CEN/TC 113 - Heat pumps and air conditioning units
Standardization of testing and requirements for the performance of factory assembled heat pumps, air conditioning units (ducted and non ducted), hydronic room fan coil units, and liquid chilling packages whether vapour compression or sorption, regardless of energy used, for domestic or commercial purposes excluding industrial processes and also excluding the rational use of gas energy which is within the scope of CEN/TC 299. Also the standardization of rating conditions, performance testing and the presentation of data of refrigerant compressors and condensing units.
Heat pumps and air conditioning units
Standardization of testing and requirements for the performance of factory assembled heat pumps, air conditioning units (ducted and non ducted), hydronic room fan coil units, and liquid chilling packages whether vapour compression or sorption, regardless of energy used, for domestic or commercial purposes excluding industrial processes and also excluding the rational use of gas energy which is within the scope of CEN/TC 299. Also the standardization of rating conditions, performance testing and the presentation of data of refrigerant compressors and condensing units.
General Information
This document establishes requirements for determining, in accordance with a standardized procedure, the sound power level emitted into the surrounding air by air conditioners, heat pumps, liquid chilling packages with electrically driven compressors when used for space heating and/or cooling, and/or for process, as described in the prEN 14511 series, and dehumidifiers, as described in EN 810.
This document also covers the measurement of the sound power level of evaporatively cooled condenser air conditioners, as defined in EN 15218. However, the measurement will be done without external water feeding and these units will thus be considered as the other air conditioners covered by the prEN 14511 series.
It is emphasized that this measurement standard only refers to airborne noise.
- Standard41 pagesEnglish languagesale 10% offe-Library read for1 day
This document is applicable to hydronic fan coil units (FCU) as factory-made single assemblies which provide the functions of cooling and/or heating but do not include the source of cooling or heating.
This document is applicable to both air free delivery and air ducted units with a maximum external static pressure due to duct resistance of 300 Pa max.
This document specifies methods for the determination of the acoustical performance of fan coil units, defining standard working condition and installation.
It is not the purpose of this document to specify the tests used for production or field testing.
NOTE For the purpose of remaining clauses, the term “unit” is used to mean “fan coil unit”.
- Standard24 pagesEnglish languagesale 10% offe-Library read for1 day
This document is applicable to air conditioners, heat pumps and liquid chilling packages, including comfort and process chillers. It applies to factory made units defined in EN 14511-1, except single duct, double duct, control cabinet and close control units. It also covers direct exchange-to-water(brine) heat pumps (DX-to-water(brine)) as defined in EN 15879-1.
This document also applies to hybrid units as defined in this standard.
This document specifies the temperatures, part load conditions and the calculation methods for the determination of seasonal energy efficiency SEER and SEERon, seasonal space cooling energy efficiency ηs,c, seasonal coefficient of performance SCOP, SCOPon and SCOPnet, seasonal space heating energy efficiency ηs,h and seasonal energy performance ratio SEPR.
Such calculation methods can be based on calculated or measured values.
In case of measured values, this document specifies the test methods for determination of capacities, EER and COP values during active mode at part load conditions. It also establishes test methods for power input during thermostat-off mode, standby mode, off mode and crankcase heater mode.
NOTE 1 The word "unit" is used instead of the full terms of the products.
NOTE 2 The word "heating" is used to refer to space heating.
- Standard137 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies methods for testing, rating of performance and calculation of water heating energy efficiency of air/water, brine/water, water/water and direct exchange/water heat pump water heaters and heat pump combination heaters with electrically driven compressors and connected to or including a domestic hot water storage tank for domestic hot water production.
This European Standard comprises only the testing procedure for the domestic hot water production of the heat pump system.
NOTE 1 Testing procedures for simultaneous operation for domestic hot water production and space heating are not treated in this standard. Simultaneous means that domestic hot water production and space heating generation occur at the same time and may interact.
NOTE 2 For heat pump combination heaters the seasonal efficiency of space heating is determined according to EN 14825.
This European Standard only applies to water heaters which are supplied in a package of heat pump and storage tank. In the case of water heaters consisting of several parts with refrigerant connections, this European Standard applies only to those designed and supplied as a complete package.
This European Standard does not specify requirements of the quality of the used water.
- Standard57 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the terms, definitions, test conditions, test methods and requirements for rating the performance of air conditioners and liquid chilling packages, with electrically driven compressors and with evaporatively cooled condenser when used for space cooling. The evaporatively cooled condenser is cooled by air and by the evaporation of external additional water. This additional external water is fed by a specific water supply circuit or by a water tank.
This document is not applicable to air-to-air and air-to-water air conditioners with a condenser cooled by air and by the evaporation of water condensed on their evaporator.
This document is applicable to units equipped with a water tank or with a continuous water circuit supply that can also operate without water feeding. However, this document only concerns the testing of these units with water feeding.
