Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 2: Test conditions

This part of EN 14511 specifies the test conditions for the rating of air and water cooled air conditioners, liquid chilling packages, air-to-air, water-to-air, air-to-water and water-to-water heat pumps with electrically driven compressors when used for space heating and/or cooling. It also specifies test conditions for heat recovery operation of multisplit systems.
This European Standard applies to factory made units that can be ducted.
This standard applies to factory made liquid chilling packages with integral condensers or for use with remote condensers.
This standard applies to factory-made units of either fixed capacity or variable capacity by any means.
Packaged units, single split and multisplit systems are covered by this standard. Single duct and double duct units are covered by the standard.
In the case of units consisting of several parts, the standard applies only to those designed and supplied as a complete package, except for liquid chilling packages with remote condenser.
This standard is primarily intended for water and brine chilling packages but can be used for other liquid subject to agreement.
This standard applies to air-to-air air conditioners which evaporate the condensate on the condenser side.
The units having their condenser cooled by air and by the evaporation of external additional water are not covered by this standard.
This standard does not apply to units using transcritical cycles, e.g. with CO2 as refrigerant.
Installations used for heating and/or cooling of industrial processes are not within the scope of this standard.
NOTE   Part load testing of units is dealt with in CEN/TS 14825.

Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und Kühlung - Teil 2: Prüfbedingungen

Dieser Teil der EN 14511 legt die Bedingungen für die Prüfung der Leistung von luft- und wassergekühlten Luftkonditionierern, Flüssigkeitskühlsätzen, Luft/Luft-, Wasser/Luft-, Luft/Wasser- und Wasser/Wasser-Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumheizung und/oder -kühlung fest. Er legt
ferner die Bedingungen für die Prüfung von Multi-Split-Systemen für die Wärmerückgewinnung fest.
Diese Europäische Norm gilt für fabrikmäßig zusammengebaute Geräte, die mit Luftkanalanschlüssen ver¬sehen sein können.
Diese Norm gilt für fabrikmäßig zusammengebaute Flüssigkeitskühlsätze, die mit eingebauten Verflüssigern oder mit getrennt angeordneten Verflüssigern betrieben werden.
Diese Norm gilt für fabrikmäßig zusammengebaute Geräte mit fest eingestellter oder durch beliebige Vorrichtungen zu verändernder Leistung (variable Leistung).
Kompaktgeräte, Einzelgeräte in Split-Bauweise und Multi-Split-Systeme fallen unter den Anwendungsbereich dieser Norm. Geräte mit Ein- und Zweikanal-Systemen werden ebenfalls in dieser Norm behandelt.
Wenn die Geräte aus mehreren Teilen bestehen, gilt diese Norm mit der Ausnahme von Flüssigkeitskühl¬sätzen mit getrennt angeordnetem Verflüssiger nur für die Teile, die als vollständige Baueinheit konstruiert und geliefert werden.
Diese Norm gilt hauptsächlich für Wasser- und Solekühlsätze, kann jedoch bei Vereinbarung auf weitere Flüssigkeitskühlsätze angewendet werden.
Diese Norm gilt für Luft/Luft-Luftkonditionierer, die das Kondensat auf der Verflüssigerseite verdampfen.
Geräte, deren Verflüssiger durch Belüftung und durch Verdampfung von zusätzlichem, von außen zuge¬führtem Wasser abgekühlt wird, werden in dieser Norm nicht behandelt.
Diese Norm gilt nicht für Geräte, bei denen, z. B. mit CO2 als Kältemittel, der Kreisprozess transzyklisch betrieben wird.
Anlagen für die Beheizung und/oder Kühlung industrieller Prozesse fallen nicht in den Anwendungsbereich dieser Norm.

Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 2: Conditions d'essai

La présente partie de l’EN 14511 spécifie les conditions d’essai pour la détermination des caractéristiques de
performance des climatiseurs à condensation par air et à condensation par eau, des groupes refroidisseurs
de liquide et des pompes à chaleur air/air, eau/air, air/eau et eau/eau, avec compresseur entraîné par moteur
électrique, lorsqu’ils sont utilisés pour le chauffage et/ou la réfrigération des locaux. Il spécifie aussi les
conditions d’essais pour le fonctionnement de la récupération de chaleur des systèmes multi-split.
La présente Norme européenne s’applique aux appareils fabriqués en usine qui peuvent être raccordés.
La présente norme s’applique aux groupes refroidisseurs de liquide autonomes fabriqués en usine ou conçus
pour être utilisés avec des condenseurs fournis séparément.
La présente norme s’applique aux appareils fabriqués en usine de capacité fixe ou variable par tous moyens.
La présente norme couvre les systèmes monoblocs, à deux éléments séparés et multi-split. La présente
norme couvre les appareils à simple et à double raccordement.
Dans le cas d’appareils à éléments séparés, la présente norme ne s’applique qu’aux appareils conçus et
fournis comme un ensemble, sauf pour ce qui concerne les groupes refroidisseurs de liquide avec
condenseur séparé.
La présente norme est principalement destinée aux groupes refroidisseurs d’eau et d’eau glycolée mais peut
être utilisée, après accord, pour d’autres liquides.
La présente norme s’applique aux climatiseurs air/air qui évaporent les condensats du côté condenseur.
La présente norme ne couvre pas les appareils ayant leur condenseur refroidi par air et par évaporation d’eau
d’un circuit supplémentaire externe.
La présente norme ne couvre pas les appareils utilisant des cycles transcritiques, par exemple avec CO2
comme fluide frigorigène.
La présente norme ne s’applique pas aux installations utilisées pour le chauffage et/ou le refroidissement des
procédés industriels.
NOTE Les e

