Standard Practice for Calculating the Superimposed Load on Wood-frame Floor-Ceiling Assemblies for Standard Fire-Resistance Tests

SIGNIFICANCE AND USE
Test Methods E119, E1529, and other standard fire resistance test methods specify that throughout the fire-resistance test, a constant superimposed load shall be applied to a load-bearing test specimen to simulate a maximum load condition. This superimposed load shall be the maximum load allowed by design under nationally recognized structural design criteria for the tested floor configuration (that is, joist selection, spacing, and span).  
For this Practice, the nationally recognized structural design criteria to be used to determine the maximum load condition are those for allowable stress design in the NDS (National Design Specification for Wood Construction).
Alternatively, the standard fire resistance test methods shall be permitted to be conducted by applying a load less than the maximum allowable load in 4.1.1 for the tested configuration; however, these tests shall be identified in the test report as being conducted under restricted loading conditions.
This practice describes procedures for calculating the superimposed load to be applied in standard fire resistance tests of wood floor-ceiling assemblies. Practice D6513 provides a similar methodology for calculating the superimposed load on wood-frame walls.
Statements in either the fire resistance test method standard or the nationally recognized structural design standard supersede any procedures described by this practice.  
The NDS shall be reviewed to ensure calculations are in compliance with all applicable provisions of that standard.
SCOPE
1.1 This practice covers procedures for calculating the superimposed load required to be applied to load-bearing wood-frame floor-ceiling assemblies throughout standard fire-resistance tests.
1.2 These calculations determine the maximum superimposed load to be applied to the floor-ceiling assembly during the fire resistance test. The maximum superimposed load, calculated in accordance with nationally-recognized structural design criteria, shall be designed to induce the maximum allowable stress in the wood floor-ceiling fire test configuration being tested.
1.3 This practice is only applicable to those wood-frame floor-ceiling assemblies for which the nationally recognized structural design criteria are the NDS (National Design Specification for Wood Construction).
1.4 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.  
1.5 The values stated in inch-pound units are to be regarded as standard. No other units of measurement are included in this standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
14-Nov-2011
Technical Committee
Drafting Committee
Current Stage
Ref Project

