Standard Guide for Extension of Data From Fire Resistance Tests Conducted in Accordance with ASTM E 119

SIGNIFICANCE AND USE
4.1 The methods and procedures set forth in this guide relate to the extension of the fire resistance ratings obtained from particular fire tested specimens to constructions that have not been tested.  
4.2 Users of this guide must have knowledge and understanding of the provisions of Test Method E119 including those pertaining to conditions of acceptance.  
4.3 In order to apply some of the principles described in this guide, reference to the original fire test report will be necessary.  
4.4 In Test Method E119, the specimens are subjected to specific laboratory fire test exposure conditions. Substitution of different test conditions or changes in the end use conditions have the ability to change the measured fire-test-response characteristics. Therefore, the extensions of data are valid only for the fire test exposure conditions described in Test Method E119,.
SCOPE
1.1 This guide covers the extension of fire resistance ratings obtained from fire tests performed in accordance with Test Method E119 to constructions that have not been tested. Test Method E119 evaluates the duration for which test specimens will contain a fire, retain their standard integrity, or both during a predetermined test exposure.  
1.2 This guide is based on principles involving the extension of test data using simple considerations. The acceptance of these principles and their application is based substantially on an analogous worst case proposition.  
1.3 These principles are only applicable to temperature conditions represented by the standard time-temperature curve described in Test Method E119. Test Method E119 is a fire-test-response standard.  
1.4 The types of building constructions which are the subject of this guide are categorized as follows: beams; floor and roof assemblies; columns; and walls and partitions. Floor and roof assemblies include such assemblies with ceiling protective membranes.  
1.5 The extension of test data using numerical calculations based on empirical data or theoretical models is not covered in this guide.  
1.6 This guide does not cover the substitution of one proprietary material for another proprietary material, or materials for which fire test data are not presently available.  
1.7 This guide does not purport to be comprehensive in its treatment of non-proprietary modifications of tested constructions. Engineering evaluation or tests are recommended for assessing modifications not specifically covered in this guide.  
1.8 The values stated in SI units are to be regarded as standard.  
1.9 This standard is used to determine certain fire-test responses of materials, products, or assemblies to heat and flame under controlled conditions by using results obtained from fire-test-response standards. The results obtained from using this standard do not by themselves constitute measures of fire hazard or fire risk.  
1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Jul-2013
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Guide
ASTM E2032-09(2013) - Standard Guide for Extension of Data From Fire Resistance Tests Conducted in Accordance with ASTM E 119
English language
10 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E2032 − 09 (Reapproved 2013) An American National Standard
Standard Guide for
Extension of Data From Fire Resistance Tests Conducted in
Accordance with ASTM E 119
This standard is issued under the fixed designation E2032; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 1.9 This standard is used to determine certain fire-test
responses of materials, products, or assemblies to heat and
1.1 This guide covers the extension of fire resistance ratings
flame under controlled conditions by using results obtained
obtained from fire tests performed in accordance with Test
from fire-test-response standards. The results obtained from
Method E119 to constructions that have not been tested. Test
using this standard do not by themselves constitute measures of
Method E119 evaluates the duration for which test specimens
fire hazard or fire risk.
will contain a fire, retain their standard integrity, or both during
1.10 This standard does not purport to address all of the
a predetermined test exposure.
safety concerns, if any, associated with its use. It is the
1.2 This guide is based on principles involving the exten-
responsibility of the user of this standard to establish appro-
sionoftestdatausingsimpleconsiderations.Theacceptanceof
priate safety and health practices and determine the applica-
these principles and their application is based substantially on
bility of regulatory limitations prior to use.
an analogous worst case proposition.
2. Referenced Documents
1.3 These principles are only applicable to temperature
2.1 ASTM Standards:
conditions represented by the standard time-temperature curve
C168 Terminology Relating to Thermal Insulation
described in Test Method E119. Test Method E119 is a
C553 Specification for Mineral Fiber Blanket Thermal Insu-
fire-test-response standard.
lation for Commercial and Industrial Applications
1.4 The types of building constructions which are the
C612 Specification for Mineral Fiber Block and Board
subject of this guide are categorized as follows: beams; floor
Thermal Insulation
and roof assemblies; columns; and walls and partitions. Floor
E119 Test Methods for Fire Tests of Building Construction
and roof assemblies include such assemblies with ceiling
and Materials
protective membranes.
E176 Terminology of Fire Standards
1.5 The extension of test data using numerical calculations E631 Terminology of Building Constructions
based on empirical data or theoretical models is not covered in E1264 Classification for Acoustical Ceiling Products
this guide. E1513 Practice for Application of Sprayed Fire-Resistive
Materials (SFRMs)
1.6 This guide does not cover the substitution of one
proprietary material for another proprietary material, or mate-
3. Terminology
rials for which fire test data are not presently available.
