Standard Specification for Surge Suppressors for Shipboard Use

ABSTRACT
This specification establishes the performance requirements for surge suppressors used on shipboard ac power circuits that may consist of a single circuit element or may be a hybrid device using several suppression devices. The surge suppressor shall be a protective device for limiting voltage transients on equipment by discharging, dissipating internally, bypassing surge current, or a combination thereof, and which prevents continued flow of follow current to ground and is capable of repeating these functions. Surge suppressors shall be classified into the following classes and types: Class A—surge suppressor associated with long circuit branch; Class B—surge suppressor for short branch circuit; and Type I—permanent connected type; Type II—plug-in type; Type III—cord-connected type; and Type IV—power director (power center) type. The surge suppressors shall conform to specified performance, operating, grounding, and supplementary protection requirements. They shall also undergo designated design, and conformance production tests such as insulation withstand test, power frequency withstand test, impulse voltage-time tests (including fast-front impulse suppression tests and slow-front impulse suppression tests), voltage protection level tests, duty cycle tests, life cycle tests (including voltage and current impulses), load current and voltage drop tests (including rated current and voltage drop and inrush current), and ground continuity test.
SCOPE
1.1 This standard establishes performance requirements of surge suppressors for use on shipboard ac power circuits.
1.2 Surge suppressor shall be a protective device for limiting voltage transients on equipment by discharging, dissipating internally, bypassing surge current, or a combination thereof; and which prevents continued flow of follow current to ground and is capable of repeating these functions.
1.3 Surge suppressors covered by this specification may consist of a single circuit element, or may be a hybrid device employing several suppression devices.

General Information

Status
Historical
Publication Date
31-Jan-2006
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM F1507-99(2006) - Standard Specification for Surge Suppressors for Shipboard Use
English language
9 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
An American National Standard
Designation: F1507 – 99 (Reapproved 2006)
Standard Specification for
Surge Suppressors for Shipboard Use
This standard is issued under the fixed designation F1507; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 3. Terminology
1.1 This specification establishes performance requirements 3.1 Definitions:
of surge suppressors for use on shipboard ac power circuits.
NOTE 1—These definitions other than specific to the standard are taken
1.2 Surge suppressor shall be a protective device for limit-
from UL 1449, ANSI/IEEE C62.41, and MIL-STD 1399 to provide for
ing voltage transients on equipment by discharging, dissipating
harmonization of terms.
internally, bypassing surge current, or a combination thereof
3.2 power interface—The electrical points where the surge
and which prevents continued flow of follow current to ground
suppression device is electrically connected to the ac power
and is capable of repeating these functions.
system.
1.3 Surge suppressors covered by this specification may
3.3 combination wave—Asurge delivered by an instrument
consist of a single circuit element or may be a hybrid device
that has the inherent capability of applying a 1.2/50-µs voltage
using several suppression devices.
wave across an open circuit and delivering an 8/20-µs current
wave into a short circuit. The exact wave that is delivered is
2. Referenced Documents
determined by the instantaneous impedance to which the
2.1 The following documents of the issue in effect on the
combination wave is applied. (Also called combination
dateofmaterialpurchaseformapartofthisspecificationtothe
voltage/current surge or combination V/I surge.)
extent referenced herein:
3.4 crest (peak) value (of a wave, surge or impulse)—The
2.2 American National Standards:
maximum value that a wave, surge, or impulse attains.
ANSI/IEEE Std 4 IEEE Standard Techniques for High
3.5 electric power source—The electric power that is sup-
Voltage Testing
plied for testing.
ANSI/IEEE C62.41 Recommended Practice on Surge Volt-
3.6 electric power system ground—Ground is a plane or
age in Low-Voltage AC Power Circuits
surface used by the electric power system as a common
ANSI/IEEE C62.45 Guide on Surge Testing for Equipment
reference to establish zero potential. Usually, this surface is the
Connected to Low-Voltage AC Power Circuits
metallic hull of the ship. On a nonmetallic hull ship, a special
ANSI/IEEE C84.1 Electrical Power Systems and
ground system is installed for this purpose.
Equipment—Voltage Ratings
3.7 follow(power)current—Thecurrentfromtheconnected
2.3 Military Standard:
power source that flows through a surge protective device
MIL-STD-1399 Section 300; Military Standard Interface
following the passage of discharge current.
Standard for Shipboard Systems, Section 300, Electric
3.8 frequency tolerance—Frequency tolerance is the maxi-
Power, Alternating Current
mum permitted departure from nominal frequency during
2.4 Underwriters Laboratories Standard:
normal operation, excluding transient and cyclic frequency
UL 1449 Transient Voltage Surge Suppressors, 2nd Edition
variations. This includes variations such as those caused by
load changes, switchboard frequency meter error, and drift.
This specification is under the jurisdiction of ASTM Committee F25 on Ships Unless specified otherwise, frequency tolerance shall be con-
and Marine Technology and is the direct responsibility of Subcommittee F25.10 on
sidered to be 610 % of nominal frequency.
Electrical.