This document is applicable to factory-made units which can be ducted.
This document is applicable to factory-made units of either fixed capacity or variable capacity by any means.
Packaged units, single split and multisplit systems are covered by this document.
With regard to units consisting of several parts, this document applies only to those designed and supplied as a complete package.
For evaporatively cooled condenser units that can also operate in heating mode, their performance in this mode is determined according to EN 14511:2022 (all parts).
Units used for industrial processes cooling are not within the scope of this document.
This document specifies the conditions for which performance data will be declared for compliance with the Ecodesign Regulation 206/2012 and with the Energy Labelling Regulation 626/2011 of air conditioners with evaporatively cooled condenser in cooling mode.
NOTE All the symbols given in this text can be used regardless of language.
- Standard18 pagesEnglish languagesale 10% offe-Library read for1 day
1.1 The scope of EN 14511-1:2022 is applicable.
1.2 This document specifies the test methods for the rating and performance of air conditioners, liquid chilling packages and heat pumps using either air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and cooling. These test methods also apply for the rating and performance of process chillers.
It also specifies the method of testing and reporting for heat recovery capacities, system reduced capacities and the capacity of individual indoor units of multisplit systems, where applicable.
This document also makes possible to rate multisplit and modular heat recovery multisplit systems by rating separately the indoor and outdoor units.
- Standard88 pagesEnglish languagesale 10% offe-Library read for1 day
1.1 The scope of EN 14511-1:2022 is applicable, with the exception of process chillers.
1.2 This document specifies minimum operating requirements which ensure that air conditioners, heat pumps and liquid chilling packages using either air, water or brine as heat transfer media, with electrical driven compressors are fit for the use designated by the manufacturer when used for space heating and/or cooling.
- Standard14 pagesEnglish languagesale 10% offe-Library read for1 day
1.1 The scope of EN 14511-1:2022 is applicable.
1.2 This document specifies the test conditions for the rating of air conditioners, liquid chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. The document also specifies the test conditions for the rating of air-cooled and water(brine)-cooled process chillers.
1.3 This document specifies the conditions for which performance data are to be declared for single duct and double duct units for compliance to the Ecodesign Regulation 206/2012 and Energy Labelling Regulation 626/2011.
- Standard21 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the terms and definitions for the rating and performance of air conditioners, liquid chilling packages and heat pumps using either air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling.
It also specifies the terms and definitions for the rating and performance of process chillers.
This document does not apply to heat pumps for domestic hot water, although certain definitions can be applied to these.
This document applies to:
- factory-made units that can be ducted,
- factory-made liquid chilling packages with integral condensers or for use with remote condensers, and
- air-to-air air conditioners which can also evaporate the condensate on the condenser side.
Packaged units, single split and multisplit systems are covered by this document. Single duct and double duct units are covered by this document, as well.
In the case of units consisting of several parts, this document applies only to those designed and supplied as a complete package, except for liquid chilling packages with remote condenser.
This document is primarily intended for water and brine chilling packages but can be used for other liquid subject to agreement.
The units having their condenser cooled by air and by the evaporation of external additional water will have their performance in the cooling mode determined in accordance to EN 15218. For those which can also operate in the heating mode, the EN 14511 series applies for the determination of their performance in the heating mode.
NOTE 1 Part load testing of units is dealt with in EN 14825.
NOTE 2 All the symbols given in this text are used regardless of the language.
- Standard17 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard applies to hydronic fan coil units (FCU) as factory-made single assemblies which provide the functions of cooling and/or heating but do not include the source of cooling or heating.
The standard covers both air free delivery and air ducted units with a maximum external static pressure due to duct resistance of 120 Pa max.
The standard applies to all types of fan speed control of a fan coil unit (variable speed, multispeed).
This standard deals with the cooling and heating functions of the FCU considered as an emitter for cooling/heating of a room/space. It does not cover any ventilation function of the unit.
If the FCU can also provide fresh air, this function is not considered and the fresh air inlet closed during testing.
This European Standard provides a method for the determination of the thermal performance of fan coil units in standard conditions, for the use with hot or chilled water or water mixtures. The test procedures given in this standard may additionally be used for determining performance at other conditions.
It also provides the method for the determination of the air flow rate supplied by the fan coil unit.
The standard does not cover the rating of heating or cooling from direct expansion coils or heating from electric resistance elements.
The standard does not cover acoustic performance of fan coil units which is dealt with in EN 16583.
It is not the purpose of this standard to specify the tests used for production or field testing.
NOTE For the purpose of remaining clauses, the term “unit” is used to mean “fan coil unit” as defined in 3.1.
- Standard30 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies the rating conditions, tolerances and presentation of manufacturer's performance data for condensing units for refrigeration with compressors of the positive-displacement type. These include single stage compressors and single and two stage compressors having an integrated means of fluid sub cooling. This is required so that a comparison of different condensing units can be made. The data relate to the refrigerating capacity and power absorbed and include requirements for part-load performance where applicable.