Buy Standard

Standard
ASTM D7746-11 - Standard Practice for Calculating the Superimposed Load on Wood-frame Floor-Ceiling Assemblies for Standard Fire-Resistance Tests
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: D7746 − 11
StandardPractice for
Calculating the Superimposed Load on Wood-frame Floor-
Ceiling Assemblies for Standard Fire-Resistance Tests
This standard is issued under the fixed designation D7746; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope D6513Practice for Calculating the Superimposed Load on
Wood-frame Walls for Standard Fire-Resistance Tests
1.1 This practice covers procedures for calculating the
E119Test Methods for Fire Tests of Building Construction
superimposed load required to be applied to load-bearing
and Materials
wood-frame floor-ceiling assemblies throughout standard fire-
E176Terminology of Fire Standards
resistance tests.
E1529Test Methods for Determining Effects of Large Hy-
1.2 These calculations determine the maximum superim-
drocarbon Pool Fires on Structural Members and Assem-
posed load to be applied to the floor-ceiling assembly during
blies
the fire resistance test. The maximum superimposed load,
2.2 Other Standards:
calculated in accordance with nationally-recognized structural
NDSNational Design Specification for Wood Construction
design criteria, shall be designed to induce the maximum
NDS SupplementDesign Values for Wood Construction
allowablestressinthewoodfloor-ceilingfiretestconfiguration
being tested.
3. Terminology
1.3 This practice is only applicable to those wood-frame
3.1 Definitions—Definitions used in this practice are in
floor-ceiling assemblies for which the nationally recognized
accordance with Terminology D9 and Terminology E176,
structural design criteria are the NDS (National Design Speci-
unless otherwise indicated.
fication for Wood Construction).
3.2 Definitions of Terms Specific to This Standard:
1.4 The text of this standard references notes and footnotes
3.2.1 gross area, n—section area calculated from overall
whichprovideexplanatorymaterial.Thesenotesandfootnotes
actual dimensions of member.
(excluding those in tables and figures) shall not be considered
3.2.2 net section area, n—sectionareacalculatedbydeduct-
as requirements of the standard.
ing from the gross section area the projected area of all
1.5 Thevaluesstatedininch-poundunitsaretoberegarded
materials removed by boring, grooving, dapping, notching, or
asstandard.Nootherunitsofmeasurementareincludedinthis
other means.
standard.
3.2.3 superimposed load, n—the additional external load
1.6 This standard does not purport to address all of the
needed to be applied to the assembly to result in the calculated
safety concerns, if any, associated with its use. It is the
stresses within the assembly when any dead load of the
responsibility of the user of this standard to establish appro-
assembly itself is accounted for in the calculations.
priate safety and health practices and determine the applica-
bility of regulatory limitations prior to use.
4. Significance and Use
2. Referenced Documents
4.1 Test Methods E119, E1529, and other standard fire
resistance test methods specify that throughout the fire-
2.1 ASTM Standards:
resistancetest,aconstantsuperimposedloadshallbeappliedto
D9Terminology Relating to Wood and Wood-Based Prod-
a load-bearing test specimen to simulate a maximum load
ucts
condition. This superimposed load shall be the maximum load
allowed by design under nationally recognized structural
This practice is under the jurisdiction ofASTM Committee D07 on Wood and
design criteria for the tested floor configuration (that is, joist
is the direct responsibility of Subcommittee D07.05 on Wood Assemblies.
selection, spacing, and span).
Current edition approved Nov. 15, 2011. Published March 2012. DOI: 10.1520/
D7746–11.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on Available fromAmericanWood Council (AWC), 803 Sycolin Road, Suite 201,
the ASTM website. Leesburg, VA 20175, http://www.awc.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
D7746 − 11
4.1.1 For this Practice, the nationally recognized structural Reference design values: M, V, R , E, EI , and K for I-joists
r I min
design criteria to be used to determine the maximum load are given in the product literature, or code evaluation report.
condition are those for allowable stress design in the NDS
6.2 Design Value Adjustments—Reference design values
(National Design Specification for Wood Construction).
shall be multiplied by all applicable adjustment factors to
4.1.2 Alternatively,thestandardfireresistancetestmethods
determine the adjusted design values. Additional adjustments
shallbepermittedtobeconductedbyapplyingaloadlessthan
may be required to address special design considerations for
the maximum allowable load in 4.1.1 for the tested configura-
the specific member type. Not all factors may be applicable to
tion;however,thesetestsshallbeidentifiedinthetestreportas
all product types.
being conducted under restricted loading conditions.
6.2.1 Bending—F for rectangular sections and M for
b
4.2 This practice describes procedures for calculating the I-joists shall be multiplied by all applicable NDS adjustment
superimposedloadtobeappliedinstandardfireresistancetests factors including: C , C , C, C , C , C , C , C, C , C .
D M t L F V fu i r c
of wood floor-ceiling assemblies. Practice D6513 provides a 6.2.2 Compression parallel to the grain, F , shall be multi-
c
similar methodology for calculating the superimposed load on plied by all applicable NDS adjustment factors including: C ,
D
wood-frame walls. C , C, C , C, and C .
M t F i P
6.2.3 Shear parallel to grain—F for rectangular sections
v
4.3 Statements in either the fire resistance test method
and V for I-joists shall be multiplied by all applicable NDS
standardorthenationallyrecognizedstructuraldesignstandard
adjustment factors including: C , C , C, C.
D M t i
supersede any procedures described by this practice.
6.2.4 Tension parallel to grain, F, shall be multiplied by all
t
4.4 TheNDSshallbereviewedtoensurecalculationsarein
applicable NDS adjustment factors including: C , C , C, C ,
D M t F
compliance with all applicable provisions of that standard.
C.
i
6.2.5 Bearing:
5. Test Assumptions
6.2.5.1 Compression perpendicular-to-grain—F for rect-
c'
5.1 Floor Assembly—For design considerations, wood-
angular sections shall be multiplied by all applicable NDS
frame floor-ceiling assemblies consist of horizontal structural
adjustment factors including: C , C, C, C .
M t i b
members(thatis,joists),thefloordeckingorsheathing,andthe
6.2.5.2 I-joist Reference Design Reaction—R ,shallbemul-
r
perimeter rim boards.
tipliedbyallapplicableNDSadjustmentfactorsincluding: C ,
D
C , C.
5.2 Loading Conditions—Horizontal framing members sup-
M t
6.2.6 Modulus of elasticity—E or E for rectangular sec-
port a vertical load that is uniformly distributed on the floor
min
tions and E and EI for I-joists shall be multiplied by all
assembly.Itisassumedthatloadapplicationsystemforthetest
I min
applicable NDS adjustment factors including: C , C, C, C .
distributes load between and along framing members in a
M t i T
manner consistent with a uniform load assumption and pro-
6.3 Adjustment Factors for Design Values—The following
vides load distribution to members that is representative of the
adjustment factors are to be assumed by default. If values less
end-use application.
thanthoselistedbelowareemployed,thentheappropriateload
restrictionshallbereportedinthetestreportandusedtoadjust
NOTE 1—The calculation procedure in this standard is not appropriate
the design bending and shear capacity in application:
for a test that uses a load application system that incorporates discrete
point load distribution beams or frames with spanning capabilities that
6.3.1 Load duration factor, C , is 1.0.
D
servetoartificiallyre-distributeloadfromafailingmembertotheadjacent
6.3.2 Wet service factor, C , is 1.0.
M
framing. Such a system would require a higher load to be applied that
6.3.3 Temperature factor, C, is 1.0.
t
considers the enhanced load-sharing between members provided by the
6.3.4 Beam stability factor, C , is 1.0 for a single span,
load frame and the departure from a uniform load condition.An example
L
of a system that conforms to the calculation assumption would be one in sheathed fire test assembly.
which each discrete load element (that is, dead weight pack, water barrel,
6.3.5 Size factor, C , is the value taken from tables in the
F
hydraulic cylinder, pneumatic cylinder, etc.) is applied to the floor at not
NDS Supplement for the sawn lumber joist material in the test
more than two locations along the length of the framing by distribution
assembly.
beams that span across not more than three framing members.
6.3.6 Volume factor, C , per NDS provisions for glued-
V
5.3 Lateral or torsional end support, including but not
laminated timber members. The value of C for structural
v
limited to bridging, blocking, or bracing, shall be provided at
composite lumber shall be defined by the product literature or
pointsofbearingtopreventrotation.Whenadditionallateralor
code evaluation report.The value of C used shall be the value
v
torsional support is used away from the ends to enhance
for the joist material in the test assembly.
performance of the
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.