Standard Specification for Mineral Fiber Block and Board Thermal Insulation

SCOPE
1.1 This specification covers the classification, composition, dimension, and physical properties of mineral fiber (rock, slag, or glass) semirigid and rigid board insulation for the use on cooled surfaces and on heated surfaces up to 1800oF (982oC). For specific applications, the maximum and minimum temperature limits shall be agreed upon between the supplier and the purchaser.
1.2 The orientation of the fibers within the boards is primarily parallel to the principal surface (face). This specification does not cover fabricated pipe and tank wrap insulation where the insulation has been cut and fabricated to provide a fiber orientation that is perpendicular to the principal large surface (face).
1.3 For satisfactory performance, properly installed protective vapor retarders must be used in low-temperature (below ambient) applications to prevent movement of water vapor through or around the insulation towards the colder surface.
1.4 The values stated in inch-pound units are to be regarded as the standard. The SI equivalents of inch-pound units are given in parentheses for information only and may be approximate.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
09-Nov-2000
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C612-00 - Standard Specification for Mineral Fiber Block and Board Thermal Insulation
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
Designation: C 612 – 00
Standard Specification for
1
Mineral Fiber Block and Board Thermal Insulation
This standard is issued under the fixed designation C 612; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1. Scope C 303 Test Method for Density of Preformed Block-Type
2
Thermal Insulations
1.1 This specification covers the classification, composition,
C 356 Test Method for Linear Shrinkage of Preformed
dimension, and physical properties of mineral fiber (rock, slag,
High-Temperature Thermal Insulation Subjected to Soak-
or glass) semirigid and rigid board insulation for the use on
2
ing Heat
cooled surfaces and on heated surfaces up to 1800°F (982°C).
C 390 Criteria for Sampling and Acceptance of Preformed
For specific applications, the maximum and minimum tem-
2
Thermal Insulation Lots
perature limits shall be agreed upon between the supplier and
C 411 Test Method for Hot-Surface Performance of High-
the purchaser.
2
Temperature Thermal Insulation
1.2 The orientation of the fibers within the boards is
C 447 Practice for Estimating the Maximum Use Tempera-
primarily parallel to the principal surface (face). This specifi-
2
ture of Thermal Insulations
cation does not cover fabricated pipe and tank wrap insulation
C 518 Test Method for Steady-State Heat Flux Measure-
where the insulation has been cut and fabricated to provide a
ments and Thermal Transmission Properties by means of
fiber orientation that is perpendicular to the principal large
2
the Heat Flow Meter Apparatus
surface (face).
C 665 Specification for Mineral-Fiber Blanket Thermal In-
1.3 For satisfactory performance, properly installed protec-
sulation for Light Frame Construction and Manufactured
tive vapor retarders must be used in low-temperature (below
2
Housing
ambient) applications to prevent movement of water vapor
C 680 Practice for Determination of Heat Gain or Loss and
through or around the insulation towards the colder surface.
the Surface Temperatures of Insulated Pipe and Equipment
1.4 The values stated in inch-pound units are to be regarded
2
Systems by the Use of a Computer Program
as the standard. The SI equivalents of inch-pound units are
C 795 Specification for Thermal Insulation for Use in Con-
given in parentheses for information only and may be approxi-
2
tact with Austenitic Stainless Steel
mate.
C 1045 Practice for Calculating Thermal Transmission
1.5 This standard does not purport to address all of the
2
Properties Under Steady-State Conditions
safety concerns, if any, associated with its use. It is the
C 1058 Practice for Selecting Temperatures for Evaluating
responsibility of the user of this standard to establish appro-
2
and Reporting Thermal Properties of Thermal Insulation
priate safety and health practices and determine the applica-
C 1101/C 1101M Test Methods for Classifying the Flexibil-
bility of regulatory limitations prior to use.
ity or Rigidity of Mineral Fiber Blanket and Board
2
2. Referenced Documents
Insulation
C 1104/C 1104M Test Method for Determining the Water
2.1 ASTM Standards:
2
Vapor Sorption of Unfaced Mineral Fiber Insulation
C 165 Test Method for Measuring Compressive Properties
2
C 1114 Test Method for Steady-State Thermal Transmission
of Thermal Insulations
2
Properties by Means of the Thin-Heater Apparatus
C 168 Terminology Relating to Thermal Insulating Materi-
2
C 1136 Specification for Flexible, Low Permeance Vapor
als
2
Retarders for Thermal Insulation
C 177 Test Method for Steady-State Heat Flux Measure-
C 1304 Test Method for Assessing the Odor Emission of
ments and Thermal Transmission Properties by Means of
2
2
Thermal Insulation Materials
the Guarded-Hot-Plate Apparatus
C 1335 Test Method for Measuring the Non-Fibrous Con-
2
tent of Man-Made Rock and Slag Mineral Fiber Insulation
1
This specification is under the jurisdiction of ASTM Committee C-16 on
E 84 Test Method for Surface Burning Characteristics of
Thermal Insulation and is the direct responsibility of Subcommittee C16.20 on
3
Homogeneous Inorganic Thermal Insulation. Building Materials
Current edition approved Jan. 10, 2000. Published April 2000. Originally
published as C 612 – 67 T. Last previous edition C 612 – 93.
2 3
Annual Book of ASTM Standards, Vol 04.06. Annual Book of ASTM Standards, Vol 04.07.
Copyright © ASTM, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
C 612
3. Terminology 6.2 Facings:
6.2.1 The purchaser shall specify whether the insulation
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.