Standard Specification for Folded Poly(Vinyl Chloride) (PVC) Pipe for Existing Sewer and Conduit Rehabilitation

SCOPE
1.1 This specification covers requirements and test methods for materials, dimensions, workmanship, flattening resistance, impact resistance, pipe stiffness, extrusion quality, and a form of marking for folded (vinyl chloride) (PVC) pipe for existing sewer and conduit rehabilitation.
1.2 Pipe produced to this specification is for use in non-pressure sewer and conduit rehabilitation where the folded PVC pipe is inserted into and then expanded to conform to the wall of the original conduit forming a new structural pipe-within-a-pipe.  
Note 1-An ASTM specification for the installation of folded PVC pipe is under preparation and will be referenced in this specification when published.  
1.3 This specification includes pipe made only from materials specified in Section 6. This specification does not include pipe manufactured from reprocessed, recycled, or reclaimed PVC.
1.4 The values stated in inch-pound units are to be regarded as the standard. The SI units given in parentheses are provided for information only.
1.5 The following precautionary statement pertains to the test method portion only, Section 11, of this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
09-Aug-1997
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM F1504-97 - Standard Specification for Folded Poly(Vinyl Chloride) (PVC) Pipe for Existing Sewer and Conduit Rehabilitation
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

Designation: F 1504 – 97 An American National Standard
AMERICAN SOCIETY FOR TESTING AND MATERIALS
100 Barr Harbor Dr., West Conshohocken, PA 19428
Reprinted from the Annual Book of ASTM Standards. Copyright ASTM
Standard Specification for
Folded Poly(Vinyl Chloride) (PVC) Pipe for Existing Sewer
1
and Conduit Rehabilitation
This standard is issued under the fixed designation F 1504; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope D 1600 Terminology for Abbreviated Terms Relating to
2
Plastics
1.1 This specification covers requirements and test methods
D 1784 Specification for Rigid Poly(Vinyl Chloride) (PVC)
for materials, dimensions, workmanship, flattening resistance,
Compounds and Chlorinated Poly(Vinyl Chloride)
impact resistance, pipe stiffness, extrusion quality, and a form
2
(CPVC) Compounds
of marking for folded (vinyl chloride) (PVC) pipe for existing
D 2122 Test Method of Determining Dimensions of Ther-
sewer and conduit rehabilitation.
3
moplastic Pipe and Fittings
1.2 Pipe produced to this specification is for use in non-
D 2152 Test Method for Degree of Fusion of Extruded
pressure sewer and conduit rehabilitation where the folded
Poly(Vinyl Chloride) (PVC) Pipe and Molded Fittings by
PVC pipe is inserted into and then expanded to conform to the
3
Acetone Immersion
wall of the original conduit forming a new structural pipe-
D 2412 Test Method of Determination of External Loading
within-a-pipe.
3
Characteristics of Plastic Pipe by Parallel-Plate Loading
NOTE 1—An ASTM specification for the installation of folded PVC
D 2444 Test Method for Impact Resistance of Thermoplas-
pipe is under preparation and will be referenced in this specification when
3
tic Pipe and Fittings by Means of a Tup (Falling Weight)
published.
3
F 412 Terminology Relating to Plastic Piping Systems
1.3 This specification includes pipe made only from mate-
F 1057 Practice for Estimating the Quality of Extruded
rials specified in Section 6. This specification does not include
Poly(Vinyl Chloride) (PVC) Pipe by the Heat Reversion
pipe manufactured from reprocessed, recycled, or reclaimed 3
Technique
PVC.
2.2 Federal Standard:
4
1.4 The values stated in inch-pound units are to be regarded
Fed. Std. No. 123 Marking for Shipment (Civil Agencies)
as the standard. The SI units given in parentheses are provided
2.3 Military Standard:
4
for information only.
MIL-STD-129 Marking for Shipment and Storage
1.5 The following precautionary statement pertains to the
test method portion only, Section 11, of this specification: This 3. Terminology
standard does not purport to address all of the safety concerns,
3.1 General—Abbreviations used in this specification are in
if any, associated with its use. It is the responsibility of the user
accordance with Terminology D 1600 and definitions are in
of this standard to establish appropriate safety and health
accordance with Terminology F 412 unless otherwise indi-
practices and determine the applicability of regulatory limita-
cated.
tions prior to use.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 folded pipe—pipe that has been manufactured in a
2. Referenced Documents
folded shape for use in existing sewer and conduit rehabilita-
2.1 ASTM Standards:
tion. See Fig. 1.
D 618 Practice for Conditioning Plastics and Electrical
3.2.2 rounded pipe—A rounded pipe is a sample for test
2
Insulating Materials for Testing
purposes formed when the folded pipe has been inserted into a
D 790 Test Methods for Flexural Properties of Unreinforced
circular casing pipe and expanded with heat and pressure to fit
and Reinforced Plastics and Electrical Insulating Materi-
tightly to the casing pipe taking a circular cross section, in
2
als
accordance with Section 10. See Fig. 1.
4. Significance and Use
4.1 The requirements of this specification are intended to
1
This specification is under the jurisdiction of ASTM Committee F-17 on Plastic
provide folded pipe suitable for the rehabilitation of existing
Piping Systems and is the direct responsibility of Subcommittee F17.67 on
Trenchless Plastic Pipeline Technology.
3
Current edition approved Aug. 10, 1996. Published November 1997. Originally
Annual Book of ASTM Standards, Vol 08.04.
4
published as F 1504 – 94. Last previous edition F 1504 – 96.
Available from Standardization Documents Order Desk, Bldg. 4 Section D, 700
2
Annual Book of ASTM Standards, Vol 08.01.
Robbins Ave., Philadelphia, PA 19111-5094, Attn: NPODS.
1

---------------------- Page: 1 ----------------------
F 1504
ting, cracking, or breaking when the rounded pipe is tested in
accordance with 11.3.
7.2 Pipe Impact Strength—The impact strength of the
rounded pipe shall not be less than the values given in Table 2
when tested in accordance with 11.4.
NOT
...