- Standard21 pagesEnglish languagesale 10% offe-Library read for1 day
- Standard21 pagesEnglish languagesale 10% offe-Library read for1 day
- Standard21 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies methods for testing the sound power level of air/water, brine/water, water/water and direct exchange/water heat pump water heaters and heat pump combination heaters with electrically driven compressors and connected to or including a domestic hot water storage tank for domestic hot water production.
This European Standard comprises only the testing procedure for the domestic hot water production of the heat pump system.
NOTE 1 Testing procedures for simultaneous operation for domestic hot water production and space heating are not treated in this standard. Simultaneous operation means that domestic hot water production and space heating generation occur at the same time and may interact.
NOTE 2 For space heating function, the requirements are given in EN 12102-1:2017.
This European Standard only applies to water heaters which are supplied in a package of heat pump and storage tank. In the case of water heaters consisting of several parts with refrigerant connections, this European Standard applies only to those designed and supplied as a complete package.
This European Standard does not specify requirements for the quality of the used water.
- Standard34 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard applies only to condensing units for refrigeration and describes a number of selected performance test methods. These methods provide sufficiently accurate results for the determination of the refrigerating capacity, power absorbed, refrigerant mass flow and the coefficient of performance.
This European Standard applies only to performance tests conducted at the manufacturer's works or wherever the instrumentation and load stability for testing to the accuracy required is available.
- Standard30 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies performance test methods for refrigerant compressors. These methods provide sufficiently accurate results for the determination of the refrigerating capacity, power absorbed, refrigerant mass flow, isentropic efficiency and the coefficient of performance.
This European Standard applies only to performance tests where the equipment for testing is available.
- Standard39 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies the rating conditions, tolerances and the method of presenting manufacturer’s data for positive displacement refrigerant compressors. These include single stage compressors and single and two stage compressors using a means of fluid subcooling. This is required so that a comparison of different refrigerant compressors can be made. The data relate to the refrigerating capacity and power absorbed and include requirements for part-load performance where applicable.
- Standard14 pagesEnglish languagesale 10% offe-Library read for1 day
ISO/TS 16491:2012 gives guidance on the practical applications of the principles of performance measurement of air-cooled air-conditioners and air-to-air heat pumps as described in ISO 5151, ISO 13253, and ISO 15042.
- Technical report36 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies the terms and definitions, test conditions, test procedures and requirements for the rating and performance of direct exchange-to-water ground coupled heat pumps with electrically driven compressors, used for space heating and/or cooling. Brine can be used instead of water.
This European Standard applies to factory-made units with horizontal in-ground collectors. In the case of units consisting of several parts, this standard applies only to those designed and supplied as a complete package.
Water-to-direct exchange and direct-exchange-to-direct exchange ground coupled heat pumps are covered by EN 15879-2.
Direct exchange-to-air ground coupled heat pumps and air-to-direct exchange heat pumps are covered by EN 15879-3.
This European Standard does not apply to units using transcritical cycles, e.g. with CO2 as refrigerant.
- Standard24 pagesEnglish languagesale 10% offe-Library read for1 day
This standard specifies the methods for testing and reporting the rating and operational requirements and it specifies requirements for marking for dehumidifiers with electrically driven compressors. This standard does not apply to continuously variable capacity control units. In the case of dehumidifiers consisting of several parts, the standard applies only to those designed and supplied as a complete package.
- Standard20 pagesEnglish languagesale 10% offe-Library read for1 day
1.1 The scope of EN 14511-1:2022 is applicable.
1.2 This document specifies the test conditions for the rating of air conditioners, liquid chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. The document also specifies the test conditions for the rating of air-cooled and water(brine)-cooled process chillers.
1.3 This document specifies the conditions for which performance data are to be declared for single duct and double duct units for compliance to the Ecodesign Regulation 206/2012 and Energy Labelling Regulation 626/2011.
- Draft5 pagesEnglish languagesale 10% offe-Library read for1 day
1.1 The scope of EN 14511-1:2022 is applicable.
1.2 This document specifies the test methods for the rating and performance of air conditioners, liquid chilling packages and heat pumps using either air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and cooling. These test methods also apply for the rating and performance of process chillers.
It also specifies the method of testing and reporting for heat recovery capacities, system reduced capacities and the capacity of individual indoor units of multisplit systems, where applicable.
This document also makes possible to rate multisplit and modular heat recovery multisplit systems by rating separately the indoor and outdoor units.
- Draft4 pagesEnglish languagesale 10% offe-Library read for1 day
This document is applicable to hydronic fan coil units (FCU) as factory-made single assemblies which provide the functions of cooling and/or heating but do not include the source of cooling or heating.