3.9 inrush current—The inrush current is a sudden change
Current edition approved Feb. 1, 2006. Published February 2006. Originally
in line current that occurs during startup or as a result of a
approved in 1994. Last previous edition approved in 1999 as F1507 – 99. DOI:
10.1520/F1507-99R06.
change to the operating mode. Inrush current is dependent on
Available fromAmerican National Standards Institute (ANSI), 25 W. 43rd St.,
the type of load connected to the surge suppressor, and
4th Floor, New York, NY 10036.
3 typically will rise to a maximum value in a few milliseconds
AvailablefromStandardizationDocumentsOrderDesk,Bldg.4SectionD,700
and decay to rated value in several milliseconds to several
Robbins Ave., Philadelphia, PA 19111-5094, Attn: NPODS.
Available from Underwriters Laboratories (UL), Corporate Progress, 333
seconds.
Pfingsten Rd., Northbrook, IL 60062.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
F1507 – 99 (2006)
3.10 leakage current—Line current drawn, either line-to- 3.23 transient voltage surge suppressor (TVSS)—A surge
line or line-to-ground, by the suppressor when operated at the protective device intended for connection electrically on the
maximum continuous operating voltage. load side of the main overcurrent protection in circuits not
exceeding 600V. (Location CategoriesAand B as described in
3.11 maximum continuous operating voltage—Maximum
ANSI/IEEE C62.41.)
sinusoidal rms voltage which may be continuously applied
3.24 two-port transient voltage surge suppressor—ATVSS
without degradation or deleterious effects.
having one set of electrical connections (terminals, leads and
3.12 measured limiting voltage—The crest (peak) value of
the like) intended for connection to the ac power circuit and
the voltage measured at the leads, terminals, receptacle con-
one or more separate sets of electrical connections (terminals,
tacts and the like, intended for connection to the load(s) to be
leads, outlet receptacles, and so forth) intended for connecting
protected, and resulting from application of a specified surge.
theload(s)tobeprotected.Thisdeviceisseries-connectedsuch
3.13 nominal frequency—the nominal frequency is the des-
that load current will flow through the transient voltage surge
ignated frequency in Hz.
suppressor.
3.14 nominal system voltage—A nominal value assigned to
3.25 voltage drop—Voltage differential measured from in-
designate a system of a given voltage class in accordance with
put terminals to output terminals under conditions of rated load
ANSI/IEEE C84.1. For the purpose of this standard, nominal
current for two-port surge suppressors.
system voltages are 120, 208, 240, and 480 vac.All voltages in
3.26 voltage protection level—A suppression rating (or
this standard are root-mean-square (rms) unless stated other-
ratings) in volts or kilovolts, selected by the manufacturer that
wise. All tolerances are expressed in percent of the nominal
is based on the measured limiting voltage determined during
system voltage.
surgetesting.Alsoreferredtoasthesuppressionvoltagerating.
3.15 one-port transient voltage surge suppressor—ATVSS
3.27 voltage spike—A voltage spike is a voltage change of
having one set of electrical connections (terminals, leads and
veryshortduration(100µsto ⁄2cycle).Thestandard1.2/50-µs
the like) intended only for shunt-connection to the ac power
lightning impulse, as defined by ANSI/IEEE Std 4,isthe
circuit, such that load current in the ac power circuit bypasses
characteristic voltage spike used for test purposes.
the TVSS.
3.28 voltage tolerance—Voltage tolerance is the maximum
3.16 peak overshoot voltage—Maximum voltage above the
permitted departure from nominal system voltage during nor-
voltage protection level (peak voltage minus suppression
mal operation, excluding transient voltage variations. Voltage
voltage rating) across the suppressor output terminals during
tolerance includes variations such as those caused by load
initial response to a voltage spike.
changes, switchboard meter error, and drift. Unless otherwise
3.17 rated rms voltage (varistor)—Maximum continuous
specified, voltage tolerance shall be considered to be 610 % of
sinusoidal rms voltage which may be applied to a varistor.
nominal system voltage.
3.18 response time (varistor)—The time between the point
at which the wave exceeds the voltage protection level (sup- 4. Classification
pression voltage rating) and the peak of the voltage overshoot.
4.1 Surge suppressors covered in this specification shall be
For the purpose of this definition, voltage protection level is
classified by class and type.
defined with an 8/20-µs current waveform of the peak current
4.2 The two classes of surge suppressors covered in this
amplitude as the waveform used for this response time.
specification are based on and reflect ANSI/IEEE C62.41
3.19 secondary surge arrestor—A surge protector device
locations.
acceptable ahead of the service entrance equipment on circuits
4.2.1 Class A—Surge suppressor associated with long cir-
not exceeding 1000-Vrms (location category C as described in
cuitbranchthatbeinggreaterthan30-ftcabledistancefromthe
ANSI/IEEE C62.41).
distribution panel and usually installed as a series-connected
3.20 surge—Atransientovervoltagesuperimposedontheac
TVSS at the distribution system receptacle (wall outlet).
power circuit. A voltage surge is generally one in which the
4.2.2 Class B—Surge suppressor for short branch circuit,
superpositionofthesurgeandnormalpowerfrequencyvoltage
either installed at loads within 30-ft cable distance from the
involves peak voltage levels of twice or more the normal
circuit breaker distribution panel or within the distribution
voltage of the ac power system and generally lasting not more
panel.
than one-half period of the nominal system voltage waveform.
