Standard Practice for Installation of Thick Poured Lightweight Cellular Concrete Underlayments and Preparation of the Surface to Receive Resilient Flooring

SIGNIFICANCE AND USE
This practice provides minimum recommendations for the installation of thick poured lightweight cellular concrete floor underlayments suitable to receive resilient floor coverings. This practice establishes the proper preparation, installation and quality control for thick poured lightweight cellular concrete floor underlayments.
Actual requirements for thick poured lightweight cellular concrete underlayments are generally included as part of project plans or specifications and may vary from the recommendations set forth in this practice. Project plans or specifications, or both, shall supersede the recommendations set forth in this practice.
SCOPE
1.1 This practice covers the installation and preparation of the thick poured lightweight cellular concrete underlayments over wood structural panel subfloors in commercial structures or over concrete floors in commercial structures and the preparation of the thick poured lightweight cellular concrete underlayment surface prior to the installation of resilient flooring in commercial buildings.
1.2 This practice points out the factors that are required to be controlled while installing thick poured lightweight cellular concrete underlayment as a base for resilient flooring.
1.3 This practice does not cover the structural adequacy of the wood structural panel subfloor or concrete subfloor. The structural integrity of assemblies is governed by local building codes.
1.4 This practice does not supercede the thick poured lightweight cellular concrete underlayment manufacturers', adhesive manufacturers' or resilient flooring manufacturers' written instructions. Consult the individual manufacturer for specific recommendations.
1.5 Thick poured lightweight cellular concrete underlayments are not suitable for use on concrete slabs on ground due to potential moisture problems arising from moisture intrusion, unless an adequate vapor retarder or vapor barrier is present directly beneath the concrete subfloor.
1.6 The values stated in inch-pound units are to be regarded as standard. The values stated in parentheses are mathematical conversions to SI Units, which are provided for information only.
1.7  This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
30-Nov-2008
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM F2471-08 - Standard Practice for Installation of Thick Poured Lightweight Cellular Concrete Underlayments and Preparation of the Surface to Receive Resilient Flooring
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM F2471-08 - Standard Practice for Installation of Thick Poured Lightweight Cellular Concrete Underlayments and Preparation of the Surface to Receive Resilient Flooring
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM F2471-08 - Standard Practice for Installation of Thick Poured Lightweight Cellular Concrete Underlayments and Preparation of the Surface to Receive Resilient Flooring
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: F2471 − 08
StandardPractice for
Installation of Thick Poured Lightweight Cellular Concrete
Underlayments and Preparation of the Surface to Receive
1
Resilient Flooring
This standard is issued under the fixed designation F2471; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 2. Referenced Documents
2
1.1 This practice covers the installation and preparation of 2.1 ASTM Standards:
the thick poured lightweight cellular concrete underlayments C330 Specification for Lightweight Aggregates for Struc-
over wood structural panel subfloors in commercial structures tural Concrete
or over concrete floors in commercial structures and the F141 Terminology Relating to Resilient Floor Coverings
preparation of the thick poured lightweight cellular concrete F710 Practice for Preparing Concrete Floors to Receive
underlayment surface prior to the installation of resilient Resilient Flooring
flooring in commercial buildings. F2170 Test Method for Determining Relative Humidity in
Concrete Floor Slabs Using in situ Probes
1.2 This practice points out the factors that are required to
F1482 Practice for Installation and Preparation of Panel
be controlled while installing thick poured lightweight cellular
Type Underlayments to Receive Resilient Flooring
concrete underlayment as a base for resilient flooring.
1.3 This practice does not cover the structural adequacy of
3. Terminology
the wood structural panel subfloor or concrete subfloor. The
3.1 Definitions used in this practice shall be in accordance
structural integrity of assemblies is governed by local building
with Terminology F141.
codes.