This document is applicable to both air free delivery and air ducted units with a maximum external static pressure due to duct resistance of 300 Pa max.
This document specifies methods for the determination of the acoustical performance of fan coil units, defining standard working condition and installation.
It is not the purpose of this document to specify the tests used for production or field testing.
NOTE For the purpose of remaining clauses, the term "unit" is used to mean "fan coil unit".
- Draft4 pagesEnglish languagesale 10% offe-Library read for1 day
document specifies the terms and definitions, the test conditions and the test methods of air-sourced
and water-cooled roof-top units, driven by electric compressor(s), which may be equipped with a
supplementary heater using electrical resistance or combustion of fossil fuel.
This document covers roof-top units with 2, 3 or 4 dampers, including several features as the free-cooling,
mixing air flows (on both sides) and heat recovery.
This document deals with roof-top units providing space heating and/or cooling for comfort application.
Process applications are not covered by this document.
This document provides the part load conditions and the calculation methods taking into account roof-top
units features for the determination of seasonal energy efficiency SEER and SEERon, seasonal space
cooling energy efficiency ηs,c, seasonal coefficient of performance SCOP, SCOPon and SCOPnet,
seasonal space heating energy efficiency ηs,h and the overall annual efficiency.
Such calculation methods may be based on calculated or measured values.
In case of measured values, this document covers the test methods for determination of capacities, EER
and COP values during active mode at part load conditions. It also covers test methods for the
determination of power input during thermostat-off mode, standby mode, off-mode and crankcase heater
mode.
A roof-top unit that is not using at least the thermodynamic cycle for space heating is considered as a
cooling only unit.
Roof-top units equipped with additional air heating and/or cooling heat exchangers will be rated without
operation of these heat exchangers.
- Draft101 pagesEnglish languagesale 10% offe-Library read for1 day
This document is applicable to air conditioners, heat pumps and liquid chilling packages, including comfort and process chillers. It applies to factory made units defined in EN 14511-1, except single duct, double duct, control cabinet and close control units. It also covers direct exchange-to-water(brine) heat pumps (DX-to-water(brine)) as defined in EN 15879-1.
This document also applies to hybrid units as defined in this standard.
This document specifies the temperatures, part load conditions and the calculation methods for the determination of seasonal energy efficiency SEER and SEERon, seasonal space cooling energy efficiency ηs,c, seasonal coefficient of performance SCOP, SCOPon and SCOPnet, seasonal space heating energy efficiency ηs,h and seasonal energy performance ratio SEPR.
Such calculation methods can be based on calculated or measured values.
In case of measured values, this document specifies the test methods for determination of capacities, EER and COP values during active mode at part load conditions. It also establishes test methods for power input during thermostat-off mode, standby mode, off mode and crankcase heater mode.
NOTE 1 The word "unit" is used instead of the full terms of the products.
NOTE 2 The word "heating" is used to refer to space heating.
- Draft22 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the rating conditions, tolerances and the method of presenting performance data of refrigerant compressors.
This document is applicable to single stage compressor and two stage compressor data with or without an additional intermediate pressure inlet.
The performance data of compressors used with R-744 in transcritical operation are covered in this document.
The data relating to the refrigerating capacity, heating capacity and power absorbed include requirements for part load operation where applicable. Presenting performance in this way enables a comparison of different compressors.
- Draft19 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the terms and definitions, the test conditions and the test methods of air-sourced and water-cooled roof-top units, driven by electric compressor(s), which may be equipped with a supplementary heater using electrical resistance or combustion of fossil fuel.
This document covers roof-top units with 2, 3 or 4 dampers, including several features as the free-cooling, mixing air flows (on both sides) and heat recovery.
This document deals with roof-top units providing space heating and/or cooling for comfort application. Process applications are not covered by this document.
This document provides the part load conditions and the calculation methods taking into account roof-top units features for the determination of seasonal energy efficiency SEER and SEERon, seasonal space cooling energy efficiency ηs,c, seasonal coefficient of performance SCOP, SCOPon and SCOPnet, seasonal space heating energy efficiency ηs,h and the overall annual efficiency.
Such calculation methods may be based on calculated or measured values.
In case of measured values, this document covers the test methods for determination of capacities, EER and COP values during active mode at part load conditions. It also covers test methods for the determination of power input during thermostat-off mode, standby mode, off-mode and crankcase heater mode.
A roof-top unit that is not using at least the thermodynamic cycle for space heating is considered as a cooling only unit.
Roof-top units equipped with additional air heating and/or cooling heat exchangers will be rated without operation of these heat exchangers.
- Draft75 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies methods for testing, rating of performance and calculation of water heating energy efficiency of air/water, brine/water, water/water and direct exchange/water heat pump water heaters and heat pump combination heaters with electrically driven compressors and connected to or including a domestic hot water storage tank for domestic hot water production.
This European Standard comprises only the testing procedure for the domestic hot water production of the heat pump system.