3.1 Definitions:
1.7 This guide does not purport to be comprehensive in its
3.1.1 For definitions used in this guide, refer to Terminolo-
treatment of non-proprietary modifications of tested construc-
gies E176, C168, E631, and Test Method E119.
tions. Engineering evaluation or tests are recommended for
3.1.2 mineral fiber insulation, n—insulation composed prin-
assessing modifications not specifically covered in this guide.
cipally of fibers manufactured from rock, slag, or glass
processed from molten state into fibrous form to comprise
1.8 The values stated in SI units are to be regarded as
flexiblebattsorblankets,rigidorsemi-rigidblocksandboards,
standard.
or loose fill insulations, with or without binder.
3.1.2.1 Discussion—Mineral fiber blanket thermal insula-
tions and mineral fiber block and board thermal insulations are
This standard guide is under the jurisdiction ofASTM Committee E05 on Fire
Standards and is the direct responsibility of Subcommittee E05.11 on Fire
Resistance. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved Aug. 1, 2013. Published September 2013. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 1999. Last previous edition approved in 2009 as E2032–09. DOI: Standards volume information, refer to the standard’s Document Summary page on
10.1520/E2032-09R13. the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E2032 − 09 (2013)
classified into various types based upon the maximum use 3.2.13 non-composite, n—as applied to loadbearing
temperature, which can range from 204°C (400°F) to 982°C elements,structuralinteractionbetweencontiguouselementsis
(1800°F), and the apparent thermal conductivity (See Specifi- assumed not to exist in the evaluation of load capacity.
cations C553 and C612).
3.2.14 sand-lightweight concrete, n—concrete made with a
combination of expanded clay, shale, slag, or slate or sintered
3.1.3 unit weight, n—as applied to concrete, weight per unit
fly ash and natural sand and generally weighing between 1680
volume.
and 1920 kg/m (105 to 120 pcf).
3.2 Definitions of Terms Specific to This Standard:
3.2.15 specified load, n—as applied to loadbearing
3.2.1 acoustical ceiling panel, n—a form of a prefabricated
elements, the test load applied to the element in a Test Method
sound absorbing ceiling element used with exposed suspension
E119 test.
systems (see Specification E1264).
3.2.15.1 Discussion—In Test Method E119 testing, the
3.2.2 acoustical ceiling tile, n—a form of a prefabricated
specified load is generally the design load (see 3.2.6).
sound absorbing ceiling element used with concealed or
3.2.16 test specimen, n—the specific construction assembly
semi-exposed suspension systems, stapling, or adhesive bond-
that was tested in accordance with Test Method E119.
ing (see Specification E1264).
3.2.17 transfer, n—the process of substituting a loadbearing
3.2.3 beams, n—all horizontally oriented structural mem-
element from one test specimen for the loadbearing element in
bersemployedinbuildingconstructionandknownvariouslyas
another test specimen, or utilizing a loadbearing element from
beams, joists, or girders.
onetestspecimenforuseinanothertestspecimenthatdoesnot
3.2.4 ceiling protective membrane, n—a ceiling membrane
include a loadbearing element.
attached to or suspended from the structural members of the
3.2.18 ultimate capacity, n—as applied to loadbearing
floor or ceiling assembly, usually by hanger wire or threaded
elements, the actual maximum load carrying capacity of an
rods, consisting of a grid suspension system with lay-in ceiling
element based on properties specific to the material constitut-
panels or a grid of steel furring channels to which the ceiling
ing the element.
membrane is directly attached, intended to provide fire
protection, acoustical and or aesthetic enhancements, or both.
4. Significance and Use
3.2.5 composite, n—as applied to loadbearing elements, an
4.1 Themethodsandproceduressetforthinthisguiderelate
interaction between structural components which is to be taken
to the extension of the fire resistance ratings obtained from
into account in the evaluation of load capacity.
particular fire tested specimens to constructions that have not
3.2.6 design load, n—the intended maximum design load
been tested.
condition allowed by design under appropriate nationally
4.2 Users of this guide must have knowledge and under-
recognized structural design criteria.
standingoftheprovisionsofTestMethodE119includingthose
3.2.7 directlyappliedfireresistivecoating,n—materialsthat
pertaining to conditions of acceptance.
are normally sprayed onto substrates to provide fire-resistive
4.3 In order to apply some of the principles described in this
protection of the substrates.
guide,referencetotheoriginalfiretestreportwillbenecessary.
3.2.7.1 Discussion—These coatings are called sprayed fire-
4.4 In Test Method E119, the specimens are subjected to
resistive materials in Standard Practice E1513 and related
specificlaboratoryfiretestexposureconditions.Substitutionof
standards.
different test conditions or changes in the end use conditions
3.2.8 equivalent thickness, n—the calculated solid thickness
have the ability to change the measured fire-test-response
of concrete or masonry for purposes of determining fire
characteristics. Therefore, the extensions of data are valid only
resistance ratings of barrier elements on the basis of heat
for the fire test exposure conditions described in Test Method
transmission end-point criteria.
E119,.
3.2.9 insulation, n—a material that is normally added to an
assembly to provide resistance to heat flow for purpose of
5. General Principles
energy conservation.