Klimatske naprave, enote za tekočinsko hlajenje in toplotne črpalke z električnimi kompresorji za segrevanje in hlajenje prostora - 2. del: Preskusni pogoji

General Information

Status
Withdrawn
Publication Date
27-Nov-2007
Withdrawal Date
11-Oct-2011
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
12-Oct-2011
Completion Date
12-Oct-2011

Relations

Buy Standard

Standard
EN 14511-2:2008
English language
16 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und Kühlung - Teil 2: PrüfbedingungenClimatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 2: Conditions d'essaiAir conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 2: Test conditions91.140.30VLVWHPLVentilation and air-conditioning27.080Heat pumps23.120QDSUDYHVentilators. Fans. Air-conditionersICS:Ta slovenski standard je istoveten z:EN 14511-2:2007SIST EN 14511-2:2008en,fr,de01-maj-2008SIST EN 14511-2:2008SLOVENSKI
STANDARDSIST EN 14511-2:20041DGRPHãþD

EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 14511-2November 2007ICS 23.120Supersedes EN 14511-2:2004
English VersionAir conditioners, liquid chilling packages and heat pumps withelectrically driven compressors for space heating and cooling -Part 2: Test conditionsClimatiseurs, groupes refroidisseurs de liquide et pompes àchaleur avec compresseur entraîné par moteur électriquepour le chauffage et la réfrigération des locaux - Partie 2:Conditions d'essaiLuftkonditionierer, Flüssigkeitskühlsätze undWärmepumpen mit elektrisch angetriebenen Verdichternfür die Raumbeheizung und Kühlung - Teil 2:PrüfbedingungenThis European Standard was approved by CEN on 12 October 2007.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2007 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 14511-2:2007: ESIST EN 14511-2:2008

Energy labelling application.13 A.1 General.13 A.2 Rating conditions.13 A.2.1 General.13 A.2.2 Air-cooled air conditioners (air-to-air conditioners).13 A.2.3 Single-duct air conditioners.13 A.2.4 Water-cooled air conditioners (water-to-air conditioners).13 A.2.5 Double duct air conditioners.14 A.2.6 Other appliances.14 A.3 Test procedure.14 A.4 Tolerances permitted on declared values.14 A.4.1 General.14 A.4.2 First testing.14 A.4.3 Second testing.15 Bibliography.16
Table 1 — Environmental conditions for units designed for installation indoors Type Measured quantities Rating test Water-to-water units Dry bulb temperature 15 °C to 30 °C Air-to-water units with duct connection on the air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Air-to-water units without duct connection on the air inlet side Dry bulb temperature Wet bulb temperature
As inlet temperatures see Table 9 or Table 10 Water-to-air units with duct connection
on the air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Water-to-air units without duct connection on the air inlet and outlet side Dry bulb temperature Wet bulb temperature
As inlet temperatures see Table 5 or Table 6 Air-to-air units with duct connection
on the indoor air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Air-to-air units without duct connection
on the indoor air inlet and outlet side Dry bulb temperature Wet bulb temperature
As inlet temperatures see Table 3 or Table 4
Table 2 — Environmental conditions for units designed for installation outdoors Type Measured quantities Rating test Air-to-water units
Dry bulb temperature Wet bulb temperature As inlet temperatures see Table 9 and Table 10 Water-to-air units without duct connection on the air inlet side Dry bulb temperature Wet bulb temperature
As inlet temperatures see Table 5 and Table 6 Air-to-air units with duct connection on the indoor air inlet and outlet side Dry bulb temperature Wet bulb temperature
As inlet temperatures see Table 3 and Table 4
4.2 Rating conditions For the rating tests, the appropriate test conditions shall be applied in accordance with:  Table 3 for air-to-air units in heating mode;  Table 4 for air-to-air units in cooling mode;  Table 5 for water-to-air units in heating mode; SIST EN 14511-2:2008

Inlet dry bulb temperature°C Inlet wet bulb temperature°C Inlet dry bulb temperature °C Inlet wet bulb temperature°C Outside air / recycled air (e.g. window, double duct, split units) 7 6 20 15 max Exhaust air / recycled air 20 12 20 12 Standard rating
Conditions Exhaust air / outdoor air 20 12 7 6 Outside air / recycled air (e.g. window, double duct, split units) 2 1 20 15 max. Outside air / recycled air (e.g. window, double duct, split units) - 7 - 8 20 15 max. Outside air / recycled air (e.g. window, double duct, split units) - 15 - 20 15 max. Exhaust air / outdoor air 20 12 2 1 Application rating
conditions Exhaust air / outdoor air 20 12 - 7 - 8
Inlet dry bulb temperature°C Inlet wet bulb temperature°C Inlet dry bulb temperature °C Inlet wet bulb temperature°C Comfort (outside air / recycled air) (e.g. window, double duct, split units)
35 24 a 27 19 Comfort (exhaust air / recycled air) 27 19 27 19 Comfort (exhaust air / outdoor air) 27 19 35 24 Single duct b, c 35 24 35 24 Control cabinet 35 24 35 24 Standard rating
Conditions Close control 35 24 24 17 Comfort (outside air / recycled air) (e.g. window, double duct, split units)
27 19 a 21 15 Single duct b, c 27 19 27 19 Comfort (outside air / recycled air) (e.g. window, double duct, split units)
46 24 a 29 19 Co
...