NOTE 1 Testing procedures for simultaneous operation for domestic hot water production and space heating are not treated in this standard. Simultaneous means that domestic hot water production and space heating generation occur at the same time and may interact.
NOTE 2 For heat pump combination heaters the seasonal efficiency of space heating is determined according to EN 14825.
This European Standard only applies to water heaters which are supplied in a package of heat pump and storage tank. In the case of water heaters consisting of several parts with refrigerant connections, this European Standard applies only to those designed and supplied as a complete package.
This European Standard does not specify requirements of the quality of the used water.
- Draft12 pagesEnglish languagesale 10% offe-Library read for1 day
- Corrigendum3 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies methods for testing, rating of performance and calculation of water heating energy efficiency of air/water, brine/water, water/water and direct exchange/water heat pump water heaters and heat pump combination heaters with electrically driven compressors and connected to or including a domestic hot water storage tank for domestic hot water production.
This European Standard comprises only the testing procedure for the domestic hot water production of the heat pump system.
NOTE 1 Testing procedures for simultaneous operation for domestic hot water production and space heating are not treated in this standard. Simultaneous means that domestic hot water production and space heating generation occur at the same time and may interact.
NOTE 2 For heat pump combination heaters the seasonal efficiency of space heating is determined according to EN 14825.
This European Standard only applies to water heaters which are supplied in a package of heat pump and storage tank. In the case of water heaters consisting of several parts with refrigerant connections, this European Standard applies only to those designed and supplied as a complete package.
This European Standard does not specify requirements of the quality of the used water.
- Standard52 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies the terms, definitions, test conditions, test methods and requirements for rating the performance of air conditioners and liquid chilling packages, with electrically driven compressors and with evaporatively cooled condenser when used for space cooling. The evaporatively cooled condenser is cooled by air and by the evaporation of external additional water. This additional external water is fed by a specific water supply circuit or by a water tank.
This European Standard does not apply to air-to-air and air-to-water air conditioners with a condenser cooled by air and by the evaporation of water condensed on their evaporator.
This European Standard applies to units equipped with a water tank or with a continuous water circuit supply that can also operate without water feeding. However the standard only concerns the testing of these units with water feeding.
This European Standard applies to factory-made units which can be ducted.
This European Standard applies to factory-made units of either fixed capacity or variable capacity by any means.
Packaged units, single split and multisplit systems are covered by this European Standard.
With regard to units consisting of several parts, this European Standard applies only to those designed and supplied as a complete package.
Evaporatively cooled condenser units that can also operate in heating mode shall have their performance in this mode determined according to EN 14511.
Installations used for industrial processes cooling are not within the scope of this European Standard.
This European Standard specifies the conditions for which performance data shall be declared for compliance to the Ecodesign regulation 206/2012 and to the Energy Labelling regulation 626/2011 of air conditioners with evaporatively cooled condenser in cooling mode.
NOTE All the symbols given in this text can be used regardless of language.
- Standard17 pagesEnglish languagesale 10% offe-Library read for1 day
1.1 The scope of EN 14511 1 is applicable, with the exception of process chillers.
1.2 This European Standard specifies minimum operating requirements which ensure that air conditioners, heat pumps and liquid chilling packages using either air, water or brine as heat transfer media, with electrical driven compressors are fit for the use designated by the manufacturer when used for space heating and/or cooling.
- Standard14 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies the terms and definitions for the rating and performance of air conditioners, liquid chilling packages and heat pumps using either air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling.
It also specifies the terms and definitions for the rating and performance of process chillers.
This European Standard does not apply to heat pumps for domestic hot water, although certain definitions can be applied to these.
This European Standard applies to:
- factory-made units that can be ducted,
- factory-made liquid chilling packages with integral condensers or for use with remote condensers,
- factory-made units of either fixed capacity or variable capacity by any means, and
- air-to-air air conditioners which can also evaporate the condensate on the condenser side.
Packaged units, single split and multisplit systems are covered by this standard. Single duct and double duct units are covered by the standard.
In the case of units consisting of several parts, this European Standard applies only to those designed and supplied as a complete package, except for liquid chilling packages with remote condenser.
This European Standard is primarily intended for water and brine chilling packages but can be used for other liquid subject to agreement.
The units having their condenser cooled by air and by the evaporation of external additional water should have their performance in the cooling mode determined in accordance to EN 15218. For those which can also operate in the heating mode, the EN 14511 series applies for the determination of their performance in the heating mode.
NOTE 1 Part load testing of units is dealt with in EN 14825.
NOTE 2 All the symbols given in this text are used regardless of the language.
- Standard17 pagesEnglish languagesale 10% offe-Library read for1 day
1.1 The scope of EN 14511 1 is applicable.
1.2 This European Standard specifies the test conditions for the rating of air conditioners, liquid chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. The standard also specifies the test conditions for the rating of air-cooled and water(brine)-cooled process chillers.
