from the completed conductor tested in accordance with 7.5.
7.2 When the completed conductor is tested as a unit, the breaking strength shall be not less than the rated strength of 1350-H19
conductors or the minimum rated strength of 1350-H16, -H26, -H14, -H24, -H142, and -H242 conductors if failure occurs in the
free length at least 1 in. [25 mm] beyond the end of either gripping device. The strength shall be not less than 95 % of the rated
or minimum rated strength if failure occurs inside, or within 1 in. of the end of either gripping device. The breaking strength of
1350-H16, -H26, -H14, -H24, -H142, and -H242 conductors shall be not greater than their maximum rated strengths. The free
length between grips of the test specimen shall be not less than 24 in. (600 mm) and care shall be taken to ensure that the wires
in the conductor are evenly gripped during the test (Explanatory Note 3).
7.3 The rated strength of 1350-H19 conductors and the minimum rated strength of 1350-H16, -H26, -H14, -H24, -H142, and
-H242 conductors shall be taken as 93 % of the sum of the specified minimum average tensile strengths of the component wires
for 1350-H19 conductors, as prescribed in Table 1, Tensile Requirements, of Specification B230/B230M, and of the sum of the
specified minimum tensile strengths of the component wires for 1350-H16, -H26, -H14, -H24, -H142, and -H242 conductors, as
prescribed in Specification B609/B609M, as applicable. The maximum rated strength of the 1350-H16, -H26, -H14, -H24, -H142
and -H242 conductors shall be taken as the sum of the specified maximum strengths of the component wires, as prescribed in
Specification B609/B609M, as applicable. The rated strengths shall be calculated using specified nominal wire diameters.
7.4 Rated strength and breaking strength values shall be rounded to three significant figures, in the final value only, in
accordance with the rounding method in Practice E29.
7.5 When wires are removed from the completed conductor and tested, 1350-H19 wires shall have minimum tensile strengths
not less than 95 % of the tensile strengths prescribed for individual tests in Table 1, Tensile Requirements, of Specification
B230/B230M. 1350-H16, -H26, -H14, -H24, -H142, and -H242 wires shall have tensile strengths not less than 95 % of the
minimum tensile strength nor more than 105 % of the maximum tensile strength prescribed in Specification B609/B609M, as
applicable (Explanatory Note 4).
7.6 All wires composing the conductors shall be capable of meeting the bending properties stated in Specification B230/B230M
after stranding. Routine production testing after stranding is not required.
7.7 Mechanical and electrical tests of conductors in 8000 series aluminum alloys in “0” temper, H1X or H2X wire and not
annealed after stranding shall be in accordance with Section 9 of Specification B801.
8. Mechanical and Electrical Tests of Conductors Annealed after Stranding
8.1 Tensile properties and electrical resistivity shall be determined on samples taken from 10 % of the reels or coils of
conductor, but from not less than five (or all if the lot is less than five) reels or coils. Resistivity shall be determined as prescribed
in the Resistivity section of Specification B230/B230M on one wire from each conductor sample except this test is not required
if performed previously on the 1350-H19 wire. At the manufacturer’s option, tension tests shall be made either on one of the inner
seven wires and one wire from each additional layer of each conductor sample to determine conformance with 8.2 or on the
conductor as a unit to determine conformation with 8.3.
8.2 When wires removed from the completed conductor are tested, 1350-H26, -H24, and -H242 w
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.