4.3 Type designations for surge suppressors covered in this
3.21 surge protective device (SPD)—A protective device specification are as follows:
composed of any combination of linear or non-linear circuit
4.3.1 Type I; Permanent Connected Type—A suppressor
elements and intended for limiting surge voltages on equip-
designedforhard-wiredorpanel-mountapplications.Thistype
ment by diverting or limiting surge current; it prevents contin-
surge suppressor is the only one-port-type TVSS.
ued flow of follow (power) current and is capable of repeating
4.3.2 Type II; Plug-In Type—A suppressor provided with
these functions as specified.
blades for direct connection at a receptacle and with integral
3.22 temporary overvoltage (TOV)—Avoltage swell from a output receptacle(s). By nature of its design, a plug-in suppres-
sor is inserted into the circuit as a series connection.
sudden change in voltage which goes outside the voltage
tolerance limits but does not exceed 120 % of nominal system 4.3.3 Type III; Cord-Connected Type—A suppressor that is
voltage and returns to and remains within these limits within 2 connected to a receptacle through a flexible cord that is
s after the initiation of the disturbance. permanently attached to the suppressor device. The cord shall
F1507 – 99 (2006)
be in accordance with requirements of UL 1449. Cord-
Inrush current 10 times rated current for 10
cycles
connected devices shall not have means for permanent mount-
Peak surge current 3000 A
ing.
Operating temperature −10 to 60°C
4.3.4 Type IV; Power Director (Power Center) Type—A Storage temperature −40 to 85°C
Minimum insulation resistance to 10 MV at 500 VDC
suppressor unit with two-pole main circuit breaker, a master
case
switch for controlling all receptacle outlets, and individual
Humidity resistance 0 to 100 %
switches for controlling all outlets.
Minimum life 2000 operations
A
5. Ordering Information
For two-port (plug-in and series-connected) suppressors only.
B
Measured line-to-line and line-to-neutral with an 8/20-µs, 3000-A peak wave-
5.1 Orders for suppressors under this specification shall
form per ANSI/IEEE C62.41 applied.
include the following:
7.2 Operating Requirements:
5.1.1 This specification number;
7.2.1 Protection modes for all two-port hybrid surge protec-
5.1.2 Nominal system voltage—120, 208, 240, and 480 V;
tive devices shall provide protection for common mode (line-
5.1.3 Frequency—50, 60, and 400 Hz;
to-ground and neutral-to-ground) and normal mode (line-to-
5.1.4 Service—single-phase, three-phase delta, three-phase
line) transients.
wye;
7.2.2 Fails to an open (versus short) circuit unless otherwise
5.1.5 Load current;
specified and provides indication (visual) of failure.
5.1.6 Surge suppressor—class and type;
7.2.3 Capable of installation into a dedicated container for
5.1.7 Protection modes;
mounting or as an assembly or component of a switchboard or
5.1.8 Voltage protection level (suppression rating), if
power supply.
known;
7.2.4 Maximum voltage drop for two-port devices at full
5.1.9 Quantity;
current/voltage shall not exceed 0.25 % of nominal system
5.1.10 Testing requirements—include only if tests other
voltage.
thantheproductiontestsrequiredbythisspecificationaretobe
7.3 Grounding Requirements:
performed;
7.3.1 The surge suppressor shall be provided with a means
5.1.11 Certification requirements; and
5.1.12 Packaging and shipping requirements. for grounding all exposed dead-metal parts that might become
energized. Grounding shall be accomplished in accordance
6. Materials and Manufacture
with the requirements of UL 1449.
7.3.2 Type I (permanently connected) suppressors requiring
6.1 Materials—All materials used in the construction of
these surge suppressors shall be of a quality suitable for the grounding shall have a field-wiring terminal or an insulated
ground lead that is intended solely for connection of a
purpose intended and shall conform to the requirements of this
grounding conductor.
specification.
6.1.1 All metallic enclosures shall be either painted or 7.3.3 The flexible cord of Types III and IV suppressors
coated with corrosion resistant material. which requires grounding shall have a grounding conductor
6.2 Manufacture—Plastic, when used, shall be a suitable connected to the suppressor enclosure. Type II, direct plug-in,
thermoplastic or thermosetting material so molded as to suppressors requiring grounding shall be provided with a
produce a dense solid structure, uniform in texture, finish, and grounding pin as one of the attachment plug contacts.
mechanical properties.
7.3.4 Any leads emanating from a suppressor are to be of
color coded insulated wire. The color green shall be used for
7. Requirements Requirements
the grounding conductor and shall not be used for any other
7.1 Performance Requirements: purpose.
7.4 Supplementary Protection:
7.4.1 Surge protective devices that are series-connected
Maximum continuous operating 110 % of nominal voltage
(Types II, III, and IV) shall have supplementary overcurrent
voltage
protection and overtemperature protection.
Temporary overvol
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.