1.3 This European Standard specifies the conditions for which performance data is to be declared for single duct and double duct units for compliance to the Ecodesign Regulation 206/2012 and Energy Labelling Regulation 626/2011.
- Standard21 pagesEnglish languagesale 10% offe-Library read for1 day
1.1 Es gilt der Anwendungsbereich von EN 14511-1.
1.2 Diese Europäische Norm legt die Prüfverfahren für die Bemessung und Leistung von Luftkondi-tionierern, Flüssigkeitskühlsätzen und Wärmepumpen, die Luft, Wasser oder Sole als Wärmeträger nutzen und mit elektrisch angetriebenen Verdichtern betrieben werden, für die Raumbeheizung und -kühlung fest. Diese Prüfverfahren gelten auch für die Bemessung und Leistung von Prozess-Kühlern.
Sie legt weiterhin ein Verfahren zur Prüfung und Angabe von Wärmerückgewinnungsleistungen, systemreduzierten Leistungen sowie der Leistung von Einzelgeräten von Multi-Split-Systemen für die Aufstellung im Innenraum, soweit zutreffend, fest.
Diese Europäische Norm bietet außerdem die Möglichkeit, die Leistung von Multi-Split-Systemen und modularen Multi-Split-Systemen mit Wärmerückgewinnung durch getrennte Leistungsbemessung von Geräten für die Aufstellung im Innenraum und Geräten für die Außenaufstellung (Innen- und Außengeräte) zu bemessen.
- Standard58 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard establishes requirements for determining, in accordance with a standardized procedure, the sound power level emitted into the surrounding air by air conditioners, heat pumps, liquid chilling packages with electrically driven compressors when used for space heating and/or cooling, and/or for process, as described in the EN 14511 series and dehumidifiers as described in EN 810.
This European Standard also covers the measurement of the sound power level of evaporatively cooled condenser air conditioners, as defined in EN 15218. However, the measurement will be done without external water feeding and these units will thus be considered as the other air conditioners covered by the EN 14511 series.
It is emphasized that this measurement standard only refers to airborne noise.
- Standard35 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard applies to hydronic fan coil units (FCU) as factory-made single assemblies which provide the functions of cooling and/or heating but do not include the source of cooling or heating.
The standard covers both air free delivery and air ducted units with a maximum external static pressure due to duct resistance of 120 Pa max.
This European Standard provides methods for the determination of the acoustical performance of fan coil units, defining standard working condition and installation.
It is not the purpose of this standard to specify the tests used for production or field testing.
NOTE For the purpose of remaining clauses, the term “unit” is used to mean “fan coil unit” as defined in 3.1 of FprEN 1397:2015.
- Standard22 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard covers air conditioners, heat pumps and liquid chilling packages, including comfort and process chillers. It applies to factory made units defined in EN 14511-1, except single duct, double duct, control cabinet and close control units. It also covers direct expansion-to-water(brine) heat pumps (DX-to-water) as defined in EN 15879-1.
This European Standard also covers hybrid heat pumps as defined in this standard.
This European Standard gives the temperatures and part load conditions and the calculation methods for the determination of seasonal energy efficiency SEER and SEERon, seasonal space cooling energy efficiency ηs,c seasonal coefficient of performance SCOP, SCOPon and SCOPnet, and seasonal space heating energy efficiency ηs,h and seasonal energy performance ratio SEPR.
Such calculation methods may be based on calculated or measured values.
In case of measured values, this European Standard covers the test methods for determination of capacities, EER and COP values during active mode at part load conditions. It also covers test methods for electric power consumption during thermostat-off mode, standby mode, off-mode and crankcase heater mode.
NOTE 1 The word "unit" is used instead of the full terms of the products.
NOTE 2 The word "cooling" is used to refer to both space cooling and process cooling.
NOTE 3 The word "heating" is used to refer to space heating.
- Standard133 pagesEnglish languagesale 10% offe-Library read for1 day
TC origin: mistake in Formula (4) (SV on 2016-06-10)
- Corrigendum2 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard applies to hydronic fan coil units (FCU) as factory-made single assemblies which provide the functions of cooling and/or heating but do not include the source of cooling or heating.
The standard covers both air free delivery and air ducted units with a maximum external static pressure due to duct resistance of 120 Pa max.
The standard applies to all types of fan speed control of a fan coil unit (variable speed, multispeed).
This standard deals with the cooling and heating functions of the FCU considered as an emitter for cooling/heating of a room/space. It does not cover any ventilation function of the unit.
If the FCU can also provide fresh air, this function is not considered and the fresh air inlet closed during testing.
This European Standard provides a method for the determination of the thermal performance of fan coil units in standard conditions, for the use with hot or chilled water or water mixtures. The test procedures given in this standard may additionally be used for determining performance at other conditions.