5.1 The same criteria or conditions of acceptance as set out
3.2.9.1 Discussion—Insulation materials are also used to
in the Test Method E119 and followed in the establishment of
improve sound control or improve fire resistance.
the fire resistance rating of the original test specimen shall be
3.2.10 lightweight aggregate concrete, n—concrete made used in the evaluation of the effect of the modification or
with aggregates of expanded clay, shale, slag, or slate or substitution of components in a test specimen.
sintered fly ash, and weighing 1360 to 1840 kg/m (85 to 115 5.1.1 The criteria or conditions of acceptance for the evalu-
ation of modified test specimens shall likewise be in accor-
pcf).
dance with the appropriate sections of Test Method E119.
3.2.11 material, generic, n—is one for which a nationally
recognized Standard Specification exists. 5.2 Statements in this guide only indicate whether a change
intheconstructioneither“canreduce”or“doesnotreduce”the
3.2.12 material proprietary, n—is one whose fire perfor-
fire resistance rating.
mance characteristics are determined in consideration of a
formulation or process of production that is proprietary. 5.3 Limitations:
E2032 − 09 (2013)
5.3.1 The extension of fire resistance ratings is valid only roof is not reduced in actual building constructions designed
for changes to the tested specimen that fall within normal and for either composite or non-composite action.
reasonable limits of standard construction practices.
5.5.2 Conversely, fire resistance ratings of beams and floors
5.3.2 Statements are valid only if the identified changes are or roofs tested in non-composite design shall be limited to
the only changes in the construction or properties of the building constructions designed for non-composite action.
components.
6. Principles Pertaining to Heat Transfer Characteristics
5.3.3 It is possible that multiple changes have a different
of Concrete
cumulative effect than that of individual changes applied
separately.
6.1 Theprovisionsinthissectionareapplicableonlyasthey
5.3.4 Unless otherwise indicated, statements are only valid
affect the transfer of heat through concrete. Considerations
if the change identified does not change the specified load.
involving structural fire resistance are addressed in other
5.3.4.1 Provisions in this guide involving the ratio of
sections.
specifiedloadtodesignloadassumethatthesafetyfactor(ratio
6.2 For concrete test specimens where temperature rise on
of ultimate capacity to design load) inherent in the design
the unexposed surface of a concrete slab (wall, floor, or roof)
procedure is constant.
is the governing criterion, the following modifications do not
5.3.4.2 Increasing the ratio of the maximum applied load
reduce the fire resistance rating of the assembly:
(specified load, dead plus live load) to the design load of an
6.2.1 Decrease in concrete unit weight;
element beyond that realized in the test specimen can reduce
6.2.2 Substitutionofsandedlight-weightaggregateconcrete
the fire resistance rating.
or light-weight aggregate concrete for normal weight concrete;
5.3.5 Provisions in this guide pertaining to concrete only
also, substitution of carbonate aggregate for siliceous aggre-
apply to concrete with a compressive strength of 55.1 MPa
gate for either the coarse or the fine aggregate used in the
(8000 psi) or less.
concrete;
5.4 Restrained/Unrestrained Specimens:
6.2.3 Decrease in the nominal maximum size of coarse
aggregate within a given concrete aggregate type;
5.4.1 The fire resistance rating of a beam, floor, or roof test
specimen is related to either a restrained or unrestrained
6.2.4 Increaseordecreaseinthecompressivestrengthofthe
condition, or both. A restrained condition in a fire test is concrete;
considered to be one in which the displacement or rotation due
6.2.5 Change in the type of portland cement, flyash or
to fire induced thermal expansion of a load bearing element is
admixtures used in the concrete;
resisted by forces external to the element. An unrestrained
6.2.6 Changes in the type or amount of reinforcement;
condition in a fire test is one in which the load bearing element
6.2.7 Increase in the equivalent thickness of the slab for a
is free to expand and rotate at its supports or is not subject to
given type of aggregate concrete; and
substantial thermal expansion and its resulting restraining
6.2.8 Changeinslabdesignorrestraintconditions,provided
forces.
the equivalent thickness of slab does not decrease.
5.4.2 Ratings of restrained beam, floor, or roof test speci-
6.2.9 In slabs or constructions incorporating joints other
mens are intended for application to elements which are
than construction joints, changes in joint design provided that
considered to be suitable for use in restrained building con-
the substituted joint design has been tested in a Test Method
struction where the surrounding or supporting structure is
E119 test and met the required fire resistance rating.
capable of resisting substantial thermal expansion throughout
6.2.10 For slabs containing hollow cores or air cavities,
the range of anticipated elevated fire conditions.
filling of cores or voids with non-combustible insulation
5.4.3 Ratings of unrestrained beam, floor or roof test speci-
material;
mens are intended for application to elements which are
6.3 For temperature rise to be the governing criteria, it is
considered to be suitable for use in unrestrained and restrained
assumed that the structural design requirements of the slab are
building construction where the surrounding or supporting
met and adequate cover protection is provided to the steel
structure is or is not capable of resisting substantial thermal
reinforcement (prestressing and reinforcing bars).
expansion throughout the range of anticipated elevated fire
conditions.
7. Principles Pertaining to Protective Finish Systems
5.4.3.1 The ap
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.