3.2 Definitions of Terms Specific to This Standard:
1.4 This practice does not supercede the thick poured
3.2.1 fully adhered flooring, n—resilient flooring which has
lightweight cellular concrete underlayment manufacturers’,
adhesive under the entire product, bonding it to the underlay-
adhesive manufacturers’ or resilient flooring manufacturers’
ment surface (see Practice F1482).
written instructions. Consult the individual manufacturer for
3.2.2 non-fully adhered flooring, n—resilient flooring that
specific recommendations.
may be loose laid, in which no adhesive is utilized, or partially
1.5 Thick poured lightweight cellular concrete underlay-
bonded to the surface of the underlayment, typically at seams
ments are not suitable for use on concrete slabs on ground due
and the surrounding perimeter of the product (see Practice
to potential moisture problems arising from moisture intrusion,
F1482).
unless an adequate vapor retarder or vapor barrier is present
3.2.3 thick poured lightweight cellular concrete underlay-
directly beneath the concrete subfloor.
ment , n—thatlayerofmaterialcomposedprimarilyofPortland
1.6 The values stated in inch-pound units are to be regarded
cement (conforming to, Type I, II, or Block Cement) slurry,
as standard. The values stated in parentheses are mathematical
sand, water, pea gravel and foam that is mixed, pumped and
conversions to SI Units, which are provided for information 1
poured at a minimum thickness of 1 ⁄2 in. (38 mm) in a liquid
only.
state and installed on or over a subfloor to provide an
1.7 This standard does not purport to address all of the underlayment.
safety concerns, if any, associated with its use. It is the
3.2.4 wood structural panel, n—a panel manufactures from
responsibility of the user of this standard to establish appro-
veneers, or wood strands or wafers, or a combination of veneer
priate safety and health practices and determine the applica-
and wood strands, or wafers, bonded together with waterproof
bility of regulatory limitations prior to use.
synthetic resins or other suitable, waterproof bonding systems.
1
This practice is under the jurisdiction of ASTM Committee F06 on Resilient
2
Floor Coverings and is the direct responsibility of Subcommittee F06.40 on For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Practices. contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Current edition approved Dec. 1, 2008. Published January 2009. Originally Standards volume information, refer to the standard’s Document Summary page on
approved in 2005 as F2471-05. DOI: 10.1520/F2471-08. the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
F2471 − 08
4. Significance and Use and dead loads in compliance with the local building code and
the resilient flooring manufacturers installation requirements.
4.1
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:F2471–05 Designation:F2471–08
Standard Practice for
Installation of Thick Poured Lightweight Cellular Concrete
Underlayments and Preparation of the Surface to Receive
1
Resilient Flooring
This standard is issued under the fixed designation F 2471; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This practice covers the installation and preparation of the thick poured lightweight cellular concrete underlayments over
wood structural panel subfloors in commercial structures or over concrete floors in commercial structures and the preparation of
the thick poured lightweight cellular concrete underlayment surface prior to the installation of resilient flooring in commercial
buildings.
1.2 This practice points out the factors that are required to be controlled while installing thick poured lightweight cellular
concrete underlayment as a base for resilient flooring.
1.3 This practice does not cover the structural adequacy of the wood structural panel subfloor or concrete subfloor. The
structural integrity of assemblies is governed by local building codes.
1.4 This practice does not supercede the thick poured lightweight cellular concrete underlayment manufacturers’, adhesive
manufacturers’ or resilient flooring manufacturers’ written instructions. Consult the individual manufacturer for specific
recommendations.
1.5 Thick poured lightweight cellular concrete underlayments are not suitable for use on concrete slabs on ground due to
potential moisture problems arising from moisture intrusion, unless an adequate vapor retarder or vapor barrier is present directly
beneath the concrete subfloor.
1.6 The values stated in inch-pound units are to be regarded as standard. The values stated in parentheses are mathematical
conversions to SI Units, which are provided for information only.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
C 330 Specification for Lightweight Aggregates for Structural Concrete
F 141 Terminology Relating to Resilient Floor Coverings
F 710 Practice for Preparing Concrete Floors to Receive Resilient FloorsFlooring
F 2170 Test Method for Determining Relative Humidity in Concrete Floor Slabs Using in situ Probes
F 1482 Practice for Installation and Preparation of Panel Type Underlayments to Receive Resilient Flooring
3. Terminology
3.1 Definitions used in this practice shall be in accordance with Terminology F 141.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 fully adhered flooring, n—resilient flooring which has adhesive under the entire product, bonding it to the underlayment
surface (see Practice F 1482).
