Standard Specification for Compressed Round Stranded Copper Conductors, Hard, Medium-Hard, or Soft Using Single Input Wire Construction

SCOPE
1.1 This specification covers stranded conductors made from round copper wires, either uncoated or coated with tin, lead, or lead alloy for general use in insulated conductor assemblies for electrical purposes. These conductors shall be composed of one or more roller shaped or die closed layers of helically laid wires using the single input wire (SIW) methodology. (see Note 1 and Explanatory Note 1)Note 1
Sealed conductors which are intended to prevent longitudinal water propagation and are further covered/insulated, are also permitted within the guidelines of this specification.
1.2 The values stated in inch-pound or SI units are to be regarded separately as standard. The values in each system are not exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the specification.
1.2.1 For density, resistivity, and temperature, the values stated in SI units are to be regarded as standard.

General Information

Status
Historical
Publication Date
31-Mar-2004
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM B902-04 - Standard Specification for Compressed Round Stranded Copper Conductors, Hard, Medium-Hard, or Soft Using Single Input Wire Construction
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: B 902 – 04
Standard Specification for
Compressed Round Stranded Copper Conductors, Hard,
1
Medium-Hard, or Soft Using Single Input Wire Construction
This standard is issued under the fixed designation B 902; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope Area of Stranded Conductors
B 354 Terminology Relating to Uninsulated Metallic Elec-
1.1 This specification covers stranded conductors made
trical Conductors
from round copper wires, either uncoated or coated with tin,
4
2.2 Other Standard:
lead, or lead alloy for general use in insulated conductor
NBS Handbook 100: Copper Wire Tables
assemblies for electrical purposes. These conductors shall be
composed of one or more roller shaped or die closed layers of
3. Classification
helically laid wires using the single input wire (SIW) method-
3.1 The conductors described in this specification are in-
ology. (see Note 1 and Explanatory Note 1)
tended for subsequent insulation or covering. The classification
NOTE 1—Sealed conductors which are intended to prevent longitudinal
of these conductors is SIW compressed.
water propagation and are further covered/insulated, are also permitted
within the guidelines of this specification.
4. Ordering Information
1.2 The values stated in inch-pound or SI units are to be
4.1 Orders for material under this specification shall include
regarded separately as standard. The values in each system are
the following information:
not exact equivalents; therefore, each system shall be used
4.1.1 Quantity of each size,
independently of the other. Combining values from the two
4.1.2 Conductor size: circular-mil area or AWG (see Section
systems may result in nonconformance with the specification.
7),
1.2.1 For density, resistivity, and temperature, the values
4.1.3 Class: SIW compressed (see 1.2 and Table 1),
stated in SI units are to be regarded as standard.
4.1.4 Temper (see 5.3),
4.1.5 Whether coated or uncoated; if coated (see 5.1 and
2. Referenced Documents
5.2).
2
2.1 ASTM Standards:
4.1.6 Details of special-purpose lays, if required (see 7.3).
B 1 Specification of Hard-Drawn Copper Wire
4.1.7 When physical tests shall be made (see 10.2 and 10.3).
B 2 Specification for Medium-Hard-Drawn Copper Wire
4.1.8 Package size (see 16.1).
B 3 Specification for Soft or Annealed Copper Wire
4.1.9 Lagging, if required (see 16.2).
B 33 Specification for Tinned Soft or Annealed Copper
4.1.10 Special package marking, if required (see Section
Wire for Electrical Purposes
16.3), and
B 189 Specification for Lead-Coated and Lead-Alloy-
4.1.11 Place of inspection (see Section 15).
3
Coated Soft Copper Wire for Electrical Purposes
5. Requirements for Wires
B 193 Test Method for Resistivity of Electrical Conductor
Materials
5.1 The purchaser shall designate the type of wire and the
B 246 Specification for Tinned Hard-Drawn and Medium-
kind of coating, if any, to be used in the conductor.
Hard-Drawn Copper Wire for Electrical Purposes
5.2 Before stranding, the copper wire used shall meet all of
B 263 Test Method for Determination of Cross-Sectional
the requirements of the following specifications of ASTM that
are applicable to its type:
5.2.1 Specification B 3,
1
This specification is under the jurisdiction of ASTM Committee B01 of
5.2.2 Specification B 33,
Electrical Conductors and is the direct responsibility of Subcommittee B01.04 on
5.2.3 Specification B 2,
Conductors of Copper Alloys.
Current edition approved April 1, 2004. Published April 2004. Orignally 5.2.4 Specification B 1,
approved in 2000. Last previous edition approved in 2000 as B 902 – 00.
5.2.5 Specification B 189, and
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
4
the ASTM website. Available from National Technical Information Service, 5285 Port Royal Road,
3
Withdrawn. Springfield, VA 22161.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
B902–04
TABLE 1 Construction Requirements of Compressed Round SIW Standard Copper Conductors
Compressed Strand Dimensions
Conductor Size Nominal Nominal
Diameter Diameter
of SIW of SIW
Minimum Compressed Compressed
Number of Conductor, Conductor, Mass DC Resistance at 20°C
2
cmils AWG mm Wires in. mm. lb/1000ft kg/km V/1000ft V/km
5 000 000 2534 217 2.424 61.57 15890 23649 0.00218 0.00715
4 500 000 2280 217 2.300 58.41 14300 21283 0.00242 0
...