It also provides the method for the determination of the air flow rate supplied by the fan coil unit.
The standard does not cover the rating of heating or cooling from direct expansion coils or heating from electric resistance elements.
The standard does not cover acoustic performance of fan coil units which is dealt with in EN 16583.
It is not the purpose of this standard to specify the tests used for production or field testing.
NOTE For the purpose of remaining clauses, the term “unit” is used to mean “fan coil unit” as defined in 3.1.
- Standard26 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies the rating conditions, tolerances and presentation of manufacturer's performance data for condensing units for refrigeration with compressors of the positive-displacement type. These include single stage compressors and single and two stage compressors having an integrated means of fluid sub cooling. This is required so that a comparison of different condensing units can be made. The data relate to the refrigerating capacity and power absorbed and include requirements for part-load performance where applicable.
- Standard18 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard covers air conditioners, heat pumps and liquid chilling packages. It applies to factory made units defined in EN 14511-1, except single duct, double duct, control cabinet and close control units.
This European Standard gives the temperatures and part load conditions and the calculation methods for the determination of seasonal energy efficiency SEER and SEERon, seasonal coefficient of performance SCOP, SCOPon and SCOPnet, and seasonal space heating energy efficiency s.
Such calculation methods may be based on calculated or measured values.
In case of measured values, this European Standard covers the test methods for determination of capacities, EER and COP values during active mode at part load conditions. It also covers test methods for electric power consumption during thermostat-off mode, standby mode, off-mode and crankcase heater mode.
Note: The word unit is used instead of the full terms of the products.
- Standard85 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies the terms and definitions for the rating and performance of air conditioners, liquid chilling packages and heat pumps using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. This European Standard does not apply to heat pumps for domestic hot water, although certain definitions can be applied to these.
This European Standard applies to:
- factory-made units that can be ducted,
- factory-made liquid chilling packages with integral condensers or for use with remote condensers,
- factory-made units of either fixed capacity or variable capacity by any means, and
- air-to-air air conditioners which can also evaporate the condensate on the condenser side.
Packaged units, single split and multisplit systems are covered by this standard. Single duct and double duct units are covered by the standard.
In the case of units consisting of several parts, this European Standard applies only to those designed and supplied as a complete package, except for liquid chilling packages with remote condenser.
This European Standard is primarily intended for water and brine chilling packages but can be used for other liquid subject to agreement.
The units having their condenser cooled by air and by the evaporation of external additional water should have their performance in the cooling mode determined in accordance to EN 15218. For those which can also operate in the heating mode, EN 14511 applies for the determination of their performance in the heating mode.
Installations used for heating and/or cooling of industrial processes are not within the scope of this standard.
NOTE 1 Part load testing of units is dealt with in EN 14825.
NOTE 2 All the symbols given in this text are used regardless of the language used.
- Standard13 pagesEnglish languagesale 10% offe-Library read for1 day
1.1 The scope of EN 14511-1 is applicable.
1.2 This European Standard specifies minimum operating requirements which ensure that air conditioners, heat pumps and liquid chilling packages using either air, water or brine as heat transfer media, with electrical driven compressors are fit for the use designated by the manufacturer when used for space heating and/or cooling.
- Standard13 pagesEnglish languagesale 10% offe-Library read for1 day
1.1 The scope of EN 14511-1 is applicable.
1.2 This European Standard specifies the test conditions for the rating of air conditioners, liquid chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. It also specifies test conditions for heat recovery operation of multisplit systems.
1.3 This European Standard specifies the conditions for which performance data shall be declared for single duct and double duct units for compliance to the Ecodesign regulation 206/2012 and Energy labelling regulation 626/2011.
- Standard19 pagesEnglish languagesale 10% offe-Library read for1 day
1.1 The scope of EN 14511-1:2013 is applicable.
1.2 This European Standard specifies the test methods for the rating and performance of air conditioners, liquid chilling packages and heat pumps using either air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and cooling.
It also specifies the method of testing and reporting for heat recovery capacities, system reduced capacities and the capacity of individual indoor units of multisplit systems, where applicable.
This European Standard also makes possible to rate multisplit and modular heat recovery multisplit systems by rating separately the indoor and outdoor units.
- Standard55 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard establishes requirements for determining, in accordance with a standardized procedure, the sound power level emitted into the surrounding air by air conditioners, heat pumps, liquid chilling packages with electrically driven compressors when used for space heating and/or cooling, including water cooled multisplit systems, as described in EN 14511 and dehumidifiers as described in EN 810.
This European Standard also covers the measurement of the sound power level of evaporatively-cooled condenser air conditioners, as defined in EN 15218. However, the measurement should be done without external water feeding and these units will thus be considered as the other air conditioners covered by EN 14511.
It is emphasised that this measurement standard only refers to airborne noise.