3.2.2 non-fully adhered flooring, n—resilient flooring that may be loose laid, in which no adhesive is utilized, or partially
bonded to the surface of the underlayment, typically at seams and the surrounding perimeter of the product (see Practice F 1482).
3.2.3 subfloor, n—that wood structural panel or concrete layer intended to provide support for design loads, which may receive
resilient floor coverings directly if the surface is appropriate or indirectly via an underlayment if its surface is not suitable or if
1
This practice is under the jurisdiction of ASTM Committee F06 on Resilient Floor Coverings and is the direct responsibility of Subcommittee F06.40 on Practices.
Current edition approved June 1, 2005. Published July 2005.
Current edition approved Dec. 1, 2008. Published January 2009. Originally approved in 2005 as F 2471-05.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
F2471–08
underlayment is required by appropriate code authorities.
3.2.4thick poured lightweight cellular concrete underlayment , n—that layer of material composed primarily o
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:F2471–05 Designation:F2471–08
Standard Practice for
Installation of Thick Poured Lightweight Cellular Concrete
Underlayments and Preparation of the Surface to Receive
1
Resilient Flooring
This standard is issued under the fixed designation F 2471; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This practice covers the installation and preparation of the thick poured lightweight cellular concrete underlayments over
wood structural panel subfloors in commercial structures or over concrete floors in commercial structures and the preparation of
the thick poured lightweight cellular concrete underlayment surface prior to the installation of resilient flooring in commercial
buildings.
1.2 This practice points out the factors that are required to be controlled while installing thick poured lightweight cellular
concrete underlayment as a base for resilient flooring.
1.3 This practice does not cover the structural adequacy of the wood structural panel subfloor or concrete subfloor. The
structural integrity of assemblies is governed by local building codes.
1.4 This practice does not supercede the thick poured lightweight cellular concrete underlayment manufacturers’, adhesive
manufacturers’ or resilient flooring manufacturers’ written instructions. Consult the individual manufacturer for specific
recommendations.
1.5 Thick poured lightweight cellular concrete underlayments are not suitable for use on concrete slabs on ground due to
potential moisture problems arising from moisture intrusion, unless an adequate vapor retarder or vapor barrier is present directly
beneath the concrete subfloor.
1.6 The values stated in inch-pound units are to be regarded as standard. The values stated in parentheses are mathematical
conversions to SI Units, which are provided for information only.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
C 330 Specification for Lightweight Aggregates for Structural Concrete
F 141 Terminology Relating to Resilient Floor Coverings
F 710 Practice for Preparing Concrete Floors to Receive Resilient FloorsFlooring
F 2170 Test Method for Determining Relative Humidity in Concrete Floor Slabs Using in situ Probes
F 1482 Practice for Installation and Preparation of Panel Type Underlayments to Receive Resilient Flooring
3. Terminology
3.1 Definitions used in this practice shall be in accordance with Terminology F 141.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 fully adhered flooring, n—resilient flooring which has adhesive under the entire product, bonding it to the underlayment
surface (see Practice F 1482).
3.2.2 non-fully adhered flooring, n—resilient flooring that may be loose laid, in which no adhesive is utilized, or partially
bonded to the surface of the underlayment, typically at seams and the surrounding perimeter of the product (see Practice F 1482).
3.2.3 subfloor, n—that wood structural panel or concrete layer intended to provide support for design loads, which may receive
resilient floor coverings directly if the surface is appropriate or indirectly via an underlayment if its surface is not suitable or if
1
This practice is under the jurisdiction of ASTM Committee F06 on Resilient Floor Coverings and is the direct responsibility of Subcommittee F06.40 on Practices.
Current edition approved June 1, 2005. Published July 2005.
Current edition approved Dec. 1, 2008. Published January 2009. Originally approved in 2005 as F 2471-05.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
F2471–08
underlayment is required by appropriate code authorities.
3.2.4thick poured lightweight cellular concrete underlayment , n—that layer of material composed primarily o
...