This European Standard offers ways to determine the sound power level of units. Some of them are specifically adapted to provide results with low uncertainties, by using laboratory class acoustic methods and highly controlled working conditions. Those measurements are suitable for certification, labelling and marking purposes.
In some cases, the target and/or the environment of the measurements do not allow such precision-class methods. This European Standard also offers ways to assess sound power levels with acceptable accuracy even though acoustic methods and/or working conditions are not laboratory-type, e.g. in situ or quality control measurements.
This European Standard gives two classes of measurements and results, according to the test environment:
- Class A measurements correspond to controlled working conditions (standard or application rating conditions). It is defined by the respect to the tolerances of Table 2 and should be used for the conformity to requirements of the Commission Regulation (EC) No 206/2012 of 6 March 2012 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for air conditioners
- Class B measurements correspond to the case where the range defined by the tolerances of Table 2 cannot be fulfilled.
In both classes, precision or engineering class acoustic methods should be applied. The choice of the acoustic measurement method is done in accordance with EN ISO 3740 and EN ISO 9614 depending on the type of surrounding acoustic fields (diffuse or free field, enclosed or open space), and the available instrumentation. Whatever the current working conditions, the reference of acoustic standard should be reported, with explicit mention of its accuracy class.
The use of EN ISO 3746 and EN ISO 3747 as survey grade methods are not recommended due to the high level of uncertainties. Their use is only allowed for non controlled environments.
Three methods for determining the sound power levels are specified in order to avoid unduly restricting existing facilities and experience:
- the first methodology is based on reverberation room measurement (see EN ISO 3741, EN ISO 3743 and EN ISO 3747 in some favourable cases when the engineering grade can be fulfilled);
- the second method is based on measurements in an essentially free field over a reflecting plane (see EN ISO 3744 and EN ISO 3745);
- the third method is based on sound intensity measurement (see EN ISO 9614) in preferably free field environment.
The references in this European Standard to EN ISO 3743 should be understood as EN ISO 3743-1 or EN ISO 3743-2 as well.
The necessity to regulate the test conditions obviously leads to recommend test methods implemented in acoustically designed (enclosed) spaces, such as EN ISO 3741, EN ISO 3743, EN ISO 3745 and also EN ISO 9614 when implemented in an enclosed space.
The open spaces should be covered only in specific cases, e.g. when the size or the power of the unit under test cannot be managed by standard test rooms. Suitable test methods are EN ISO 3744 and EN ISO 9614.
- Standard25 pagesEnglish languagesale 10% offe-Library read for1 day
This part of EN 13771 applies only to condensing units for refrigeration and describes a number of selected performance test methods. These methods provide sufficiently accurate results for the determination of the refrigerating capacity, power absorbed, refrigerant mass flow and the coefficient of performance.
This European Standard applies only to performance tests conducted at the manufacturer's works or wherever the instrumentation and load stability for testing to the accuracy required is available.
The type of measuring instrument and the allowable uncertainties within which measurements shall be made are listed in Table 2.
- Standard25 pagesEnglish languagesale 10% offe-Library read for1 day
TC - Correction of the 1st hyphen in the 10th paragraph - Heating, cooling, ventilation and air conditing - Others
- Corrigendum2 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies methods for testing and reporting of the rating and it specifies requirements for marking of air/water, brine/water, water/water and direct exchange/water heat pumps with electrically driven compressors connected to or including a domestic hot water storage tank. When these units are used for space heating, then EN 14511 (all parts) applies.
In case of air-to-water heat pumps, this European Standard comprises only factory-made units which can be ducted on the airside.
This European Standard comprises only the testing procedure for the domestic hot water production of the heat pump system.
NOTE Testing procedures for simultaneous operation for domestic hot water production and space heating are not treated in this standard. Simultaneous means that domestic hot water production and space heating generation occur at the same time and may interact.
In the case of units consisting of several parts, the standard applies only to those designed and supplied as a complete package.
This European Standard does not include any requirement about the quality of water.
- Standard35 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies the rating conditions, tolerances and presentation of performance data for single-stage condensing units for refrigeration with compressors of the positive-displacement type. This is required so that a comparison of different condensing units can be made. The performance data relate to the refrigerating capacity and power absorbed, they include correction factors and refer to full load operation of the condensing unit.
- Standard7 pagesEnglish languagesale 10% offe-Library read for1 day
This part 1 of the European Standard applies only to refrigerant compressors and describes a number of selected performance test methods. These methods provide sufficiently accurate results for the determination of the refrigerating capacity, power absorbed, refrigerant mass flow, isentropic efficiency and the coefficient of performance. This standard applies only to performance tests conducted at the manufacturer's works or wherever the equipment for testing to the accuracy required is available. The type of measuring instrument and the limits within which measurements shall be made are listed in normative annex A.
- Standard26 pagesEnglish languagesale 10% offe-Library read for1 day